- 24 -
a period
0006
Clear out
0400
UI record
UI status
Bit0:
Over-voltage on A phase
Bit1:
Over-voltage on B phase
Bit2:
Over-voltage on C phase
Bit3:
Lose-voltage on A phase
Bit4:
Lose-voltage on B phase
Bit5:
Lose-voltage on C phase
Bit6:
Reversing on A phase
Bit7:
Reversing on B phase
Bit8:
Reversing on C phase
Bit9:
Over current on A phase
Bit10:
Over current on B phase
Bit11:
Over current on C phase
Bit12:
Low current on A phase
Bit13:
Low current on B phase
Bit14:
;
Low current on C phase
0700
Time calibration
Example: The address is 001 at present, and we send the code: 01 03 30 01 00 06
9B 08 to get the last event record, and the slave station will give back: 01 03 0C 12 01
08 0A 01 01
(
2018/1/8 10:1:1
)
01 00
(
powered
)
00 00
(
no details
)
00 00
(
reserved
)
80 23