Suburban Dynaline 3 A&E Manual 12/2021 Rev.2

9

The supplier will provide packaged terminal gas heat/electric air  

conditioner of the sizes and capacities shown on the schedule and listed  

in the specifications. Each unit shall consist of a chassis, wall case/sleeve, 

outside grille and room cabinet. Units shall be UL listed and/or  

ETL design certified and shall be Suburban Manufacturing Company 

DYNALINE

 3 models, or equivalents. The units shall be located as shown on 

the drawings.
Unit’s steady state efficiency shall be rated at 80% nominal and the EER 

of the air conditioner shall not be less than ASHRAE 90.1 - 2010 standards.
Units shall be designed to operate on 208/230 volts, 60 Hz, single 

phase power.
Unit dimensions shall not exceed 42" wide and 16" high without optional air 

discharge package in place, and not more than 22-29/32" from face of room 

cabinet to face of standard exterior grille.
Units shall be designed to operate on Natural or LP gas for the heating cycle.

CHASSIS:

 

Unit chassis shall be a standard product of the manufacturer and shall 

be packed to prevent damages when reasonable care is exercised during 

shipment. Warnings on packaging shall alert handlers to the hazards of 

improper handling or stacking.
Chassis shall slide into a standard-sized wall case and, after installation 

and testing, be ready to operate. Each chassis shall consist of the following 

system and components:
  •  Refrigeration system constructed to isolate the hermetically sealed 

    rotary-type compressor from external vibration. The system shall 

    include copper/aluminum condenser and evaporator coils with 

    capillary refrigerant control.
  •  Air flow system consists of a two-speed room air motor (for Hi &  

    Low A/C and Hi & Low heat speeds) and a fan cycle switch to permit 

    continuous indoor fan operation. A separate condenser fan operates in  

    the A/C cycle only. The condenser fan, not operating in the heating  

    mode, eliminates the potential for exhaust gases to  be drawn back and  

    freezing in the chassis compartment. The room air system incorporates 

    a tangential blower wheel for reduced noise and increased efficiency.
  •  Condenser coils, with not less than 13 fins per inch, and evaporator  

    coils, with not less than 11 fins per inch. Coils shall be constructed 

    of copper/aluminum and fins shall be bonded to tubes to prevent 

    electrolytic action.  
  •  Indoor and outdoor airflow which match the coil capacity for efficient  

    transfer of heat. Design of the unit shall prevent water blow-off on the  

    indoor evaporator coil. Indoor supply air grille, constructed of extruded 

    aluminum, shall discharge air at 52 degrees off vertical pattern.
  •  Electrostatic return air filter, constructed of washable media, that installs  

  and removes without tools.
  •  Factory-installed, gas-fired heat exchanger with electronic controlled,  

    pilotless ignition system and a “draw-through” negative draft 

    combustion air system. Gas ignition shall occur by energizing hot 

    surface ignitor, which lights the burner on each thermostatically 

    controlled heating cycle. Heat exchanger shall be located in indoor 

    air stream so as not to be visible or accessible through indoor supply 

  air 

grille.

SUGGESTED BID SPECIFICATIONS

FOR PRODUCT 

AND APPLICATION

Dynaline 3  Fits any Decor 

The Dynaline 3 PTAC features a 
modern, compact, and sleek design. 
Four standard colors, stainless steel 
and custom options to match any 
decor. Small and snug against the 
wall, it complements any room 
without commanding attention. 

Standard Color Options

1. 

Marvair Beige

2. 

Pebble Gray 

3. 

White

4. 

Gray 

Stainless Steel and custom powder coating 
are also available

1

.

1

Minimum order quantities required.

Содержание Suburban Dynaline 3 DYNA07AC

Страница 1: ...s Motels Apartments and Senior Housing Three BTU h Capacities 12 20 MBTU Gas Heat Low Heating Amp Draw R 410A Refrigerant ARCHITECT S AND ENGINEER S MANUAL A Combination Gas Heating Electric Cooling S...

Страница 2: ...o open flame is the modern alternative to pilot lights HSI increases energy conservation while ensuring safety Easy to Install and Service Gas LP or Natural connections may be inside or outside the ro...

Страница 3: ...g Tips 33 Accessory Description Review 34 Dynaline 3 Airflow 35 Suburban Limited Warranty 36 37 Dynaline 3 PTAC Features and Benefits 38 39 Hotels Motels Individual room control Energy management inte...

Страница 4: ...or each specific locale Utilizing BIN Hour temperature data the following table provides representative examples of costs to operate one PTAC for one year Suburban will gladly prepare a BIN Hour Cost...

Страница 5: ...er year at the mid point temperature specific to a geographical location The BIN hours are derived from historical weather data For example at a location with 7 023 heating BIN hours such as Syracuse...

Страница 6: ...g infiltration of air water and contaminants into the conditioned area Electrical components Located on the indoor side of the wall they are protected from the weather and easily accessed for service...

Страница 7: ...32 21 14 7 8 1 16 7 25 32 42 7 14 42 16 16 42 11 16 40 5 8 3 8 14 3 4 UNIT WALL SLEEVE DIMENSIONS Figure 4 Specifications subject to change without notice Freeze Protection Forces heating operation i...

Страница 8: ...50 1125 150 1550 260 Min Wire Size Copper 14 AWG 14 AWG 14 AWG 14 AWG 14 AWG Protection Fused 2 15 amp 2 15 amp 2 15 amp 2 15 amp 2 15 amp Protection Circuit HACR type Dual 15 amp Dual 15 amp Dual 15...

Страница 9: ...and Hi Low heat speeds and a fan cycle switch to permit continuous indoor fan operation A separate condenser fan operates in the A C cycle only The condenser fan not operating in the heating mode elim...

Страница 10: ...ructed of 20 gauge galvanized steel with a protective baked on enamel finish similar to the wall case GAS TYPE Natural gas units shall be equipped with a gas valve having a built in regulator set to o...

Страница 11: ...unit should be installed where it can effectively circulate air into the room Generally the best location is midway along the wall and away from a stairwell or other opening Unit must not be located...

Страница 12: ...a location inspect the wall and floor areas to determine that there are no hidden electrical wires piping tubing ducts girders wall studs etc that might interfere with the proper installation and safe...

Страница 13: ...4 slope to the outside Do not slope toward front To avoid water damage to the wall do not put holes through the bottom of the wall sleeve NOTE If the unit is to be mounted flush with the exterior wall...

Страница 14: ...Remote thermostat Dynaline 3 chassis are supplied for standard built in control To convert the standard chassis to function with remote thermostat connect the thermostat wiring according to thermosta...

Страница 15: ...HED INTERIOR WALL SURFACE OF FINISHED INTERIOR WALL CABINET FRONT SLOPE DOWN TO THE OUTSIDE MIN PROJECTION BEYOND EXTERIOR WALL MOUNTING HOLES AND SCREWS BY INSTALLER DO NOT PUT HOLES THROUGH WALL SLE...

Страница 16: ...LL WALL SLEEVE ANGLES SCREWS BY INSTALLER DO NOT PUT HOLES THROUGH OR DRIVE SCREWS INTO WALL SLEEVE BOTTOM CAULK AROUND WALL SLEEVE WINDOW OR WALL CABINET FRONT WALL SLEEVE MAX LONG SCREWS FOR SECURIN...

Страница 17: ...f pipe of different diameters and lengths in cubic feet per hour with pressure drop of 0 3 inches and specific gravity of 0 60 inches Iron Pipe Sizes IPS Inches Pipe Length feet 1 2 3 4 1 1 1 4 1 1 2...

Страница 18: ...15 4 Using the two 2 8 32 x 1 2 self tapping screws provided secure hi ear elbow as illustrated See C Figure 15 5 Insert gas inlet tube assembly See D Figure 15 through bushing in firewall NOTE The sh...

Страница 19: ...arge to the right but can easily be converted for discharge to the left The adaptor is 43 1 4 long with female connection The extension is 43 1 4 long with 1 male tapered flange If you wish to dischar...

