“节温设置”,子菜单下可在线绑定温度传感器,绑定方法为:进入节温设置界面后通过左
右键先选中要绑定的节点,然后按“
Enter
”键,光标会选中“
0x
F
FFF
”,查看传感器上标签,比如
“
FF FF FF FF FF FF 07 E3
”,
ATE400
传感器的标签为“
119071023007E3
”,通过左右键输入“
0x07E3
”,
再按“
Enter
”键确认,光标会定位到节点名称上,完成后按“
SET
”键退出,如果有修改,界面会
提示是否保存修改过的设置,再按“
Enter
”键保存即可。如果传感器为
ATE100/200
且关闭状态请
打开传感器开关。在线绑定方式适合修改个别传感器的配对,多个传感器的配对建议使用配套调试
软件。
(
V1.36
及以上版本支持手动输入
ID
)
.
“
Sensor Setting
”
, we can bind sensor ID online, the method is: enter the submenu and select
node by left or right button, then press
“
Enter
”
,
“
0x
F
FFF
”
will be selected, check the label on the sensor,
like
“
FF FF FF FF FF FF 07 E3
”
, the label of ATE400 is like
“
119071023007e3
”
, input
“
0x07E3
”
by left or right
button, then press
“
Enter
”
button, the cursor will be back to node selected. Press
“
SET
”
and back to last
interface, if modified, prompt information will be show on the screen, press
“
Enter
”
button for confirm. If
sensor type is 2.4GHz, and it is closed
,
turn on the switch. Binding sensor ID online is suit for a few
sensors, use debug software if there are a large number of sensors.
(User can input sensor ID manually if
the version is V1.36 and above).
“节温校准”,子菜单下可校准已绑定传感器的温度,校准方法为:进入校准界面后通过左右
键先选中要校准的节点,然后按“
Enter
”键,光标会选中温度值,修改为当前实际温度值,再按“
Enter
”
键确认(光标会定位到节点名称上),修改完成后按“
SET
”键退出,如果有修改,界面会提示是否
保存修改过的设置,然后再按“
Enter
”键保存即可,按“
SET
”键取消操作。
“
Calibrate
”
, we can calibrate the temperature values of registered sensors, the method is: enter
the submenu and select node by left or right button, then press
“
Enter
”
, the temperature value will be
selected, modify the value to current temperature, then press
“
Enter
”
button (node will be selected),
after all of temperature values have be modified, press
“
SET
”
, if modified, prompt information will be
show on the screen, press
“
Enter
”
button to confirm, press
“
Set
”
button to cancer.
“继电控制”,子菜单下可设置开出模式,模式分为:
“
DO Control
”, we can set the mode of relay output, the
3 modes are:
ON
:设备上电后,继电器常闭触点为断开,常开触点为闭合,适用于手动控制(
After the
device power on, the relay output closing contactor is open, opening contact is close, it is suitable for
manual
);
OFF
:设备上电后,继电器常闭触点为闭合,常开触点为断开,适用于手动控制(
After the
device power on, the relay output closing contactor is close, opening contact is open, it is suitable for
manual
);
Def
.
:由内部逻辑控制继电器的闭合或断开(