Examples are as follows:
Set Phase A overcurrent alarm of the first group of alarm enabled.
Action value: The action value is a primary value. For example, if the alarm value is set to 5.500A, when
Phase A current value exceeds 5.500A, the alarm condition is triggered and the timer starts.
Action delay time: When the alarm condition is triggered, if Phase A current value exceeds 5.500A, an alarm
record will be generated after the setted delay time (accurate to the second), Alarm group (alarm 1), alarm type
(Phase A overcurrent), alarm time (eg: 2017-5-12 14:15:20) will be recorded. If DO is associated with this alarm,
the DO acts (see DO settings).
Recovered value: The recovered value is a primary value. For example, if the recovered value is set to
5.400A, after Phase A overcurrent alarm has occurred, when Phase A current value is lower than 5.400A, the
released alarm condition is triggered and the timer starts. .
Recovered delay time: When the triggered alarm condition is released, if Phase A current value has been
lower than 5.400A, the released alarm record will be generated after the setted delay time (accurate to second),
and the alarm group (Alarm1), alarm type (Phase A overcurrent), the released alarm time (eg 2017-5-12 14:17:20)
will be recorded. If DO is associated with this alarm, the DO returns to its initial state. It can be calculated that the
alarm duration is 2 minutes.
Note: The alarm is invalid when both the action value and the recovered value are zero.
6.5 DO Settings
On the main interface, press Menu to enter the menu interface, press
∨
until
“
Parameter Setting
”
is
highlighted, and press
√
to enter the parameter setting interface. Press
∨
until
“
DO Setting
”
is highlighted, press
√
to enter the DO setting interface. Press
∧
or
∨
to switch the item set by DO, press Enter to enter the setting of
the item, press + or - to change, press > to shift, after the current item setting is changed, press Exit to exit the item
setting. Continue to repeat the above steps to modify the settings. After the change is completed, press Exit to enter
the password. The default password is 0001 (customer can change the password according to the password setting set
by 7.11 system. If you forget the password, you need to contact us). Press SaveExit to save the changes and exit,
press Esc to exit without saving the changes.
Setting item
range
Description
DO channel
DO01~DO30
DO channel selection
Output selection
Alarm 1 control, alarm 2 control, DO Control method selection
Here, you need to check the alarm type associated with DO. For
the specific alarm type, please refer to Table 1 in 5.1.2, that is, the
DO action when the alarm is generated. If it is not checked, it is
not associated, that is, DO does not operate when the alarm is
generated.