Configuration level
Configuration parameters
32
Operating manual MIR-491
Name
Value range Description
Default
HC.SC
Solid state relay (SSR) short circuit signal (only visible
when O.TYP=0)
0
0
not active
1
active
FAi.1
INP1 error (only visible when O.TYP=0)
1
0
not active
1
active
FAi.2
INP2 error (only visible when O.TYP=0)
0
0
not active
1
active
FAi.3
INP3 error (only visible when O.TYP=0)
0
0
not active
1
aktiv
Out.0
-1999...9999
Scaling of the analog output for 0% (0/4mA or 0/2V, only
visible when O.TYP=1..5)
0
Out.1
-1999...9999
Scaling of the analog output for 100% (20mA or 10V, only
visible when O.TYP=1..5)
100
O.Src
Signal source of the analog output OUT3 (only visible when
O.TYP=1..5)
1
0
not used
1
controller output y1 (continuous)
2
controller output y2 (continuous)
3
process value
4
effective set-point Weff
5
control deviation xw (process value - set-point)
6
measured value position feedback Yp
FOut
Forcing OUT3
(only visible with BlueControl!)
0
0
No forcing
1
Forcing via serial interface
Out.4
Name
Value range Description
Default
O.tYP
Signal type selection OUT4
0
0
relay / logic (only visible with current/logic voltage)
1
0 ... 20 mA continuous (only visible with
current/logic/voltage)
2
4 ... 20 mA continuous (only visible with
current/logic/voltage)
3
0...10 V continuous (only visible with current/logic/voltage)
4
2...10 V continuous (only visible with current/logic/voltage)
5
transmitter supply (only visible without OPTION)