background image

WARNING

When performing the following steps, do not touch

stripped end of jumper or SPARK terminal. The

ignition circuit generates over 10,000 volts and

electrical shock can result.

Energize the module and immediately touch one end of

the jumper firmly to the GND terminal on the module. Move

the free end of the jumper slowly toward the SPARK

terminal until a spark is established.

Pull the jumper slowly away from the terminal and note the

length of the gap when sparking stops. Check table below

.

ARC LENGTH

ACTION

N

o

 a

rc

 o

r a

rc

 l

e

s

s

Check 

external 

fuse, 

if 

provided.

than 1/8 inch [3 mm]

Verify power at module input

terminal.

Replace module if fuse and

power okay.

Arc 1/8 inch [3 mm]

Voltage output is okay.

or longer.

STEP 4: Check pilot and main burner lightoff.

Set the thermostat to call for heat.

Watch the pilot burner during the ignition sequence. See

if:

Ignition spark continues after the pilot is lit.

The pilot lights and the spark stops, but main burner

does not light.

S8610B,H; S8670D only: 

The pilot lights, the spark stops

and main burner lights, but the system shuts down.

If so, ensure adequate flame current as follows.

Turn off furnace at circuit breaker or fuse box.

Clean the flame rod with emery cloth.

TROUBLESHOOTING

IMPORTANT

1.

The following service procedures are provided as

a general guide. Follow appliance manufacturer’s

service instructions if available.

2.

On lockout and retry models, meter readings

between gas control and ignition module must be

taken within the trial for ignition period. Once the

ignition module shuts off, lockout models must be

reset by setting the thermostat down for at least

one minute before continuing. On retry models,

wait for retry or reset at the thermostat.

3.

If any component does not function properly,

make sure it is correctly installed and wired before

replacing it.

4.

The ignition module cannot be repaired. If it mal-

functions, it must be replaced.

5.

Only trained, experienced service technicians

should service intermittent pilot systems.

Perform the checkout on page 12 as the first step in

troubleshooting. Then check the appropriate troubleshoot-

ing guide (Fig. 15 or 16) and the schematic diagram (Fig .

17 or 18) to pinpoint the cause of the problem. If trou-

bleshooting indicates an ignition problem, see Ignition

System Checks below to isolate and correct the problem.

Following troubleshooting, perform the checkout proce-

dure (page 12) again to be sure system is operating

normally.

IGNITION SYSTEM CHECKS

STEP 1: Check ignition cable.

Make sure:

Ignition cable does not run in contact with any metal

surfaces.

Ignition cable is no more than 36 inches [0.9 meters]

long.

Connections to the ignition module and to the igniter or

igniter-sensor are clean and tight.

Ignition cable provides good electrical continuity.

STEP 2: Check ignition system grounding. 

Nuisance shut-

downs are often caused by a poor or erratic ground.

A common ground, usually supplied by the pilot burner

bracket, is required for the module and the pilot burner/

igniter-sensor.

Check for good metal-to-metal contact between the

pilot burner bracket and the main burner.

Check the ground lead from the GND(BURNER)

terminal on the module to the pilot burner. Make sure

connections are clean and tight. If the wire is dam-

aged or deteriorated, replace it with No. 14 through

No.18 gauge, moisture-resistant, thermoplastic insu-

lated wire with 105

°

 C [221

°

 F] minimum rating.

Check the ceramic flame rod insulator for cracks

or evidence of exposure to extreme heat, which

can permit leakage to ground. Replace pilot burner/

igniter-sensor and provide shield if necessary.

If flame rod or bracket are bent out of position,

restore to correct position.

STEP 3: Check spark ignition circuit. 

You will need a short

jumper wire made from ignition cable or other heavily

insulated wire

.

Close the manual gas valve.

Disconnect the ignition cable at the SPARK terminal on

the module.

16

Fig. 14—Examples of unsatisfactory pilot flames.