Страница 20: ...diameter hole 2 places 9 Install adaptor and collar assembly on unit as illustrated and secure with the two 2 screws retained in Step 5 Also secure the adaptor to the adaptor brackets with the screws...

Страница 21: ...daptor and collar assembly from the unit At the two locations marked on the adaptor in Step 8 drill a 7 64 diameter hole 2 places 10 Install adaptor and collar assembly on unit as illustrated and secu...

Страница 22: ...rolled by a toggle switch or other means in a control panel field supplied The units remain de energized until the room becomes occupied at which time the desk attendant can energize them The standard...

Страница 23: ...les of exterior grilles are available to complement building aesthetics Aluminum Grille Unpainted grille of stamped clear anodized aluminum Protects the outdoor fan coil and vent cap assembly Designed...

Страница 24: ...as in the event of a diaphragm rupture Gas escapement is limited within ANSI standard levels Multipurpose mounting internal or external For best performance and quick response mount in upright positi...

Страница 25: ...t the chassis built in thermostat Schematic 208 230 V A C ELECTRICAL CONNECTIONS AND WIRING C S BR Y R Y COMPRESSOR MOTOR BR ROOM AIR BR BK EXHAUST MOTOR BK MOTOR BR BR 2 4 3 1 IGNITOR 10 11 12 7 8 9...

Страница 26: ...ESSOR RELAY 8 1 HI LIMIT 2 11 PRESSURE 7 4 CONDENSOR MOTOR TEMP SENSE LO HI AIR MOTOR ROOM POWER EMERGENCY 12 3 EXHAUST MOTOR 24V 230V 6 9 FLAME PROBE ROCKER SWITCH 208VAC 230VAC SW FLUE LIMIT G 24VAC...

Страница 27: ...ency power generator without forfeiting zone temperature control on the heating cycle Dynaline 3 incorporates an A C compressor lock out capability This feature allows the compressor circuit to be loc...

Страница 28: ...ust gases through the unit s vent system is obstructed creating an unsafe condition If the limit switch is determined to be defective it must be replaced Never attempt to repair it and never shunt the...

Страница 29: ...This completes the electrical circuit to the input of the module board and a 10 second warm up period for the glo bar is established During the warm up period the glo bar comes on for 10 seconds then...

Страница 30: ...temperature rise the switch will close and the compressor will again come on provided that the thermostat is still calling for cooling NOTE Dynaline 3 has a built in 5 minute delay between compressor...

Страница 31: ...rise the switch will close and the compressor will again come on provided that the thermostat is still calling for cooling NOTE Dynaline 3 has a built in 5 minute delay between compressor cycles Anyt...

Страница 32: ...tor Air Discharge Lateral Connector 43 Air Discharge Lateral Extension 43 Rear Gas Connection Kit Field Installed 2 PSIG Regulator Leveling Legs Set of 2 each Decor Base Panel conceals gas electric co...

Страница 33: ...r either horizontally or vertically The grille is installed from the factory to deliver horizontal air flow To change the airflow to vertical simply remove the grille and reinstall in the opposite pos...

Страница 34: ...or any other material charges 2 Damages caused by shipping accident abuse negligence misuse fire flood or Acts of God 3 Damages caused by operating or staging the unit in a corrosive environment 4 Dam...

Страница 35: ...n the product or with your homeowners manual If his name is not known call your builder or general contractor if yours is a new structure SECOND Contact the Suburban distributor who supplied the produ...

Страница 36: ...case they prevent the infiltration of air water and contaminants intothe conditioned area Air Vent The manually operated lever allows entry of 70 CFM of outside air into the comfort area Return Air Fi...

Страница 37: ...ncrease in temperature than an all electric unit Economical Gas Heat Provides Comfort to Those Who Need it the Most The Dynaline 3 Difference Dynaline 3 provides warm gas heat In cooler climates parti...

Страница 38: ...request A complete warranty statement can be found in each product s Installation Operation Manual on our website As part of the Suburban continuous improvement program specifications are subject to...

Отзывы: