- 15 -
0095H
First communication path
:
Parity bit
(
high 8 bit
)
Stop bit
(
low 8 bit
)
2
R/W
parity bit
:
0
:
None
1
:
Odd
2
:
Even
stop bit
:
0
:
one stop bit
1
:
two stop bit
0096H-0098H Reserve
009FH-00A3H reserve
00A4H-00A5H Current total apparent Energy
4
R
Resolution
:
0.01kVAh
00A6H
Code
2
R/W
1-9999
00A7H-00C9H reserve
00CAH
The back light time
00CBH-0120H Reserve
0121H
Daily frozen time:Hour
2
R/W
0122H
Monthly frozen time:day
、
hour
2
R/W
0123H-0163H Reserve
0164H
Active power of A phase
4
R
Complement form
Resolution
:
0.001kW
0166H
Active power of B phase
4
R
0168H
Active power of C phase
4
R
016AH
Total active power
4
R
016CH
Reactive power of A phase
4
R
Complement form
Resolution
:
0.001kvar
016EH
Reactive power of B phase
4
R
0170H
Reactive power of C phase
4
R
0172H
Total reactive power
4
R
0174H
Apparent power of A phase
4
R
Complement form
Resolution
:
0.001kVA
0176H
Apparent power of B phase
4
R
0178H
Apparent power of C phase
4
R
017AH
Total apparent power
4
R
017CH
Power factor of A phase
2
R
Complement form
Resolution
:
0.001
017DH
Power factor of B phase
2
R
017EH
Power factor of C phase
2
R
017FH
Total power factor
2
R
0180H
Maximum demand for forward active
power on the day
2
R
Three decimal places
are reserved for daily
demand, and the
occurrence time is
arranged in minutes
and hours.
0181H
Occur time:minute
、
hour
2
R
0182H
Maximum demand for reverse active
power on the day
2
R
0183H
Time of occurrence: minute
、
hour
2
R
0184H
Maximum demand for forward
reactive power on the day
2
R
0185H
Time of occurrence: minute
、
hour
2
R
0186H
Maximum demand for reverse reactive
2
R
Содержание ADL3000-E