LAZY YELLOW FLAME

WAVING BLUE FLAME

NOISY LIFTING BLOWING FLAME

HARD SHARP FLAME

SMALL BLUE FLAME

CHECK FOR LACK OF GAS FROM:

• CLOGGED ORIFICE FILTER

• CLOGGED PILOT FILTER

• LOW GAS SUPPLY PRESSURE

• PILOT ADJUSTMENT AT MINIMUM

CHECK FOR LACK OF AIR FROM:

• DIRTY ORIFICE

• DIRTY LINT SCREEN, IF USED

• DIRTY PRIMARY AIR OPENING,

  IF THERE IS ONE

• PILOT ADJUSTMENT AT MINIMUM

CHECK FOR:

• EXCESSIVE DRAFT AT PILOT 

  LOCATION

• RECIRCULATING PRODUCTS

  OF COMBUSTION

CHECK FOR:

• HIGH GAS PRESSURE

THIS FLAME IS CHARACTERISTIC 

OF MANUFACTURED GAS

CHECK FOR:

• HIGH GAS PRESSURE

• ORIFICE TOO SMALL

M2233A

APPEARANCE

CAUSE

TRIAL FOR IGNITION

Pilot Ignition

Following prepurge timing (S8670), or on the call for heat

(S8610), the module energizes the first main valve opera-

tor. The first main valve opens, which allows gas to flow to

the pilot burner. At the same time, the electronic spark

generator in the module produces an over 10,000 volt spark

pulse output. The voltage generates a spark at the igniter

(S8610A,B) or igniter-sensor (S8610F,H; S8670) that lights

the pilot.

If the pilot does not light, or the pilot flame current is not

at least 1.0 

μ

A and steady, the module will not energize the

second (main) valve and the main burner will not light.

S8610A,F will continue to spark as long as the thermostat

calls for heat, or until the pilot lights.

Safety Lockout (S8610B,H; S8670D)

These modules provide 100 percent shutoff and safety

lockout. A timer in these models starts timing the moment

the trial for ignition starts. Ignition spark continues only until

the timed trial for ignition period ends. Then the module

goes into safety lockout. Lockout de-energizes the first

main valve operator and closes the first main (pilot) valve in

the gas control, stopping pilot gas flow. The control system

must be reset by setting the thermostat below room tem-

perature for one minute or by turning off power to the

module for one minute.

MAIN BURNER OPERATION

When the pilot flame is established, a flame rectification

circuit is completed between the sensor and burner ground.

The flame sensing circuit in the module detects the flame

current, shuts off the spark generator, and energizes the

second main valve operator. The second main valve opens

and gas flows to the main burner, where it is ignited by the

pilot burner. On lockout models, the flame current also

holds the safety lockout timer in the reset (normal) operat-

ing condition.

When the call for heat ends, both valve operators are de-

energized, and both valves in the gas control close.

Fig. 13—S8670 normal operating sequence.

    69-0523

 15

M550

START

THERMOSTAT

PREPURGE

SPARK GENERATOR POWERED

PILOT BURNER OPERATION

OR

Pilot burner lights.

S8670  senses flame current.

Pilot burner does not light.

After 15 or 90 sec   , system

locks out; must be manually reset.

   Lockout timing is

   stamped on module.

a

a

STAGE 1

PREPURGE

STAGE 2

TRIAL FOR IGNITION

STAGE 3

MAIN BURNER 

OPERATION

END

FLAME CURRENT SENSED

MAIN BURNER OPERATION

Module monitors pilot flame 

current.

THERMOSTAT SATISFIED

Valves close, pilot and main 

burners are off.

POWER INTERRUPTION

System shuts off, restarts when power is 

restored.

PILOT FLAME FAILURE

Main valve closes.

S8670 starts trial for ignition.

Spark generator off.

Second valve operator (main) 

opens.

1

2

3

4

5

6

7

CALLS FOR HEAT

Combustion air blower starts.

First valve (pilot) operator opens.

Содержание B Series

Страница 1: ...al Designed and Manufactured in Accordance with ASME Code Section IV Heating Boilers E T L Listed ASME Code Construction and Stamped Photo shown may vary from actual model Model B_G Series Gas Fired C...

Страница 2: ...site http www ajaxboiler com Email info ajaxboiler com Ace Boiler Inc formerly Ace Buehler Inc is a division of Ajax Boiler Inc ACE BOILER INC E T L Listed Q Q Q Q Q Q Q Q Q Q Q Q Q Q Q Q Q Q Q Q Q Q...

Страница 3: ...e the heater so that leakage from tank or connections will be directed to a floor drain and will not damage adjacent area or lower level floors 2 The minimum clearance between a heater and a storage t...

Страница 4: ...is measured downstream of the gas pressure regu lator Do not exceed the maximum gas pressure specified on the rating plate 4 A trap drip leg must be installed upstream of the gas pressure regulator 5...

Страница 5: ...P OP Check Valve Pressure Relief Valve Pressure Temp Gauge Primary Operational Aquastat Unit Circulation Pump System Recirculation Pump Check Valve Pilot Safety Relay Ground Hi Limit Aquastat Control...

Страница 6: ...STANDARD FOR CSD 1 G 22225 N A HEADER COMB GAS VALVE SHUT OFF VALVE PILOT LINE PILOT LINE TYP COMB GAS VALVE TYP HEADER SHUT OFF VALVE B2 THRU B8 INDOOR OUTDOOR CSD 1 GAS TRAIN FOR MODELS B11 THRU B1...

Страница 7: ......

Страница 8: ...CONTROLS AND GAS TRAIN GAS FIRED COPPER FIN CONE COIL WATER HEATERS HEAVY DUTY INDUSTRIAL WATER HEATERS MINI PACK SEMI INSTANTANEOUS WATER HEATERS PACKAGED STORAGE WATER HEATERS CLEAN STEAM BOILERS AS...

Страница 9: ...and accept the product when received as conforming to their purchase order specifications and approved drawings All claims for non conformance errors shortages etc must be made within 10 days after re...

Страница 10: ...4 United States Tel 714 437 9050 Fax 714 437 9060 http www ajaxboiler com mail ajaxboiler com June 2010 Ace Heating Solutions LLC ACE Heating Solutions LLC 2701 S HARBOR BLVD SANTA ANA CA 92704 PHONE...

Страница 11: ...060 http www ajaxboiler com mail ajaxboiler com February 2007 ACE Heating Solutions LLC 2701 S HARBOR BLVD SANTA ANA CA 92704 PHONE 714 540 2230 FAX 714 540 2239 www aceheatingllc com Ace Heating Solu...

Страница 12: ...anta Ana California 92704 United States Tel 714 437 9050 Fax 714 437 9060 http www ajaxboiler com mail ajaxboiler com ACE Heating Solutions LLC 2701 S HARBOR BLVD SANTA ANA CA 92704 PHONE 714 540 2230...

Страница 13: ......

Страница 14: ......

Страница 15: ......

Страница 16: ...es at very high temperatures insulation shielding and air circulation may be necessary to protect the controls Proper insulation or shielding should be provided by the appliance manufac turer make sur...

Страница 17: ...o ground NOTE Earth ground is not required To connect the D80B follow the wiring diagrams sup plied with the vent damper or see Fig 8 for typical connec tions Connect Ignition Module 1 Connect remaini...

Страница 18: ...T DAMPER PLUG OPT 5 2ND OPERATOR 1ST OPERATOR PILOT COM MAIN VALVE DUAL VALVE COMBINATION GAS CONTROL Fig 2 S8610F H S8670D in a heating system with an atmospheric burner 5 TABLE 4 TERMINAL CROSS REFE...

Страница 19: ...9 0523 MV MV PV PV GND BURNER 24V GND 24V TH W VENT DAMPER PLUG SPARK 5 S8610A B POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED ALTERNATE LIMIT CONTROLLER LOCATION MAXIMUM C...

Страница 20: ...TOR PILOT COM MAIN VALVE DUAL VALVE COMBINATION GAS CONTROL PILOT BURNER GROUND PILOT GAS SUPPLY 9 69 0523 Fig 8 S8610F H S8670D in a heating system with an atmospheric burner and a D80B Vent Damper L...

Страница 21: ...23 Fig 10 S8610F H S8670D in a hydronic heating system with a D80D Vent Damper 2 MV MV PV PV GND BURNER 24V GND 24V TH W OPT VENT DAMPER PLUG OPT SPARK 4 S8610F H S8670D POWER SUPPLY PROVIDE DISCONNEC...

