![Acrel APM830 Скачать руководство пользователя страница 52](http://html1.mh-extra.com/html/acrel/apm830/apm830_installation-and-operation-instruction-manual_2841076052.webp)
47
15376-16143 Power factor alarm event
16144-16911 Total harmonic alarm event
16912-17679 Total even harmonic alarm event
17680-18447 Total odd harmonic alarm event
18448-19215 Digital input alarm event
19216-19983 Other alarm events
Associated alarm configuration of other relays: Refer to associated alarm configuration of relay 1.
2602
Associated alarm configuration
of relay 2
2614
Associated alarm configuration of
relay 3
2626
Associated alarm configuration
of relay 4
2638
Associated alarm configuration
of relay 5
2650
Associated alarm configuration of
relay 6
2662
Associated alarm configuration
of relay 7
2674
Associated alarm configuration
of relay 8
2686
Associated alarm configuration of
relay 9
2698
Associated alarm configuration
of relay 10
2710
Associated alarm configuration
of relay 11
2722
Associated alarm configuration of
relay 12
2734
Associated alarm configuration
of relay 13
Register
(WORD)
Description
Unit
Data Type
Note
2500
Function selection of
relay
1
UInt16 (RW)
0: Remote control;
1: First group alarm;
2: Second group alarm
2501-2531
Function selection of
relay
2-32
Same as function selection of relay 1
2532
Output pulse width of relay 1
(effective by remote control)
1s
Int16 (RW)
When the delay time 0, it is a level trigger mode;
when it is greater than 0, it is a pulse trigger
mode.
2533-2563
Output pulse width of relay
2-32 (effective by remote
control)
Same as output pulse width of relay 1
2564-2569
Reserve
2570-2571
Initial state of switch input
Int32 (RW)
Bits0:DI1, and so on, Bits31:DI32;
1: Initial state is ON; 0: Initial state is OFF
2572-2573
Initial state of switch output
Int32 (RW)
Bits0:DO1, and so on, Bits31:DO32;
1: Initial state is ON; 0: Initial state is OFF
2574-2579
Reserve
2580-2581
Current status of switch input
Int32 (RO)
Bits0:DI1, and so on, Bits31:DI32;
1: Initial state is ON; 0: Initial state is OFF
2582-2583
Current status of switch
output
Int32 (RW)
Bits0:DO1, and so on, Bits31:DO32;
1: Initial state is ON; 0: Initial state is OFF
2584-2589
Reserve
2590-2601
Associated alarm
configuration of relay 1
Int32(RW)*6
See 2.9 DO settings in the instructions