background image

IntelliPack Series 892M/894M Computation Transmitter User's Manual                             DC Voltage/Current Input 
___________________________________________________________________________________________ 
 

 - 11 - 

serves as an isolated interface converter between EIA232 
and the IntelliPack’s SPI port. 

Baud Rate (EIA232):

  19.2K baud. 

 

SOFTWARE CONFIGURATION 

Units are fully reprogrammable via our user-friendly Windows 
95/98

 or NT

 IntelliPack Configuration Program (Model 5030-

881).  Programmable attributes for this model are given below.  A 
cable (5030-902) and converter (5030-913) are required to 
complete the interface (Software Interface Package 800C-SIP).  
See Drawing 4501-643.  Additional information can be found in 
the IntelliPack Transmitter Configuration Manual (8500-570). 
 

Input Configuration

 

Input - Range (Each Input):  

The transmitter can be configured 

to accept any one of the five input range types shown below.  
However, a short jumper wire must be installed between the 
input “I+” and “V+” terminals to utilize current input.  Input 
range volts and milliamperes can be scaled to engineering 
units per your application (see Transmitter Configuration). 

Voltage:

  0 to 10V DC, 0 to 5V DC. 

Current (Jumper Required):

 0-20mA, 4-20mA, or 0-1mA 

DC. 

Input Calibration (Each Input, Each Range):

  The IntelliPack 

Configuration Software is used to calibrate available input 
ranges at each input channel of this module. 

 
Output Configuration 
Output - Range: 

 Analog output can be configured for one of five 

ranges of current or voltage.  For voltage output, a jumper 
must also be installed between the output “I+” and “JMP” 
terminals (remove this jumper for current output). 

Voltage (Jumper Required):

  0 to 10V DC, 0 to 5V DC. 

Current:

 0 to 20mA DC, 4 to 20mA DC, or 0 to 1mA DC. 

Output - Mode:

  Select a Normal Acting (ascending), or Reverse 

Acting (descending) output response. 

Output Calibration

:  The configuration software can be used to 

calibrate the output conditioning circuit of this module.

 

 

Transmitter Configuration 
Transmitter - Scaling:

  Scaled values must be entered for each 

input to translate the nominal zero and full-scale input range 
endpoint values indicated, to engineering units per the 
requirements of your application.  Up to 8 characters may be 
used to specify constants and scientific notation is supported.  
Up to 6 characters may be used to describe the engineering 
units of the scaled input and output values.  For example, a 
4-20mA input signal range may be scaled to 0 to 5000 GPM.  
The equation only operates on the equivalent scaled input 
values.  The computed output value is also scaled to nominal 
zero and full-scale output range endpoint values for the 
voltage or current output range selected. 

Transmitter - Equation:

  Up to 200 characters may be used to 

specify an output equation that is the mathematical 
combination of up to four inputs (894M), or two inputs 
(892M).  A free-

form equation is entered in “in-fix” notation 

that uses floating-point constants, scaled input channel 
variables, standard operators (+, -, *, /, ( )), plus square root 
(SQR( )), absolute value (ABS( )), minimum select (MIN( )), 
maximum select (MAX( )), exponential (EXP( )), natural 
logarithm (LN( )), logarithm base 10 (LOG10( )), power 
(POWER( )), sine (SIN( )), cosine (COS( )), tangent (TAN( )), 
arc sine (ASIN( )), arc cosine (ACOS( )), and arc tangent 

(ATAN( )).  Support for IF-THEN-ELSE, plus AND & OR, >, 
>=, <, <=, =, <> constructs are included.  
Constants are single precision floating-point values (scientific 
notation supported) and are limited to 8 characters.  The 
computed output is then scaled to nominal output range 
endpoints. 

Transmitter - Show Simulator:

 The Show Simulator function is 

used to test your equation and ensure that a correct output 
response within range is produced, without having to drive 
the inputs with real world signals.  Slide controls are provided 
to vary simulated input signals (click and drag with your 
mouse).  Fine control of the slide controls is also possible via 
your arrow keys.  Error checking in this area is limited and it 
is up to the user to verify correct formulation for all possible 
conditions of input and output.  As such, use of the Show 
Simulator function is highly recommended for critical control 
applications. 

Visual Over-Range Indicator:

  A yellow LED for each channel 

provides visual status indication of when the input signal is 
out of range (LED is ON for over-range). 

Output HOLD Function:  

A TTL or open collector/drain signal 

(5V logic) may be wired directly to the HOLD terminal of the 
module to hold the transmitter’s output at the last value.  
HOLD is asserted low (with respect to COM) and pulled-up 
internally.  The HOLD circuit is part of the input circuit and 
isolated from the output circuit. 

 

WARNING:

  Input return (RTN) and common (COM) are not 

equivalent potentials and should never be tied together.  
Make sure that common is not inadvertently tied to ground 
which may connect to input return. 

 
Other IntelliPack Configuration Software Capabilities 

In addition to configuring all features of the module described 
above, the IntelliPack Configuration Software includes additional 
capabilities for testing and control of the module as follows: 
 

 

Monitors the input and output signal values and allows 
polling to be turned on or off. 

 

Provides a “Show Simulator” function to simulate input 
variations and test the programmed equation. 

 

Allows a configuration to be uploaded or downloaded to/from 
the module.  Also provides a means to rewrite a module’s 
firmware if the microcontroller is replaced or a module’s 
functionality is updated. 

 

Provides controls to separately calibrate the input and output 
stages and restore the original factory input or output 
calibration in case of error. 

 

Provides a control to reset a module. 

 

Provides a control to adjust a transmitter’s output signal 
independent of the input signals (includes timed override). 

 

Allows optional user documentation information to be written 
to the module.  Documentation fields are provided for tag 
number, comment, configured by, location, and identification 
information.  This information can also be uploaded from the 
module and printed via this software. 

 

Allows a module’s complete configuration to be printed in an 
easy to read, two-page form, including user documentation. 

 

Includes on-line help and context (field) sensitive help 

functions.

 

For additional information on the IntelliPack Configuration 

Software, refer to the Transmitter Configuration Manual  
8500-570. 

Содержание IntelliPack 895M Series

Страница 1: ...cess Current Voltage Inputs USER S MANUAL ACROMAG INCORPORATED 30765 South Wixom Road Wixom MI 48393 2417 U S A Tel 248 295 0880 Fax 248 624 9234 Copyright 1998 Acromag Inc Printed in the USA Data and...

Страница 2: ...NT are registered trademarks of Microsoft Corporation 1 0 INTRODUCTION These instructions cover hardware functionality of the transmitter models listed in Table 1 Supplementary sheets are attached fo...

Страница 3: ...ash memory and EEPROM This allows the functionality of this device to be reliably reprogrammed thousands of times Fully Isolated Input output and power are isolated from each other for safety and incr...

Страница 4: ...ically protected with an anti static bag during shipment However it is recommended that the module be visually inspected for evidence of mishandling prior to applying power This circuit utilizes stati...

Страница 5: ...trical Code for installations within Canada and in accordance with the authority having jurisdiction This equipment is suitable for use in Class I Division 2 Groups A B C and D or non hazardous locati...

Страница 6: ...solution must also be scaled to the nominal zero and full scale endpoints of the selected output range Up to 200 characters may be entered into the equation field to define a formula that relates the...

Страница 7: ...A B A D THEN A ELSE C 12 56 When formulating an equation or response it is important to keep the limits of module resolution in mind see Table 5 In some cases it may be necessary to normalize your va...

Страница 8: ...ir services are available from Acromag 6 0 SPECIFICATIONS 892M 0500 C Two I V Inputs Single Process I V Output 894M 0500 C Four I V Inputs Single Process I V Output General The IntelliPack Model 89XM...

Страница 9: ...LSB 8 4 20mA DC 16797 953nA LSB 2 0 5V DC 26298 190uV LSB 1 0 10V DC 26298 380uV LSB IMPORTANT Input COM and RTN are not the same potential and should never be connected together either directly or th...

Страница 10: ...t exceed 36VDC peak to avoid damage to the module Table 8 89XM Supply Current Supply Voltage Supply Current SPA Connected Supply Current SPA Not Connected 10V 330mA 300mA 12V 250mA 230mA 15V 200mA 175...

Страница 11: ...al EXP natural logarithm LN logarithm base 10 LOG10 power POWER sine SIN cosine COS tangent TAN arc sine ASIN arc cosine ACOS and arc tangent ATAN Support for IF THEN ELSE plus AND OR constructs are i...

Страница 12: ...N I3 2 2 2 3 2 6 2 5 2 4 I4 V4 RTN INSTAL L V TO I JUMPER AT INPUT FOR CURRENT INPUTS TRANSIENT VOL TAGE AND NOISE SUPPRESSION DEVICES ARE NOT SHOWN 4 9 9 4 9 9 K 5 4 9 K 1 6 VOL TS 4 9 9 5 4 9 K SERI...

Страница 13: ...LO Y LO Y H I Y X XL YH YL XH XL YL X LO X H I ANALOG INPUT X In pu t Sen s o r Ty p es Vol tag e DC M i l l i am p ere s DC AC Curren t wi th AC Se ns or I nput 1 2 Cal Val u e Cal HI Cal LO Val u e...

Страница 14: ...ONFIGURATION RUNNING WINDOWS 95 OR NT S E E USE R S MA NUA L MODULE CONFIGURA TION CONFIGURA TION P ORT FOR POWER RUN PWR LE D GREE N OV ERRA NGE LE D s YE LLOW 10 TO 36VD C TB4 A cromag R U N I N P U...

Страница 15: ...H HOLD DEASSERTED HI G H OR OPEN THE OUTPUT W I L L TRACK I N PUT CHANGES HOLD I S ASSERTED LOW AND W I L L HOLD THE TRANSM I T TER OUTPUT AT THE LAST VALUE SHI EL DED CABL E TB1 CURRENT J UM PER V2...

Страница 16: ...____________________________________ 16 Acromag R U N 1 2 3 4 INPU T STATU S 118 9 4 68 95 3 3 75 R 2 34 59 4 DIN EN 5 0 0 2 2 3 5 mm T RAIL DIN MO UNTING C L SCREWDRIVER SL O T FO R REMO VAL FRO M T...

Страница 17: ...________________________________________________ 17 Revision History The following table details the revision history for this document Release Date Version EGR DOC Description of Revision 03 AUG 2017...

Отзывы: