![Acrel APM830 Скачать руководство пользователя страница 61](http://html1.mh-extra.com/html/acrel/apm830/apm830_installation-and-operation-instruction-manual_2841076061.webp)
56
Other settings of analog input: Refer to the 1st analog input settings
5603
Setting of the 2nd analog input
5606
Setting of the 3rd analog input
5609
Setting of the 4th analog input
5612
Setting of the 5th analog input
5615
Setting of the 6th analog input
5618
Setting of the 7th analog input
5621
Setting of the 8th analog input
5624
Setting of the 9th analog input
5627
Setting of the 10th analog input
5630
Setting of the 11th analog input
5633
Setting of the 12th analog input
5636
Setting of the 13th analog input
5639
Setting of the 14th analog input
5642
Setting of the 15th analog input
5645
Setting of the 16th analog input
5648
Setting of the 17th analog input
5651
Setting of the 18th analog input
5654
Setting of the 19th analog input
5657
Setting of the 20th analog input
5660
Setting of the 21st analog input
5663
Setting of the 22nd analog input
5666
Setting of the 23rd analog input
5669
Setting of the 24th analog input
5672
Setting of the 25th analog input
5675
Setting of the 26th analog input
5678
Setting of the 27th analog input
5681
Setting of the 28th analog input
5684
Setting of the 29th analog input
5687
Setting of the 30th analog input
5690
Setting of the 31st analog input
5693
Setting of the 32nd analog input
Note: 1. Read-write property: "RO" is read-only, parameter is read with 0X03H command; "R/W" is readable and writable, and system
parameter is written with 0X10H command. Do not write data to unlisted or unwritable Address.
2
、
For Int32 type data, the high bits are in the front and the low bits are in the back
Register
(WORD)
Description
Unit
Data Type
Note
5600
Setting
of
the
1st
analog input
Input
type
and
decimal point of
display
Int16 (RW)
High byte: Input
type
(1:4-20mA,
2:0-20mA, 3:1-5V,
4:0-5V)
Low
Byte:
Decimal point of
display (0-3)
For example: 4-20mA is
selected for the
input
type , and decimal point
is 3 digits. The display
value of input high point
is set to 5000, and the
display value of input low
point is 0.
When the analog input is
20mA, the display value
is 5.000, when the analog
input is 4mA, the display
value is 0.000, and when
the analog input is 12mA,
the display value is 2.500.
5601
Display value of
input high point
Int16 (RW)
The display value
of input high point
(
0-9999
)
5602
Display value of
input low point
Int16 (RW)
The display value
of input low point
(
0-9999
)
Register
(WORD)
Description
Unit
Data Type
Note
5696-5727
Inverse value of No.1-32 analog
Input
Int16 (RO)
Inverse value of No.1-32 analog Input
5728-5759
The actual value of No.1-32 analog
Input
0.001
Int16 (RO)
The unit is mA when the input selection is 4-20mA
or 0-20mA, and the unit is V when 1-5V or 0-5V is
selected.