安科瑞电气股份有限公司
34
4.4
节点温度值显示故障
4.4 Wireless Temperature Fault
“节温”菜单无温度值显示或无某一路温度值显示?
On the
“
Temp
”
interface, the device shows
“
No Nodes or Nodes Fault
”?
可能原因:传感器电池开关未打开或未启动,传感器不配对。
Reason: Active wireless temperature sensor battery is closed or passive wireless temperature sensor
does not work, or the sensor is not matched to the device
.
处理方法:(
1
)查看无线温度传感器的电池开关是否拨到“
ON
”端?(电池开关从
OFF
端拨
到
ON
端后,无线温度传感器上的绿灯亮灭闪烁
2
次表示开关接通正常,否则等待
5s
后重拨);查
看无源测温传感器相应回路是否正常运行,且电流
8A
以上。
Solvent: (1) Check up the active wireless temperature whether its battery switch is
“
ON
”
? (When the
battery switch turn to ON from OFF, the green light will lighting twice, it is worked, otherwise, wait for 5s
and turn on it again); check up the circuit whether it worked with the current above 8A.
(
2
)查看装置上的条码与无线温度传感器上的条码是否一致,不一致时找到对应的无线温度传
感器更换或重新配对无线温度传感器(详见本说明书
2.3
章节下的“节温设置”)。
(2) Check up the bar code on wireless temperature sensor and device, if they are not same, find out
the sensors with same bar code or bind the sensors online (the detailed method is at
“
Sensor Setting
”
in
chapter 2.3).