background image

IntelliPack Series 892M/894M Computation Transmitter User's Manual                             DC Voltage/Current Input 
___________________________________________________________________________________________ 
 

 - 6 - 

 

3.0  MODULE CONFIGURATION 

 

This computation transmitter needs to be configured for your 

application.  An equation that relates the inputs to the output 
must be entered.  Configuration is 

done using Acromag’s 

Windows 95/98

 or NT

 IntelliPack Configuration Program and 

Serial Port Adapter.  Transmitter configuration details are 
included in the IntelliPack Transmitter Configuration Manual 
(8500-570) and in Section 6 of this manual.  The following section 
provides additional information regarding the formulation of the 
equation that relates the input signals to the output of this 
module. 

 

MATH FORMULATION 

 
The IntelliPack Configuration Software provides the interface 

for scaling the input and output values, and entering an equation 
via the transmitter configuration page.  A simple edit box is 
provided to enter an equation that operates on the scaled input 
values from each channel.  Equations are entered in a free-form 
format, similar to entering a cell formula in Microsoft Excel.  All 
scaling and computation is performed using a single precision, 
floating point arithmetic.  A simulator is provided to check scaling 
and computation. 

 

The 894M model will mathematically combine up to 4 scaled 

input signal values according to a preprogrammed output 
equation entered via the IntelliPack Configuration Software.  The 
equation combines standard math operators and functions, with 
floating point constants, and variables that represent the scaled 
input channel values.  The module will compute a solution to the 
equation, then scale the computed value to the desired output 
range.  The equation variables A, B, C, and D, represent the 
scaled input readings from channels 1, 2, 3, and 4, respectively. 
 

The built-in equation interpreter operates on 

scaled

 input and 

output values.  Scaled values are single-precision floating-point 
numbers representing your engineering units and are limited to 8 
characters.  Large numbers may be entered in scientific notation 
(i.e. 123456E3).  Each input, plus the output must be scaled.  
That is, for each input, you must specify a scaled value for 
nominal zero and full-scale.  For example, 4-20mA channel 1 can 
be scaled to 0-5000GPM

—the 4mA input signal endpoint is 

scaled to 0GPM and the 20mA full-scale is scaled to 5000GPM.  
The solution to your equation determines your output (before 
scaling).  The output equation solution must also be scaled to the 
nominal zero and full-scale endpoints of the selected output 
range. 
 

Up to 200 characters may be entered into the equation field 

to define a formula that relates the scaled input values to the 
scaled output value.  Note that equation constants can be 
entered as floating point numbers, or in scientific notation.  
Equation operators are shown in Table 3 below.  Channels 1, 2, 
and 3/4 may have different input type and range configurations, 
but channels 3 and 4 (894M only) share a gain register in the A/D 
converter and must be configured with the same input range and 
type (they may be scaled differently). 

 

Table 3A:  IntelliPack 89xM Math Operators 

OPERATOR 

DESCRIPTION 

Add (Do Not + Use To Indicate Polarity) 

Subtract or unary minus for constants 

Multiply 

Divide 

Left Parenthesis 

Right Parenthesis 

 

 

e 

A constant followed by the 

suffix “e” or “E” 

represents scientific notation and a power of 
10 follows (i.e. 5.25e8 = 525,000,000). 

Represents the scaled value of channel 1 

Represents the scaled value of channel 2 

Represents the scaled value of channel 3 

Represents the scaled value of channel 4 

 
Table 3B:  IntelliPack 89xM Math Functions 

FUNCTION 

DESCRIPTION 

MIN(n1,n2,..,n5)

 

 

Return the minimum value of two to five 
channels, numbers, or expressions. 

MAX(n1,n2,..,n5

 

Return the maximum value of two to five 
channels, numbers, or expressions. 

SQRT(n1)

 

n1>=0

 

Return the square root of a channel, 
number, or expression. 

ABS(n1)

 

 

Return the absolute value of a channel, 
number, or expression. 

EXP(n1)

 

Compute the exponential (

e

n1

) of a 

channel, number, or expression. 

LN(n1)

 

n1 > 0

 

Compute the natural logarithm (base 

e

of a channel, number, or expression. 

LOG10(n1)

 

n1 > 0

 

Compute the base 10 logarithm of a 
channel, number, or expression. 

POWER(n1,n2

Compute the channel, number, or 
expression n1 raised to the n2 power 
(n1

n2

). 

SIN(n1)

 

n1 is in radians

 

Compute the sine of a channel, number, 
or expression. 

COS(n1)

 

n1 is in radians

 

Compute the cosine of a channel, 
number, or expression. 

TAN(n1)

 

n1 is in radians

 

Compute the tangent of a channel, 
number, or expression. 

ASIN(n1)

 

-1 <= n1 <= 1

 

Compute the arc-sine (sin

-1

, -

/2 <= 

radians <= 

/2) of a channel, number, or 

expression. 

ACOS(n1)

 

-1 <= n1 <= 1

 

Compute the arc-cosine (cos

-1

, 0 <= 

radians <= 

) of a channel, number, or 

expression. 

