5.3.1
Input
Inp.1
and
InP.3
g
Parameters
InL.
x ,
OuL.
x,
InH.
x and
OuH.
x are only visible if
ConF
/
InP.
x /
Corr
=
3
is chosen.
In addition to these settings,
InL.
x and
InH.
x can be adjusted in the range
(0...20mA / 0...10V) determined by selection of
S.tYP
.
a
For using the predetermined scaling with thermocouple and resistance
thermometer (Pt100), the settings for
InL.
x and
OuL.
x and for
InH.
x and
OuH.
x must have the same value.
g
Input scaling changes at calibration level (
r
page 55) are displayed by input
scaling at parameter setting level. After calibration reset (
OFF
), the scaling
parameters are reset to default.
5.3.2
Input
InP.2
In addition to these settings,
InL.2
and
InH.2
can be adjusted in the range
(0...20/ 50mA) determined by selection of
S.tYP
.
5.4
Second set of parameters
MIR-491 is provided with a second set of parameters (
PArA
/
PAr.2
) for
heating and cooling.
Switch-over to the second set of parameters is dependent of configuration
(
ConF
/
LOGI
/
Pid.2
) via digital input di1/2/3, the function key on the
instrument front panel or the interface (OPTION).
g
Self-tuning is always done using the active parameter set, i.e. for optimizing, the
second set of parameters must be active.
Parameter setting level
Second set of parameters
54
Operating manual MIR-491
S.tYP
Input signal
InL.2
OuL.2
InH.2
OuH.2
30
0 … 20 mA
0
any
20
any
31
0 … 50 mA
0
any
50
any
S.tYP
Input signal
InL.
x
OuL.
x
InH.
x
OuH.
x
30
(0...20mA)
0 … 20 mA
0
any
20
any
4 … 20 mA
4
any
20
any
40
(0...10V)
0 … 10 V
0
any
10
any
2 … 10 V
2
any
10
any