Configuration level
Operating manual MIR-491
31
Configuration parameters
Out.3
Name
Value range Description
Default
O.tYP
Signal type selection OUT3
0
0
relay / logic (only visible with current/logic voltage)
1
0 ... 20 mA continuous (only visible with
current/logic/voltage)
2
4 ... 20 mA continuous (only visible with
current/logic/voltage)
3
0...10 V continuous (only visible with current/logic/voltage)
4
2...10 V continuous (only visible with current/logic/voltage)
5
transmitter supply (only visible without OPTION)
O.Act
Method of operation of output OUT3 (only visible when
O.TYP=0)
1
0
direct / normally open
1
inverse / normally closed
Y.1
Controller output Y1 (only visible when O.TYP=0)
0
0
not active
1
active
Y.2
Controller output Y2 (only visible when O.TYP=0)
0
0
not active
1
active
Lim.1
Limit 1 signal (only visible when O.TYP=0)
1
0
not active
1
active
Lim.2
Limit 2 signal (only visible when O.TYP=0)
0
0
not active
1
active
Lim.3
Limit 3 signal (only visible when O.TYP=0)
0
0
not active
1
active
dAc.A
Valve monitoring (DAC) (only visible when O.TYP=0)
0
0
not active
1
active
LP.AL
Interruption alarm signal (LOOP) (only visible when
O.TYP=0)
0
0
not active
1
active
HC.AL
Heating current alarm signal (only visible when O.TYP=0)
0
0
not active
1
active