ATAN(n1)

 

Compute the arc-tangent (tan

-1

, -

/2 <= 

radians <= 

/2) of a channel, number, or 

expression. 

IF(condition
THEN(n1
)  
ELSE(n2

Conditional Expression.  If the 
conditional expression is true, then the 
expression 

n1

 is performed, otherwise 

the expression 

n2

 is performed.  Can 

only be used one time in a formula.  
ELSE must be included. 

AND(n1,n2,..,n5)

 

Conditional construct AND of two to five 
channels, numbers, or expressions.  
True if all n1..n5 are true.  Can only be 
used inside the conditional expression 
for IF. 

Содержание IntelliPack 895M Series

Страница 1: ...cess Current Voltage Inputs USER S MANUAL ACROMAG INCORPORATED 30765 South Wixom Road Wixom MI 48393 2417 U S A Tel 248 295 0880 Fax 248 624 9234 Copyright 1998 Acromag Inc Printed in the USA Data and...

Страница 2: ...NT are registered trademarks of Microsoft Corporation 1 0 INTRODUCTION These instructions cover hardware functionality of the transmitter models listed in Table 1 Supplementary sheets are attached fo...

Страница 3: ...ash memory and EEPROM This allows the functionality of this device to be reliably reprogrammed thousands of times Fully Isolated Input output and power are isolated from each other for safety and incr...

Страница 4: ...ically protected with an anti static bag during shipment However it is recommended that the module be visually inspected for evidence of mishandling prior to applying power This circuit utilizes stati...

Страница 5: ...trical Code for installations within Canada and in accordance with the authority having jurisdiction This equipment is suitable for use in Class I Division 2 Groups A B C and D or non hazardous locati...

Страница 6: ...solution must also be scaled to the nominal zero and full scale endpoints of the selected output range Up to 200 characters may be entered into the equation field to define a formula that relates the...

Страница 7: ...A B A D THEN A ELSE C 12 56 When formulating an equation or response it is important to keep the limits of module resolution in mind see Table 5 In some cases it may be necessary to normalize your va...

Страница 8: ...ir services are available from Acromag 6 0 SPECIFICATIONS 892M 0500 C Two I V Inputs Single Process I V Output 894M 0500 C Four I V Inputs Single Process I V Output General The IntelliPack Model 89XM...

Страница 9: ...LSB 8 4 20mA DC 16797 953nA LSB 2 0 5V DC 26298 190uV LSB 1 0 10V DC 26298 380uV LSB IMPORTANT Input COM and RTN are not the same potential and should never be connected together either directly or th...

Страница 10: ...t exceed 36VDC peak to avoid damage to the module Table 8 89XM Supply Current Supply Voltage Supply Current SPA Connected Supply Current SPA Not Connected 10V 330mA 300mA 12V 250mA 230mA 15V 200mA 175...

Страница 11: ...al EXP natural logarithm LN logarithm base 10 LOG10 power POWER sine SIN cosine COS tangent TAN arc sine ASIN arc cosine ACOS and arc tangent ATAN Support for IF THEN ELSE plus AND OR constructs are i...

Страница 12: ...N I3 2 2 2 3 2 6 2 5 2 4 I4 V4 RTN INSTAL L V TO I JUMPER AT INPUT FOR CURRENT INPUTS TRANSIENT VOL TAGE AND NOISE SUPPRESSION DEVICES ARE NOT SHOWN 4 9 9 4 9 9 K 5 4 9 K 1 6 VOL TS 4 9 9 5 4 9 K SERI...

Страница 13: ...LO Y LO Y H I Y X XL YH YL XH XL YL X LO X H I ANALOG INPUT X In pu t Sen s o r Ty p es Vol tag e DC M i l l i am p ere s DC AC Curren t wi th AC Se ns or I nput 1 2 Cal Val u e Cal HI Cal LO Val u e...

Страница 14: ...ONFIGURATION RUNNING WINDOWS 95 OR NT S E E USE R S MA NUA L MODULE CONFIGURA TION CONFIGURA TION P ORT FOR POWER RUN PWR LE D GREE N OV ERRA NGE LE D s YE LLOW 10 TO 36VD C TB4 A cromag R U N I N P U...

Страница 15: ...H HOLD DEASSERTED HI G H OR OPEN THE OUTPUT W I L L TRACK I N PUT CHANGES HOLD I S ASSERTED LOW AND W I L L HOLD THE TRANSM I T TER OUTPUT AT THE LAST VALUE SHI EL DED CABL E TB1 CURRENT J UM PER V2...

Страница 16: ...____________________________________ 16 Acromag R U N 1 2 3 4 INPU T STATU S 118 9 4 68 95 3 3 75 R 2 34 59 4 DIN EN 5 0 0 2 2 3 5 mm T RAIL DIN MO UNTING C L SCREWDRIVER SL O T FO R REMO VAL FRO M T...

Страница 17: ...________________________________________________ 17 Revision History The following table details the revision history for this document Release Date Version EGR DOC Description of Revision 03 AUG 2017...

Отзывы: