- 2 -
Multi-tariff and
functions
Adapt 4 time zones, 2 time interval
lists, 14 time interval by day and 4
tariff rates
□
Max demand and occurrence time
□
Frozen data on last 48 months, last
90days
□
Date, time
□
Communicatio
n
Communication interface: RS485,
Communication protocol:
MODBUS-RTU
■
4 Technical parameter
Table 2 technical parameter descriptions
project
performance parameter
Specification
3 phase 3 wires
3 phase 4 wires
Meas
urem
ent
Voltage
Reference
voltage
3
×
100V
、
3
×
380V
3
×
57.7/100V
、
3
×
220/380V
Voltage range
3
×
100V - 3
×
450V
3
×
57.7/100V - 3
×
260/450V
Consumption
<10VA(Single phase)
Impedance
>2MΩ
Accuracy class
Error
±
0.2%
Current
Input current
3
×
1(6)A
,
3
×
10(80)A
Consumption
<1VA Single phase rated current
Accuracy class
Error
±
0.2%
Power
Active, reactive, apparent power, error
±
0.5℅
Frequency
45
~
65Hz
,
Error
±
0.2%
Mete
ring
Energy
Active energy(Accuracy class: 0.5); reactive energy(Accuracy class 2)
Clock
≤
0.5s/d
Digit
signal
Energy pulse output
1 active photocoupler output
pulse
Width of pulse
80±20ms
Pulse constant
400imp/kWh,10000imp/kWh(Correspond with the basic current)
com
mun
icati
on
Interface and
communication protocol
RS485
:
Modbus RTU
Range of communication
address
Modbus RTU:1~ 254
;
Baud rate
1200bps~38400bps
envir-
onm
ent
working temperature
-25
℃
~+55
℃
Relative humidity
≤95℅(No condensation)
Содержание ADL3000-E