background image

Series 550LX-504-4V2-10 SmartPack User's Manual                                                                    Quad VDC Input
__________________________________________________________________________________________

 - 4 -

"G" Rail (32mm), Type EN50035:  To attach a module to this
style of DIN rail, angle the unit so that the upper groove of the
adapter hooks under the top lip of the rail.  Firmly push the
unit towards the rail until it snaps solidly into place.  To
remove a module, pull the lower part of the unit outward until
it releases from the rail, lift unit from rail.

Electrical Connections:

The wire size used to connect the unit to the control system

is not critical.  All terminal strips can accommodate wire from 14-
26 AWG.  Strip back wire insulation 1/4-inch on each lead before
installing into the terminal block.  Input wiring may be shielded or
unshielded twisted pair.  Network wires should be twisted pair.
Since common mode voltages can exist on signal wiring,
adequate wire insulation should be used and proper wiring
practices followed.  It is recommended that network and power
wiring be separated from the signal wiring for safety, as well as
for low noise pickup.

1.   Power: Connect power per Connection Drawing 4501-509.

These modules operate from DC power supplies only.  Power
supply voltage is not critical and normally should be from
10.0V to 36V DC.  The supply voltage must not exceed 36
Volts, even momentarily.  Variations in power supply voltage,
above the minimum required have negligible effect on module
accuracy.  This device includes reverse polarity protection.
Refer to "POWER" in the preceding SPECIFICATIONS
section for current requirements.

2.   Network:  Connect network per Connection Drawing 4501-

509.  Note: Network circuit is isolated from input and power
circuits.  See NETWORK specifications for the maximum
number of nodes per network segment.

3.   Grounding:  The module housing is plastic and does not

require an earth ground connection.

4.   Input:  Connect input per connection diagram and observe

proper polarity (see label for input type).  If unit is factory
calibrated, the calibration label indicates range of input.
NOTE: All inputs share a common,  however, as a group they
are electrically isolated from the network and power circuits,
allowing the input to operate up to 250V AC, or 354V DC off
ground, on a continuous basis.

NETWORK VARIABLES:

To provide interoperability, standard network variable types

are used for all external interface and configuration variables.
Figure 2 illustrates the 550L's network variable types.

Figure 2: Series 550LX1-504-4V2-10 SNVT Diagram

                                                                       nvo_pvout[ 4 ]
                                                                      SNVT_lev_percent
                                        External
                                        Interface Section

             nci_pvdb[ 4 ]
             SNVT_lev_percent

             nci_pvtime[ 5 ]
             SNVT_elapsed_tm

             nci_callo[ 4 ]
             SNVT_lev_percent

             nci_calhi[ 4 ]
             SNVT_lev_percent

                                                Configuration Section

       HARDWARE INPUT

                                        Input  1       2      3      4   (VDC)

All network variables are 4-element arrays.  Analog input 1's

network variables are referenced using an array subscript of 0;
analog input 2's by a subscript of 1, and so on.  Figure 3
illustrates the relationship between input voltage and
SNVT_lev_percent value for the factory calibration case.  Figure
4 provides the general output graph & equation that relates output
in terms of calibration constants.

Network variables within the External Interface Section are

intended to be bound, polled, or written by other nodes on the
network.  These variables are maintained in RAM.  Network
variables within the Configuration Section are intended to be
accessed by a network management tool to configure and
calibrate the module.  These variables are maintained in
EEPROM and are limited to 10000 write cycles.  In addition,
values written into configuration network variables do not take
effect until the module is reset.  Reset can occur as the result of
powering-up, toggling the RESET switch, or issuing a "reset"
network management command to the module.

Содержание SmartPack EP4994

Страница 1: ...ower Certification B Typical Model Number 550L1 504 4V2 10 NCR Series Network Function Inputs Power Cert 1 Cal 2 550L1 504 4V2 10 NCR Blank C 550L3 504 4V2 10 NCR Blank C Notes Table 1 1 Consult the factory for current information on agency e g Canadian Standards Association etc approvals 2 Unit can be ordered with or without factory calibration if unit is factory calibrated to a customer s specif...

Страница 2: ...s section for a description of the module s standard network variable types and operation INPUT This unit has four independent analog inputs with software selectable output scaling ranges Zero and Full Scale calibration scaling of each input is done over the network Virtually any part of the input range can be scaled to output values in the range of 100 to 100 There are no potentiometers to adjust...

Страница 3: ...ith switching solenoids commutator and drill motors Surge Withstand Capability SWC Input Output terminations are rated per ANSI IEEE C37 90 1978 Unit is tested to a standardized test waveform that is representative of surges high frequency transient electrical interference observed in actual installations Mounting 0 Mounting General Purpose Housing with integrated DIN Rail Mount Supports G T rails...

Страница 4: ...gment 3 Grounding The module housing is plastic and does not require an earth ground connection 4 Input Connect input per connection diagram and observe proper polarity see label for input type If unit is factory calibrated the calibration label indicates range of input NOTE All inputs share a common however as a group they are electrically isolated from the network and power circuits allowing the...

Страница 5: ...D HH MM SS LL format is 00 03 38 27 000 Anything greater will be clipped at 00 03 38 27 000 To disable periodic updates set DD 65535 or all members to 0 This variable is maintained in EEPROM and does not take effect until the module is reset Initial Factory Value DD 65535 HH 00 MM 00 SS 00 LL 000 Periodic updates disabled nci_pvtime 4 Controls the update for nvo_struct_pvout output structure varia...

Страница 6: ...is 100 100 nvo_pvout VIN 60 x 100 20 60 This reduces to nvo_pvout VIN 60 x 2 5 100 CALIBRATION All modules are calibrated at the factory for an input range of 10VDC scaled to output 100 No additional calibration is normally required If it becomes necessary to calibrate the module follow the procedure outlined below for each analog input Values shown in parenthesis indicate the SNVT_lev_percent val...

Страница 7: ...ntenance except for periodic cleaning and calibration verification When a failure is suspected a convenient method for identifying a faulty module is to exchange it with a known good unit It is highly recommended that a non functioning module be returned to Acromag for repair since Acromag makes use of tested and burned in parts and in some cases parts that have been selected for characteristics b...

Страница 8: ...Series 550LX 504 4V2 10 SmartPack User s Manual Quad VDC Input __________________________________________________________________________________________ 8 ...

Страница 9: ...Series 550LX 504 4V2 10 SmartPack User s Manual Quad VDC Input __________________________________________________________________________________________ 9 ...

Страница 10: ...Series 550LX 504 4V2 10 SmartPack User s Manual Quad VDC Input __________________________________________________________________________________________ 10 ...

Страница 11: ...Series 550LX 504 4V2 10 SmartPack User s Manual Quad VDC Input __________________________________________________________________________________________ 11 ...

Страница 12: ...Series 550LX 504 4V2 10 SmartPack User s Manual Quad VDC Input __________________________________________________________________________________________ 12 ...

Отзывы: