Configuration level
Operating manual MIR-491
33
Configuration parameters
Name
Value range Description
Default
O.Act
Method of operation of output OUT4 (only visible when
O.TYP=0)
0
0
direct / normally open
1
inverse / normally closed
Y.1
Controller output Y1 (only visible when O.TYP=0)
0
0
not active
1
active
Y.2
Controller output Y2 (only visible when O.TYP=0)
0
0
not active
1
active
Lim.1
Limit 1 signal (only visible when O.TYP=0)
0
0
not active
1
active
Lim.2
Limit 2 signal (only visible when O.TYP=0)
0
0
not active
1
active
Lim.3
Limit 3 signal (only visible when O.TYP=0)
0
0
not active
1
active
dAc.A
Valve monitoring (DAC) (only visible when O.TYP=0)
0
0
not active
1
active
LP.AL
Interruption alarm signal (LOOP) (only visible when
O.TYP=0)
0
0
not active
1
active
HC.AL
Heat current alarm signal (only visible when O.TYP=0)
0
0
not active
1
active
HC.SC
Solid state relay (SSR) short circuit signal (only visible
when O.TYP=0)
0
0
not active
1
active
FAi.1
INP1 error (only visible when O.TYP=0)
0
0
not active
1
active
FAi.2
INP2 error (only visible when O.TYP=0)
0
0
not active
1
active