Error codes 

 
When appliance status is abnormal, temperature indicator on the unit will blink and display corresponding 
error code. Please refer to list below for identification of error code. 
 

Display 
Code 

Malfunction Name 

Possibles Causes 

F1

Ambient 
Temperature 
Sensor Malfunction

 

Ambient temperature sensor is loosen or is poorly connected with 
the terminal of display board.

 

Some element of display board may have been put upside down and 
cause short circuit.

 

Ambient temperature sensor is damaged.

 

Display board is damaged.

 

F2

Tube Temperature 
Sensor Malfunction

 

Temperature  sensor  on  the  evaporator  is  loosen  or  is  poorly 
connected with the terminal of display board.

 

Some element of display board may have been put upside down and 
cause short circuit.

 

Temperature sensor on the evaporator is damaged.

 

Display board is damaged.

 

F5

Discharge 
Temperature 
Sensor Malfunction

 

Temperature  sensor  on  the  evaporator  is  loosen  or  is  poorly 
connected with the terminal of display board.

 

Some element of display board may have been put upside down and 
cause short circuit.

 

Discharge temperature sensor is damaged.

 

Display board is damaged.

 

L1

Humidity Sensor 
Malfunction

 

Humidity sensor is short-circuited.

 

Humidity sensor is damaged.

 

Display board is damaged.

 

F0

2

 

Freon-lacking 
protection

 

Refrigerant is leaking.

 

System is blocked.

 

H3

High-temperature 
overload protection

 

Ambient operation condition is bad.

 

The evaporator and condenser are blocked with filth.

 

The system is abnormal.

 

E4

2

 

High discharge 
temperature 
protection of 
compressor

 

Abnormal system (e.g.: blockage, etc.).

 

Abnormal rotation speed of the motor.

 

Abnormal air intake.

 

System is normal, but the compressor discharge temperature sensor 
is abnormal or poorly contacted.

 

 

Unit’s Condition: 

Compressor and fan motor stop. The buttons are invalid.

 

2

 

Unit’s Conditio

n: 

The compressor stops; the fan motor stops after 30 seconds. 

 

 

Содержание APD Series

Страница 1: ...page DEHUMIDIFIER APD Series Owner s Manual Please read this owner s manual carefully before operating the unit and keep it for future reference All rights reserved ACD 2019 For models APD20P APD30P A...

Страница 2: ...Error Codes Electric Schematic Diagram NOTICE Graphics in this manual are only for reference Please refer to actual products for specific details This appliance is not intended for use by people incl...

Страница 3: ...rsonal injury or property loss is caused by the following reasons 1 Damage the product due to improper use or misuse of the product 2 Alter change maintain or use the product with other equipment with...

Страница 4: ...above 32 C 90 F Thesuggested rangeof relativehumidity is between 30 and90 Allow at least 18 inches of air space on all sides of theunit Close all doors windows and other outside openings of the room t...

Страница 5: ...liance Please prevent children from playing and climbing on the dehumidifier Cleaning and user maintenance shall not be made by children Before cleaning please turn it off and unplug the dehumidifier...

Страница 6: ...service from your manufacturer or certified person o There s abnormal sound during operation o Circuit break trips off frequently o The appliance gives off burning smell o Indoor unit is leaking If th...

Страница 7: ...lfunction of the unit electric shock or fire hazard Properly connect the live wire neutral wire and grounding wire of the power outlet correctly Be sure to cut off the power supply before proceeding a...

Страница 8: ...of refrigerant circuit will be high please keep the interconnection cable away from the copper tube The appliance shall be installed in accordance with national wiring regulations The grounding resist...

Страница 9: ...fier under dripping objects Select a location which is out of reach for children and far away from animals Instructions for installation and use of this product are provided by the manufacturer It is...

Страница 10: ...Parts Name NOTICE Actual product may be different from below graphics please refer to actual product for reference purposes Front View Back View...

Страница 11: ...water bucket and pull it out following the arrow direction on the graphic below 2 Check whether float in the water bucket is properly placed It might have been moved a little after long time transpor...

Страница 12: ...r gives out a beep sound simultaneously Basic Functions of the Control Panel 1 POWER Press to turn the dehumidifier on and off 2 FILTER After 250 hours of operation the filter indicator light will glo...

Страница 13: ...mper air than desired set the humidity level to a lower setting or select Nonstop mode for maximum dehumidification 4 DISPLAY Shows the set humidity level while setting then shows the actual 5 accurac...

Страница 14: ...ty and replace the bucket AUTO SHUT OFF The water level control switch shuts off the dehumidifier when the bucket is full or when the bucket is removed or not replaced in the proper position AUTO DEFR...

Страница 15: ...ut through it instead of into the bucket 1 Hold the handles on both sides of the water bucket and pull it out following the arrow direction on the graphic Attention Pull out the bucket carefully in ca...

Страница 16: ...ction in option 1 3 Thread the drain hose onto the nozzle and make sure it s securely locked 4 Replace the bucket in the unit Make sure the drain hose goes through the bucket s drain hole and is place...

Страница 17: ...t To clean the air in grille use a vacuum cleaner or brush Cleaning the water bucket Every few weeks clean the bucket to prevent growth of mold mildew and bacteria Use a soft brush to clean the bucket...

Страница 18: ...ce APD30P APD45P 3 After cleaning replace the drain lid and handle and make sure the float of water bucket is placed properly The side with foam plastic should be beneath the drain lid Do not remove t...

Страница 19: ...lean Clean the filter in warm soapy water Rinse it and let the filter dry before replacing it If the dehumidifier is use in dusty places clean the air filter more often Do not operate the dehumidifier...

Страница 20: ...sage 1 Disconnect power supply 2 Clean filter and case 3 Clean dust and obstacle of the dehumidifier 4 Empty the water bucket Long time Storage If you won t use the dehumidifier for a long time we sug...

Страница 21: ...humidifying Room temperature is too low Humidity level may be improperly set If unit is operating in a room where temperature is from 5 C to 15 C 41 F to 59 F it will start to defrost automatically Co...

Страница 22: ...Unit can function normally but it can not start up Humidity is set too high If you want the air drier press button to lower the figure or press NS button for unit to dehumidify continuously Dehumidifi...

Страница 23: ...Discharge Temperature Sensor Malfunction Temperature sensor on the evaporator is loosen or is poorly connected with the terminal of display board Some element of display board may have been put upside...

Страница 24: ...Electric Schematic Diagram NOTICE The electric schematic diagram are subject o change without notice APD20P APD30P APD45P...

Отзывы: