95-5971—2

2

L4008A,B,E,L; L6008A,G,H REMOTE BULB AQUASTAT

®

 CONTROLLERS

The Aquastat® controller can be remotely mounted—

either vertically on a wall or panel, or directly on the boiler,

tank, or vessel.

If the system is filled, drain the system to a point below the

boiler tapping, or to wherever the sensing bulb is to be

installed.

Mounting the Ca

s

e

Remove the cover and fasten the case to the wall or

panel using the three mounting holes in the back of

the case.

When mounting the remote bulb, if desirable, route

the tubing to run through any of the other three

corner notches in the case. Be careful not to kink or

bend tubing sharply. Be sure bends have at least 1 in.

(25.4 mm) radius.

In

s

talling Remote 

B

ulb with Immer

s

ion W

ell

Fit well, if used, to sensing bulb snugly for good thermal

response. Insert bulb until it rests against the bottom of the

well; then hold it there while tightening the tubing clamp.

Screw the well into the boiler, tank or pipe tapping.

Insert the bulb into the well, pushing the tubing until

the bulb bottoms in the well.

Attach the retainer clamp to the end of the well spud.

Loosen the draw nut and spread the jaws of the

clamp with the screwdriver if necessary.

With the retainer clamp attached to the well spud (be

sure jaws of clamp hook over ridge at end of the

spud, as shown in Fig. 2, points A). Adjust tubing to fit

through retainer clamp groove, as shown at point B.

Tighten the draw nut so the retainer clamp is firmly

attached to the well spud and the tubing is held by

the clamp.

Mounting with 

B

ulb Compre

ss

ion Fitting

Screw the fitting into the boiler or pipe tapping.

Slide sealing washer onto the bulb.

Insert the bulb into the fitting until bulb bottoms.

Slide split sleeve into fitting.

Place clamps A and B on assembly so that sleeve is

drawn into fitting when screws are tightened.

N

O

T

E

:

Make sure that the nub on clamp A

engages space between sleeve and clamp.

Tighten clamp screws evenly.

M8777

WELL

BULB

SPUD

MOUNTING

CLAMP

A

DRAW 

NUT

TUBING

B

INSERT— MOUNTING CLAMP

SCREWDRIVER

SPREAD JAWS

TO FIT OVER

RIDGE ON 

WELL SPUD

JAWS

Fig. 2. Immersion well fitting.

IMPORTANT

Do not secure draw nut so tightly that retainer

clamp could cut or collapse tubing.

M8815

CLAMP B

CLAMP A

CLAMP SCREWS (2)

BULB 

COMPRESSION 

FITTING

SEALING 

WASHER

BULB

INSERTION LENGTH

APPROX. 3-3/16 IN. (81 MM)

SPLIT SLEEVE

Fig. 3. Bulb compression fitting.

Mounting with Capillary Compre

ss

ion

Fitting

Screw fitting into the boiler or pipe tapping.

Place packing nut on tubing.

Slide bulb completely through fitting.

Place composition disc and 4 slotted brass washers

on tubing in the order shown in Fig. 4. Turn brass

washers so that slots are 180 degrees to each other.

Slide seal assembly into fitting and tighten packing nut.

COMPOSITION DISK

(SLOTTED)

BOILER PLUG

CAPILLARY TUBING

EXAMPLE OF SLOTTED WASHERS 

ASSEMBLED 

IN PAIRS:

PACKING NUT

M8816

IMMERSION

BULB

Fig. 4. Capillary compression fitting.

WIRING

All wiring must agree with applicable codes and ordinances

and regulations in such matters as wire size, type of

insulation, and enclosure. The controllers are provided

with conduit knockouts in the top and bottom of case.

Refer to Fig. 5 or 6 for a typical connection diagram.

X-XX UL

INST

ALLA

TION INSTRUCTIONS

®U.S. Registered Trademark

Copyright © 1995 Honeywell Inc.  •   All Rights Reserved

L4008A,

B

,E,L; L

6

008A,G,H

Aqua

s

tat

®

 Controller

s

APPLICA

TION

These remote bulb (see Fig. 7), immersion type (see Fig. 1)

controllers operate in response to temperature changes in

hydronic heating systems and other heated liquids.