Страница 22: ...ne as described in Steps 1 and 5 below on initial installation and any time work is done involving the gas pip ing STEP 3 Reset the Module Turn the thermostat to its lowest setting Wait one minute As...

Страница 23: ...burner igniter sensor and provide shield if necessary If flame rod or bracket are bent out of position restore to correct position STEP 3 Check spark ignition circuit You will need a short jumper wire...

Страница 24: ...ing the pilot adjustment screw on the gas control clockwise to decrease or counterclockwise to increase pilot flame Following adjustment always replace pilot adjustment cover screw and tighten firmly...

Страница 25: ...V PV MV PV MAIN VALVE PILOT VALVE TO 24V GND TO 24V 3 3 Fig 17 Representative schematic for S8610F H See Fig 1 for hookup S8670 is similar except the timing circuit includes a purge timer See Fig 6 fo...

Страница 26: ...water pumps are in operating condition b Test low water cutoffs automatic feed water controls pressure and temperature limit control lers and relief valves in accordance with the manufacturer s recomm...

Страница 27: ...ntrol after compression nut has been tightened because this can result in gas leakage at connection 2 Square off and remove burrs from end of tubing 3 Push tubing into compression nut clearance hole u...

Страница 28: ...ot flame 6 Always replace pilot adjustment cover screw and tighten firmly after completing adjustment to assure pro per operation Service WARNING FIRE OR EXPLOSION HAZARD CAN CAUSE PROPERTY DAMAGE SEV...

Страница 29: ...e would result in personal injury and or loss of prop erty it is the responsibility of the installer to add devices safety limit controls that protect against or systems alarm supervisory systems that...

Страница 30: ...llation and adjustment CAUTION Check the installation for no flow switch operation Make appropriate adjustments to the sensitivity adjustment screw to be sure the switch restores fully at the desired...

Страница 31: ...ls The thermostat or the fuse will be damaged DO NOT allow any flame to impinge on the regulator vent tubing if sup plied It may clog and cause gas valve malfunction DO NOT use the gas cock to adjust...

Страница 32: ...or 6 for a typical connection diagram X XX UL INSTALLATION INSTRUCTIONS U S Registered Trademark Copyright 1995 Honeywell Inc All Rights Reserved L4008A B E L L6008A G H Aquastat Controllers APPLICATI...

Страница 33: ...R IGNITION TRANSFORMER RA89A RELAY RA817A PROTECTORELAY CONTROL BURNER MOTOR 24V THERMOSTAT 2 1 3 4 T T 1 2 3 4 M8785 Fig 5 Typical oil fired hydronic heating system with domestic hot water SETTING Co...

Страница 34: ...9 mm OD for both inlet and outlet Approval CE 0063AU1215 U S Registered Trademark Copyright 2000 Honeywell Inc All Rights Reserved INSTALLATION INSTRUCTIONS 69 1225 4 VR8104 VR8204 and VR8304 Intermit...

Страница 35: ...mine if the pressure regulator setting factory set will meet the appliance manifold requirements after conversion NOTE Convertible pressure regulator models suffix letter R do not have field adjustabl...

Страница 36: ...BINATION GAS CONTROLS 5 69 1225 4 Fig 1 Top view of convertible pressure regulator cap Install Adapters To Control If adapters are being installed on the control mount them as follows Flanges 1 Choose...

Страница 37: ...hanism to reduce the pilot flow if necessary If pilot adjustment is necessary proceed as follows 1 Remove pilot adjustment cover screw See Fig 6 2 The pilot adjustment is shipped at the full pilot gas...

Страница 38: ...eter reading Convert flow rate to Btuh as described in form 70 2602 Gas Controls Handbook and compare to Btuh input rating on appliance nameplate 3 IF CHECKING GAS INPUT WITH MANOMETER Make sure the g...

Страница 39: ...Non Regulating On Off U Models Non regulating VR8204U Valves are designed for application in various parts of Europe where a separate distinct pressure regulator is required The VR8204U is similar to...

Страница 40: ...f heater falls off this is usually a sign of lime in the coil The ACE coil will bang or knock if lim ing condition is severely restricting circulation Customers have reported operating ACE heaters and...

Отзывы: