![ACT ACTPRO 3000 ACCESS CONTROL UNITS Скачать руководство пользователя страница 20](http://html.mh-extra.com/html/act/actpro-3000-access-control-units/actpro-3000-access-control-units_operating-and-installation-instructions_2842160020.webp)
AUX
Auxiliary relay (1) activates when the auxiliary relay is
AUX Any Door
activated for any door on the controller.
OP2
Open collector output OP2 (1) activates when a technical fault
Tech Fault
condition exists (tamper/mains fail/door offline).
OP3
Open collector output OP3 (1) activates when any door on the
Any Door Open
controller is open.
AUX
Auxiliary relay (2) activates when one or more users are logged
Users Present
in to the tracking area.
OP2
Open collector output OP2 (1) deactivates when the number of
User Limit A
users in a tracking area is at or above User Limit A.
OP3
Open collector output OP3 (1) deactivates when the number of
User Limit B
users in a tracking area is at or above User Limit B.
ACTpro 3000 Operating Instructions
Firmware Version 1.24
16
USER TRACKING
•
Doors maybe defined as
Perimeter
doors by pressing the
✔
key so that the door number is
displayed. Those not defined as a
Perimeter
door are displayed as -. Users that enter through a
perimeter door are tracked but not restricted. Tracking of a user means it is logged if the user is in
the tracking area or not. Entering through any perimeter doors logs the user into the area. Exiting
any perimeter door logs the user out of the area.
Note: If either Antipassback or Timed
Antipassback doors are defined then perimeter doors are ignored.
•
Doors maybe defined as
Antipassback
doors by pressing the
✔
key so that the door number is
displayed. Those not defined as
Antipassback
doors are displayed as -. The
Antipassback
doors
define the tracking area. Users are allowed entry to the area only if they have previously exited.
•
Doors may be defined as
Timed Antipassback
doors by pressing the
✔
key so that the door
number is displayed. Those not defined as
Timed Antipassback
doors are displayed as -.
Timed
Antipassback
doors define the tracking area. Users are allowed entry to the area only if they have
previously exited or after the
Timed Antipassback
period has expired. The
Timed Antipassback
period is defined on a user group basis.
Note: If a door is specified as an Antipassback door and
as a Timed Antipassback door, then the door will operate as a Timed Antipassback door.
•
Internal Doors
are doors that are inside the perimeter of the installation. Access is denied on these
doors if the cardholder has not already entered through the perimeter or Anti-passback doors
•
T
racking Reset
is used to auto-reset (log all users out) at a specific time each day, or may be reset
manually. In addition users may be individually logged in or out. This is recorded in the system
log.
•
Two
User Limits
A & B may be configured. These can be used to generate outputs when the
number of users in the area reaches a certain level. This may be used for certain security critical
areas. In addition an output may be configured to operate when any users are present within the
area. This could be used to switch on or off certain equipment when the area is empty. The larger
of the two limits is also used to determine how many tracked users to admit into the antipassback
area. Once this limit is reached, access is denied to other tracked users. This could be used in a
car-park application. User Limiting must be enabled for this to operate (see System Settings >
Operation).
OUTPUTS
The ACTpro 3000 has 6 onboard outputs that can operate in addition to the local relay. These are the
open collector outputs OP2 and OP3 (for doors 1 and 2) as well as the two auxiliary 1A relays. Normally
these outputs function as for any door, according to the programmed user and/or door settings. However
the onboard outputs on the ACTpro 3000 may be given alternate functions as outlined below.
Door 1
Door 2