background image

Series 550LX-504-4V2-10 SmartPack User's Manual                                                                    Quad VDC Input
__________________________________________________________________________________________

 - 3 -

LED Indicators:

Power LED (Green):  Indicates power applied to unit.
Service LED (Red):  LED blinks at a 1/2 Hz rate for an
unconfigured node.  LED OFF for a properly functioning
node.  LED ON for failed node.
Status LED (Yellow):  (See Figure 1) LED remains ON
indefinitely upon receiving an "offline" network management
command.  LED remains OFF upon receiving an "online"
network management command (normal operation).  LED
blinks at a 2.5Hz rate for 10 seconds upon receiving a "wink"
network command.

Figure 1: Status LED Behavior

1.   Offline/Online Commands:
                                           Indefinite
ON
OFF

        Offline Command                               Online Command

2.   Wink Command:
                                         10 Seconds
ON
OFF
                200    200

                       mS     mS

Reference Test Conditions: Input Span: 

±

10VDC,  Input Voltage

Applied: +10VDC; Network (78kB/S); 77oF (25oC); +15V DC
supply.

Accuracy:  Range A: 

±

0.05% of calibrated input span or

±

3.81mV, whichever is greater.  Range B:  

±

0.05% of input

span, or 381

µ

V, whichever is greater.  The error includes the

combined effects of module repeatability, hysteresis and
terminal point linearity.

Analog Resolution:  Range A  A-to-D resolution : 3.81mV,

Range B A-to-D resolution: 381

µ

V.

Conversion Rate:  5 conversions per second for each analog

input.

Ambient Temperature Range:  L1 (44 nodes): -13

°

F to +185

°

F

(-25

°

C to +85

°

C),  L1 (64 nodes): +32

°

F to +158

°

F (0

°

C to

70

°

C),  L3 (64 nodes): -13

°

F to +185

°

F (-25

°

C to +85

°

C).

Ambient Temperature Effect:  Less than 

±

0.003% of input span

effect per oF (

±

 0.005% per oC) over the ambient

temperature range for reference test conditions.
Specification includes the combined effects of zero and span
over temperature.

Bandwidth: -3dB at 3Hz, typical.

Response Time: 300ms typical for the network variable value to

reach 98% of the final value for a step change in input signal.

Noise Rejection:

Common Mode:  120dB at 60 Hz, 100

 unbalance, typical.

Normal Mode:  26dB at 60 Hz, 100

 source, typical.

RFI Resistance:  Less than 

±

 0.5% of input span effect with RFI

field strengths of up to 10V/meter at frequencies of 27MHz,
151MHz, and 467 MHz.

EMI Resistance:  Less than 

±

0.25% of input span effect with

switching solenoids,  commutator and drill motors.

Surge Withstand Capability (SWC): Input/Output terminations

are rated per ANSI/IEEE C37.90-1978.  Unit is tested to a
standardized test waveform that is representative of surges
(high frequency transient electrical interference) observed in
actual installations.

Mounting:  (0) Mounting:  General Purpose Housing with

integrated DIN-Rail Mount.  Supports "G" & "T" rails: "G" Rail
(32mm), Type EN50035; "T" Rail (35mm), Type EN50022.
Refer to Drawing 4501-502 for outline and clearance
dimensions.  Shipping Weight: 1 pound (0.45 Kg) packed.

Construction:

Circuit Boards: Military grade FR-4 epoxy glass circuit board.
Circuit Board Coating: Fungus resistant acrylic conformal
coat on analog input circuit board.
Terminals: Compression type, wire size 14 AWG maximum.
Mounting Position: Position insensitive.
Case: Self-extinguishing NYLON Type 6.6 polyamide
thermoplastic UL94 V-2, color black.  General Purpose,
NEMA Type 1 enclosure.

CERTIFICATION:  Consult the factory for current information on

the availability of agency (e.g. Canadian Standards
Association, Factory Mutual, etc.) approvals.

-NCR:  No Certification Required.

INSTALLATION:

The module is packaged in a general purpose type of

enclosure.  Use an auxiliary enclosure to protect against
unfavorable environments and locations.  Maximum operating
ambient temperatures should be within -13 oF to 185oF (-25oC to
+85oC) for satisfactory performance.  The module is factory
calibrated and ready for installation.  Connect as shown in
Connection Drawing 4501-509.

Mounting:  Mount module assembly - refer to Drawing 4501-502

for mounting and clearance dimensions.

DIN Rail Mounting:  Use suitable fastening hardware to
secure the DIN rail to the designated mounting surface.  A
module, can be mounted to either the "T" or "G" Rail.
Installation of the module to the rail depends on the type of
DIN rail used.  Units can be mounted side-by-side on 1.6 inch
centers, if required.

"T" Rail (35mm), Type EN50022:  To attach a module to this
style of DIN rail, angle the top of the unit towards the rail and
locate the top groove of the adapter over the upper lip of the
rail.  Firmly push the unit towards the rail until it snaps solidly
into place.  To remove a module, insert a screwdriver into the
lower arm of the connector and pull downward while applying
outward pressure to the bottom of the unit.

Содержание SmartPack EP4994

Страница 1: ...ower Certification B Typical Model Number 550L1 504 4V2 10 NCR Series Network Function Inputs Power Cert 1 Cal 2 550L1 504 4V2 10 NCR Blank C 550L3 504 4V2 10 NCR Blank C Notes Table 1 1 Consult the factory for current information on agency e g Canadian Standards Association etc approvals 2 Unit can be ordered with or without factory calibration if unit is factory calibrated to a customer s specif...

Страница 2: ...s section for a description of the module s standard network variable types and operation INPUT This unit has four independent analog inputs with software selectable output scaling ranges Zero and Full Scale calibration scaling of each input is done over the network Virtually any part of the input range can be scaled to output values in the range of 100 to 100 There are no potentiometers to adjust...

Страница 3: ...ith switching solenoids commutator and drill motors Surge Withstand Capability SWC Input Output terminations are rated per ANSI IEEE C37 90 1978 Unit is tested to a standardized test waveform that is representative of surges high frequency transient electrical interference observed in actual installations Mounting 0 Mounting General Purpose Housing with integrated DIN Rail Mount Supports G T rails...

Страница 4: ...gment 3 Grounding The module housing is plastic and does not require an earth ground connection 4 Input Connect input per connection diagram and observe proper polarity see label for input type If unit is factory calibrated the calibration label indicates range of input NOTE All inputs share a common however as a group they are electrically isolated from the network and power circuits allowing the...

Страница 5: ...D HH MM SS LL format is 00 03 38 27 000 Anything greater will be clipped at 00 03 38 27 000 To disable periodic updates set DD 65535 or all members to 0 This variable is maintained in EEPROM and does not take effect until the module is reset Initial Factory Value DD 65535 HH 00 MM 00 SS 00 LL 000 Periodic updates disabled nci_pvtime 4 Controls the update for nvo_struct_pvout output structure varia...

Страница 6: ...is 100 100 nvo_pvout VIN 60 x 100 20 60 This reduces to nvo_pvout VIN 60 x 2 5 100 CALIBRATION All modules are calibrated at the factory for an input range of 10VDC scaled to output 100 No additional calibration is normally required If it becomes necessary to calibrate the module follow the procedure outlined below for each analog input Values shown in parenthesis indicate the SNVT_lev_percent val...

Страница 7: ...ntenance except for periodic cleaning and calibration verification When a failure is suspected a convenient method for identifying a faulty module is to exchange it with a known good unit It is highly recommended that a non functioning module be returned to Acromag for repair since Acromag makes use of tested and burned in parts and in some cases parts that have been selected for characteristics b...

Страница 8: ...Series 550LX 504 4V2 10 SmartPack User s Manual Quad VDC Input __________________________________________________________________________________________ 8 ...

Страница 9: ...Series 550LX 504 4V2 10 SmartPack User s Manual Quad VDC Input __________________________________________________________________________________________ 9 ...

Страница 10: ...Series 550LX 504 4V2 10 SmartPack User s Manual Quad VDC Input __________________________________________________________________________________________ 10 ...

Страница 11: ...Series 550LX 504 4V2 10 SmartPack User s Manual Quad VDC Input __________________________________________________________________________________________ 11 ...

Страница 12: ...Series 550LX 504 4V2 10 SmartPack User s Manual Quad VDC Input __________________________________________________________________________________________ 12 ...

Отзывы: