AccuBeam 3 Digital Line Guide Sensor
62
Installation
The Digital Line Guide can be mounted in a variety of ways. Refer to the application drawings and
connection drawings on page 121 for installation information.
Note:
The Digital Line Guide must be mounted 1.00” [25.4mm] above the web surface, and
its sight-point scribe marks must be aligned with the roll center-line as shown in the
application drawing.
Sensor and Controller set-up
Note:
Refer to page 21 for more information about setting controller parameters.
1) Verify that the parameters in the controller are set correctly. The Digital Line Guide can
be configured to use Input A or Input B :
•
To use Input A (EDGE A), set controller parameter 12 to 2.
•
To use Input B (EDGE B), set controller parameter 13 to 2.
2) Press the SERVO-CENTER button on the controller and wait for the guide to move to its
center of travel.
3) Attach the Digital Line Guide test pattern (page 82) to the backup roller. Orient the
pattern with the direction of web travel as shown.
4) Using the UP and DOWN arrows on the switchpad, select the Calibrate parameter.
5) Rotate the backup roller and/or move the sensor laterally until the test pattern is
approximately centered under the sensor.
6) Press the ENTER key then wait until the “Select line/edge” message appears.
7) The test pattern should now appear in the Digital Line Guide’s graphic display. If the test
pattern line is not approximately centered in the display then move the sensor until the
line is centered, or press the DOWN arrow key until the selection window is centered on
the line.
8) Press the ENTER key then wait until the sensor has finished saving the new settings.
9) Press the EDGE A, EDGE B or LINE button on the controller, depending on which input
the sensor is configured for.
10) Press the AUTOMATIC button on the controller.
11) The guide should now steer the test pattern so that it is always in the center of the Digital
Line Guide’s field of view. If the guide moves the test pattern off to one side, then the
controller’s input polarity needs to be changed. Change the setting of controller
parameter 3, or 4.
12) Press the SERVO-CENTER button on the controller and wait for the guide to move to its
center of travel.
13) Remove the test pattern from the backup roller.
Содержание EVO 150
Страница 1: ...P O Box 7816 Madison Wisconsin 53707 7816 Instruction Manual EVO 150 Web Guide Control System...
Страница 2: ......
Страница 6: ...EVO 150 Controller 4 EVO 150TM Web Guide Control System...
Страница 56: ...PointSource and WideArray Edge Detectors 54 PointSource and WideArray Edge Detectors...
Страница 62: ...AccuBeam 3 Digital Line Guide Sensor 60 AccuBeam 3 Digital Line Guide Sensor...
Страница 85: ...AccuWeb Linear Actuators 83 AccuWeb Linear Actuators...
Страница 90: ...Remote Station Guide Point Adjust 88 Remote Station Guide Point Adjust...
Страница 99: ...Remote Station Auxiliary 97 Remote Station Auxiliary...
Страница 104: ...Fieldbus Interface 102 Fieldbus Interface...
Страница 124: ......
Страница 125: ......
Страница 126: ......
Страница 127: ......
Страница 128: ......
Страница 129: ......
Страница 130: ......
Страница 131: ......
Страница 132: ......
Страница 133: ......
Страница 134: ......
Страница 135: ......
Страница 136: ......
Страница 137: ...NOTES...