Series 550LX-504-4V2-10 SmartPack User's Manual                                                                    Quad VDC Input
__________________________________________________________________________________________

 - 2 -

SmartPacks are interoperable with

 

L

ON

W

ORKS 

products from

other manufacturers that use standard network variable types
(SNVTs).   Module calibration, configuration and network
management are performed using a Windows™ configuration
program on a PC.

SPECIFICATIONS:

Note: All specifications are given for the Reference Test
Conditions as listed later in this section.

DEFINITION:  This DC-powered, SmartPack module conditions

four DC voltage inputs, and converts these signals to network
variables using standard network variable types (SNVT).  The
analog inputs share a common ground.  As a group they are
isolated from the network and power.  This module is DIN-rail
mounted.

MODEL/SERIES:  550  (Color coded with a White label)

NETWORK (Designated by ‘LX’  of 550LX Model prefix):

Protocol: LonTalk®

L1: TP/XF-78, Twisted Pair

Speed:  78.1kb per second.
Media:  Unshielded twisted pair, UL Level IV, No. 22

gauge wire.

Distance:  Up to 6500 feet (2000 meters).
Nodes per Network Segment:  64 (0 to +70

°

C), 44 (-25 to

+85

°

C ).  A L

ON

W

ORKS

 router configured as a

repeater is required for more than 64 nodes.

L3: TP/FT-10, Free Topology

Speed:  78.1kb per second.
Media:  See Cable Type in Table 2 below.
Distance:  See Table 2 below.

Table 2:  Free Topology Specifications

Cable Type

Maximum
module-to-
module distance

Maximum total
wire length for
SmartPack
Modules

Belden 85102

1640 ft (500 m)

1640 ft (500 m)

Belden 8471

1312 ft (400 m)

1640 ft (500 m)

Level IV, 22 AWG

1312 ft (400 m)

1640 ft (500 m)

JY (St) Y 2x2x0.8

1050 ft (320 m)

1640 ft (500 m)

Nodes per Network Segment:  64.  A L

ON

W

ORKS

 router

configured as a repeater is required for more than 64
nodes.

FUNCTION:  Code number used to represent the module’s

firmware functionality.

-504:  See the network variables section for a description of
the module’s standard network variable types and operation.

INPUT: This unit has four independent analog inputs with

software selectable output scaling ranges.  Zero and Full-
Scale calibration/scaling of each input is done over the
network. Virtually any part of the input range can be scaled to
output values in the range of -100% to +100%.  There are no
potentiometers to adjust.

-4V2:  Range A: 

±

100VDC

 Range B: 

±

10VDC

Input Impedance:   Range A: 1M

 minimum

Range B:  100K

 minimum

Isolation:  Three-way isolation: input, network and power are

isolated from each other for common-mode voltages up to
250V AC, or 354V DC off DC power ground, on a continuous
basis (will withstand 1500V AC dielectric strength test for one
minute without breakdown for all combinations except
between the input and network circuits which will withstand
1000V AC dielectric strength test for one minute without
breakdown).  The 1500V AC dielectric strength test complies
with test requirements outlined in ANSI/ISA-S82.01-1988 for
the voltage rating specified.

POWER:  Connect an external DC power supply to the Power (P)

and (-) terminals.  Currents specified are maximum values
with full-scale input voltage (each input), and the module
transmitting on the network.  An internal diode provides
reverse polarity protection.

-10:  +10 to 36V DC, current draw is a function of supply

   voltage (refer to Table 3 below).

Table 3:  Supply Current

Supply Voltage

L1 Supply Current

L3 Supply Current

10V

50mA

35mA

12V

43mA

30mA

15V

37mA

25mA

24V

28mA

20mA

36V

23mA

17mA

CAUTION:  Do not exceed 36V DC peak, to avoid damage to the
                   module.

Power Supply Effect:

DC Volts:  Less than 

±

0.001% of input span change per volt

DC, for rated power supply variations.  60/120 Hz ripple:
Less than 

±

0.01% of input span per volt peak-to-peak of

power supply ripple.

Reset/Service Toggle Switch:

Reset Position:  Allows the module to be reset to power-up
conditions (toggle right).
Service Position:  Causes the Neuron® chip inside the node
to transmit its unique 48-bit ID and 8-byte program ID string
(toggle left).

Содержание SmartPack EP4994

Страница 1: ...ower Certification B Typical Model Number 550L1 504 4V2 10 NCR Series Network Function Inputs Power Cert 1 Cal 2 550L1 504 4V2 10 NCR Blank C 550L3 504 4V2 10 NCR Blank C Notes Table 1 1 Consult the factory for current information on agency e g Canadian Standards Association etc approvals 2 Unit can be ordered with or without factory calibration if unit is factory calibrated to a customer s specif...

Страница 2: ...s section for a description of the module s standard network variable types and operation INPUT This unit has four independent analog inputs with software selectable output scaling ranges Zero and Full Scale calibration scaling of each input is done over the network Virtually any part of the input range can be scaled to output values in the range of 100 to 100 There are no potentiometers to adjust...

Страница 3: ...ith switching solenoids commutator and drill motors Surge Withstand Capability SWC Input Output terminations are rated per ANSI IEEE C37 90 1978 Unit is tested to a standardized test waveform that is representative of surges high frequency transient electrical interference observed in actual installations Mounting 0 Mounting General Purpose Housing with integrated DIN Rail Mount Supports G T rails...

Страница 4: ...gment 3 Grounding The module housing is plastic and does not require an earth ground connection 4 Input Connect input per connection diagram and observe proper polarity see label for input type If unit is factory calibrated the calibration label indicates range of input NOTE All inputs share a common however as a group they are electrically isolated from the network and power circuits allowing the...

Страница 5: ...D HH MM SS LL format is 00 03 38 27 000 Anything greater will be clipped at 00 03 38 27 000 To disable periodic updates set DD 65535 or all members to 0 This variable is maintained in EEPROM and does not take effect until the module is reset Initial Factory Value DD 65535 HH 00 MM 00 SS 00 LL 000 Periodic updates disabled nci_pvtime 4 Controls the update for nvo_struct_pvout output structure varia...

Страница 6: ...is 100 100 nvo_pvout VIN 60 x 100 20 60 This reduces to nvo_pvout VIN 60 x 2 5 100 CALIBRATION All modules are calibrated at the factory for an input range of 10VDC scaled to output 100 No additional calibration is normally required If it becomes necessary to calibrate the module follow the procedure outlined below for each analog input Values shown in parenthesis indicate the SNVT_lev_percent val...

Страница 7: ...ntenance except for periodic cleaning and calibration verification When a failure is suspected a convenient method for identifying a faulty module is to exchange it with a known good unit It is highly recommended that a non functioning module be returned to Acromag for repair since Acromag makes use of tested and burned in parts and in some cases parts that have been selected for characteristics b...

Страница 8: ...Series 550LX 504 4V2 10 SmartPack User s Manual Quad VDC Input __________________________________________________________________________________________ 8 ...

Страница 9: ...Series 550LX 504 4V2 10 SmartPack User s Manual Quad VDC Input __________________________________________________________________________________________ 9 ...

Страница 10: ...Series 550LX 504 4V2 10 SmartPack User s Manual Quad VDC Input __________________________________________________________________________________________ 10 ...

Страница 11: ...Series 550LX 504 4V2 10 SmartPack User s Manual Quad VDC Input __________________________________________________________________________________________ 11 ...

Страница 12: ...Series 550LX 504 4V2 10 SmartPack User s Manual Quad VDC Input __________________________________________________________________________________________ 12 ...

Отзывы: