- 11 -
8.4 Date settings
Num
Second menu
Symbol
Mean
Range
1
ADDR
Communicate’s ADDR
settings
1-254
2
Baud
Baud choose
1200
、
2400
、
4800
、
9600
、
19200
、
38400
3
Pari
Parity choose
None
、
Odd
、
Even
4
LED
Backlight time
0-255minutes
,
more than
000 stay light-on
5
PL
Wiring sample
3P4L:3 phase 4 wires
3P3L:3 phase 3 wires
6
DIR
direction of current
no-Forward
yes-Reverse
7
S-TY
Apparent power
calculation method
PQS
RMS
8
EF-E
time-sharing
measurement function
EF-Function on
E-Function off
9
Pt
Voltage transformer
settings
1-9999
10
Ct
Current transformer
settings
1-9999
11
CoDE
Code settings
1-9999
12
PHAS
Phase angle calculation
method
No-Angle between each
current and each voltage
Yes-Angle between
three-phase current and
phase a voltage
13
nost
Starting power shield
Shielding range:0.1-2.0%
(*UnIn)
9 Communication description
The meter adapts MODBUS-RTU protocol, and the baud rate can be chosen from 1200bps
、
2400 bps
、
4800 bps
、
9600bps and 19200 bps. The parity is None.
The meter needs shielded twisted pair conductors to connect. Customers should consider the
whole network
’
s parameters such like communication wire
’
s length, the direction, communication
transformer and network cover range, etc.
Note:
1
、
Wiring should follow the wiring requirements;
2
、
Connect all the meter in the RS485 net work even some do not need to communication,