Electrical Ratings:

Switch ratings are shown on the inside cover of each

device. The electrical requirements on controlled equipment

must not exceed this rating.

L4008A—breaks the burner circuit on a rise in water

temperature. It is normally used as a limit controller.

When used as an operating controller or low limit, a

separate high limit control must be used.

L4008B—makes a control circuit on a rise in water

temperature. It is normally used as a circulator

controller to prevent circulator operation until boiler

water temperature is at or above the control setting.

L4008E—breaks the burner circuit and locks out on a

rise in water temperature. It is used as a high limit

controller where manual reset is desirable.

L4008L—is used as a 2-stage Aquastat® controller.

L6008A—makes the burner circuit on a drop in water

temperature. It is normally used as a circulator and

low limit cooling controller.

L6008G—is used as a 2-stage Aquastat® controller to

cycle 2-stage gas valve.

L6008H—is used as a low fire Aquastat® controller.

If immersion well or capillary compression fitting must be

ordered, refer to form 68-0040, Wells and Fittings for

Temperature Controllers, for part numbers and ordering

information.

INST

ALLA

TION

When In

s

talling thi

s

 Product…

1.

Read these instructions carefully. Failure to follow

them could damage the product or cause a hazard-

ous condition.

2.

Check the ratings given in the instructions and on

the product to make sure the product is suitable for

your application.

3.

Installer must be a trained, experienced service

technician.

4.

After installation is complete, check out product

operation as provided in these instructions.

CAUTION

Disconnect power supply before installation to

prevent electrical shock or equipment damage.

Depending on model and installation requirements, install

the temperature sensing bulb either in an immersion well

(see Fig. 2) that extends into the boiler or tank, or directly

immerse the temperature sensing bulb in the liquid. For

inst

al

la

ti

ons not

 usi

ng a 

well, secure the bulb with a bulb

compression fitting (see 

Fig. 3), 

or 

cap

illary 

compression

fitting (see Fig. 4). Order the well or the fitting separately.

The boiler manufacturer generally provides a tapping for

inserting the Aquastat® controller sensing element. Locate

this tapping in a representative point where typical water

temperature can be measured. Never locate the bulb or

protecting immersion well close to a hot or cold water inlet

or steam coil. Install the bulb in the supply line of an

indirect water heater, in the indirect water heater itself, or

in the feed riser about 6 in. (152 mm) above the boiler. If

the riser is valved, install the bulb between the boiler and

the valve.

95-5971-2

Fig. 1. Internal view.

M8806

SETPOINT

INDICATING DIAL

DIFFERENTIAL

ADJUSTMENT

WHEEL

ADAPTER CLAMP

SCREWS

INSERTION

ELEMENT

WITH VERTICAL MOUNTING OF IMMERSION WELL,

ELEMENT IS ATTACHED TO BOTTOM OF THE CASE.

SELECT MODELS HAVE SCREW TERMINAL, NOT TAB 

TERMINAL.

1

2

2

1

Содержание B Series

Страница 1: ...al Designed and Manufactured in Accordance with ASME Code Section IV Heating Boilers E T L Listed ASME Code Construction and Stamped Photo shown may vary from actual model Model B_G Series Gas Fired C...

Страница 2: ...site http www ajaxboiler com Email info ajaxboiler com Ace Boiler Inc formerly Ace Buehler Inc is a division of Ajax Boiler Inc ACE BOILER INC E T L Listed Q Q Q Q Q Q Q Q Q Q Q Q Q Q Q Q Q Q Q Q Q Q...

Страница 3: ...e the heater so that leakage from tank or connections will be directed to a floor drain and will not damage adjacent area or lower level floors 2 The minimum clearance between a heater and a storage t...

Страница 4: ...is measured downstream of the gas pressure regu lator Do not exceed the maximum gas pressure specified on the rating plate 4 A trap drip leg must be installed upstream of the gas pressure regulator 5...

Страница 5: ...P OP Check Valve Pressure Relief Valve Pressure Temp Gauge Primary Operational Aquastat Unit Circulation Pump System Recirculation Pump Check Valve Pilot Safety Relay Ground Hi Limit Aquastat Control...

Страница 6: ...STANDARD FOR CSD 1 G 22225 N A HEADER COMB GAS VALVE SHUT OFF VALVE PILOT LINE PILOT LINE TYP COMB GAS VALVE TYP HEADER SHUT OFF VALVE B2 THRU B8 INDOOR OUTDOOR CSD 1 GAS TRAIN FOR MODELS B11 THRU B1...

Страница 7: ......

Страница 8: ...CONTROLS AND GAS TRAIN GAS FIRED COPPER FIN CONE COIL WATER HEATERS HEAVY DUTY INDUSTRIAL WATER HEATERS MINI PACK SEMI INSTANTANEOUS WATER HEATERS PACKAGED STORAGE WATER HEATERS CLEAN STEAM BOILERS AS...

Страница 9: ...and accept the product when received as conforming to their purchase order specifications and approved drawings All claims for non conformance errors shortages etc must be made within 10 days after re...

Страница 10: ...4 United States Tel 714 437 9050 Fax 714 437 9060 http www ajaxboiler com mail ajaxboiler com June 2010 Ace Heating Solutions LLC ACE Heating Solutions LLC 2701 S HARBOR BLVD SANTA ANA CA 92704 PHONE...

Страница 11: ...060 http www ajaxboiler com mail ajaxboiler com February 2007 ACE Heating Solutions LLC 2701 S HARBOR BLVD SANTA ANA CA 92704 PHONE 714 540 2230 FAX 714 540 2239 www aceheatingllc com Ace Heating Solu...

Страница 12: ...anta Ana California 92704 United States Tel 714 437 9050 Fax 714 437 9060 http www ajaxboiler com mail ajaxboiler com ACE Heating Solutions LLC 2701 S HARBOR BLVD SANTA ANA CA 92704 PHONE 714 540 2230...

Страница 13: ......

Страница 14: ......

Страница 15: ......

Страница 16: ...es at very high temperatures insulation shielding and air circulation may be necessary to protect the controls Proper insulation or shielding should be provided by the appliance manufac turer make sur...

Страница 17: ...o ground NOTE Earth ground is not required To connect the D80B follow the wiring diagrams sup plied with the vent damper or see Fig 8 for typical connec tions Connect Ignition Module 1 Connect remaini...

Страница 18: ...T DAMPER PLUG OPT 5 2ND OPERATOR 1ST OPERATOR PILOT COM MAIN VALVE DUAL VALVE COMBINATION GAS CONTROL Fig 2 S8610F H S8670D in a heating system with an atmospheric burner 5 TABLE 4 TERMINAL CROSS REFE...

Страница 19: ...9 0523 MV MV PV PV GND BURNER 24V GND 24V TH W VENT DAMPER PLUG SPARK 5 S8610A B POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED ALTERNATE LIMIT CONTROLLER LOCATION MAXIMUM C...

Страница 20: ...TOR PILOT COM MAIN VALVE DUAL VALVE COMBINATION GAS CONTROL PILOT BURNER GROUND PILOT GAS SUPPLY 9 69 0523 Fig 8 S8610F H S8670D in a heating system with an atmospheric burner and a D80B Vent Damper L...

Страница 21: ...23 Fig 10 S8610F H S8670D in a hydronic heating system with a D80D Vent Damper 2 MV MV PV PV GND BURNER 24V GND 24V TH W OPT VENT DAMPER PLUG OPT SPARK 4 S8610F H S8670D POWER SUPPLY PROVIDE DISCONNEC...

Страница 22: ...ne as described in Steps 1 and 5 below on initial installation and any time work is done involving the gas pip ing STEP 3 Reset the Module Turn the thermostat to its lowest setting Wait one minute As...

Страница 23: ...burner igniter sensor and provide shield if necessary If flame rod or bracket are bent out of position restore to correct position STEP 3 Check spark ignition circuit You will need a short jumper wire...

Страница 24: ...ing the pilot adjustment screw on the gas control clockwise to decrease or counterclockwise to increase pilot flame Following adjustment always replace pilot adjustment cover screw and tighten firmly...

Страница 25: ...V PV MV PV MAIN VALVE PILOT VALVE TO 24V GND TO 24V 3 3 Fig 17 Representative schematic for S8610F H See Fig 1 for hookup S8670 is similar except the timing circuit includes a purge timer See Fig 6 fo...

Страница 26: ...water pumps are in operating condition b Test low water cutoffs automatic feed water controls pressure and temperature limit control lers and relief valves in accordance with the manufacturer s recomm...

Страница 27: ...ntrol after compression nut has been tightened because this can result in gas leakage at connection 2 Square off and remove burrs from end of tubing 3 Push tubing into compression nut clearance hole u...

Страница 28: ...ot flame 6 Always replace pilot adjustment cover screw and tighten firmly after completing adjustment to assure pro per operation Service WARNING FIRE OR EXPLOSION HAZARD CAN CAUSE PROPERTY DAMAGE SEV...

Страница 29: ...e would result in personal injury and or loss of prop erty it is the responsibility of the installer to add devices safety limit controls that protect against or systems alarm supervisory systems that...

Страница 30: ...llation and adjustment CAUTION Check the installation for no flow switch operation Make appropriate adjustments to the sensitivity adjustment screw to be sure the switch restores fully at the desired...

Страница 31: ...ls The thermostat or the fuse will be damaged DO NOT allow any flame to impinge on the regulator vent tubing if sup plied It may clog and cause gas valve malfunction DO NOT use the gas cock to adjust...

Страница 32: ...or 6 for a typical connection diagram X XX UL INSTALLATION INSTRUCTIONS U S Registered Trademark Copyright 1995 Honeywell Inc All Rights Reserved L4008A B E L L6008A G H Aquastat Controllers APPLICATI...

Страница 33: ...R IGNITION TRANSFORMER RA89A RELAY RA817A PROTECTORELAY CONTROL BURNER MOTOR 24V THERMOSTAT 2 1 3 4 T T 1 2 3 4 M8785 Fig 5 Typical oil fired hydronic heating system with domestic hot water SETTING Co...

Страница 34: ...9 mm OD for both inlet and outlet Approval CE 0063AU1215 U S Registered Trademark Copyright 2000 Honeywell Inc All Rights Reserved INSTALLATION INSTRUCTIONS 69 1225 4 VR8104 VR8204 and VR8304 Intermit...

Страница 35: ...mine if the pressure regulator setting factory set will meet the appliance manifold requirements after conversion NOTE Convertible pressure regulator models suffix letter R do not have field adjustabl...

Страница 36: ...BINATION GAS CONTROLS 5 69 1225 4 Fig 1 Top view of convertible pressure regulator cap Install Adapters To Control If adapters are being installed on the control mount them as follows Flanges 1 Choose...

Страница 37: ...hanism to reduce the pilot flow if necessary If pilot adjustment is necessary proceed as follows 1 Remove pilot adjustment cover screw See Fig 6 2 The pilot adjustment is shipped at the full pilot gas...

Страница 38: ...eter reading Convert flow rate to Btuh as described in form 70 2602 Gas Controls Handbook and compare to Btuh input rating on appliance nameplate 3 IF CHECKING GAS INPUT WITH MANOMETER Make sure the g...

Страница 39: ...Non Regulating On Off U Models Non regulating VR8204U Valves are designed for application in various parts of Europe where a separate distinct pressure regulator is required The VR8204U is similar to...

Страница 40: ...f heater falls off this is usually a sign of lime in the coil The ACE coil will bang or knock if lim ing condition is severely restricting circulation Customers have reported operating ACE heaters and...

Отзывы: