Wiring
Page 3
9
Power Specifications(Not applicable for North America)
NOTE:
Electric auxiliary heating type circuit breaker/fuse need to add more than 10 A.
Indoor Power Supply Specifications
MODEL
(Btu/h)
≤
18K
19K~24K 25K~36K 37K~48K 49K~60K
POWER
PHASE
1 Phase
1 Phase
1 Phase
1 Phase
1 Phase
VOLT
VOLT
VOLT
VOLT
208-240V 208-240V 208-240V 208-240V 208-240V
CIRCUIT BREAKER/
FUSE(A)
25/20
32/25
50/40
70/55
70/60
MODEL
(Btu/h)
≤
36K
37K~60K
≤
36K
37K~60K
POWER
PHASE
3 Phase
3 Phase
3 Phase
3 Phase
380-420V
380-420V
208-240V
208-240V
CIRCUIT BREAKER/FUSE(A)
25/20
32/25
32/25
45/35
MODEL
(Btu/h)
≤
18K
19K~24K 25K~36K 37K~48K 49K~60K
POWER
PHASE
1 Phase
1 Phase
1 Phase
1 Phase
1 Phase
208-240V 208-240V 208-240V 208-240V 208-240V
CIRCUIT BREAKER/
FUSE(A)
25/20
32/25
50/40
70/55
70/60
MODEL
(Btu/h)
≤
36K
37K~60K
≤
36K
37K~60K
POWER
PHASE
3 Phase
3 Phase
3 Phase
3 Phase
380-420V
380-420V
208-240V
208-240V
CIRCUIT BREAKER/FUSE(A)
25/20
32/25
32/25
45/35
Outdoor Power Supply Specifications