Accurex Grease Grabber H2O XGH2O Скачать руководство пользователя страница 21

21

Model XGH2O

Airflow Testing Procedure

NOTE

The constants 4.846 and 2.47 are factory derived for 
use with the Grease Grabber™ H

2

O.

Calculation Example:

Five (5) inlet slot velocity readings (minimum)

Average Velocity (FPM) = 
 

(175 + 210 + 250 + 190 + 160) 

 5 = 197 FPM

Hood Exhaust Rate (CFM) = 
 

[(96 x 4.846) x (197 x 2.47)] 

 144 = 1572 CFM

After the appropriate number of readings have been 
taken from the inlet slot of the hood, an average 
reading can be calculated by summing the velocity 
readings and dividing the total value by the number of 
readings taken.

Next calculate the total hood airflow volume (CFM) by 
using the following equation:
Hood CFM = [(Length of Hood in inches x 4.846) x 
(Average inlet slot velocity x 2.47)] 

 144

Average Velocity =

Sum of Velocity Readings

Number of Readings

Hood Length

48 to 72 

inches

72 to 120 

inches

120 to 192 

inches

Minimum Number 

of Test Locations

3

5

7

For measuring exhaust airflow rates (cubic feet per 
minute = CFM), use a short ridge meter to measure 
velocities along the inlet slot of the hood. To ensure 
accurate data, all appliances should be on. Multiple 
locations need to be tested as outlined below to 
ensure an accurate reading.

To take velocity readings along the length of the hood, 
the edge of the short ridge meter must start/stop six 
(6) inches from the end of the hood. Vertical placement 
of the short ridge meter along the inlet is shown.

Hood Length

96 inches

Test Location 
(off left; in inches)

6

27

48

69

90

Velocity Reading (fpm)

175 210 250 190 160

Short Ridge Meter Components

Содержание Grease Grabber H2O XGH2O

Страница 1: ...prevent accidental power up CAUTION When servicing the unit motor may be hot enough to cause pain or injury Allow motor to cool before servicing Installation Operation and Maintenance Manual Please re...

Страница 2: ...each item have been received If any items are missing report shortages to your local representative to arrange for obtaining missing parts Sometimes it is not possible that all items for the unit be s...

Страница 3: ...ically engaged to run at the same time each day through a programmable timer Grease Grabber H2O System Function Table of Contents Grease Grabber H2O System Function 3 Cleaning Cycle Manual and Automat...

Страница 4: ...r and detergent will fill the hood reservoir The soapy water will then be cycled through the hood by the attached recirculation pump cleaning both the filter banks and the exhaust plenum area on a tim...

Страница 5: ...ILL DETERGENT After pressing CLEAN HOOD Fans will automatically stop 472617 In case of emergency the wash cycle can be stopped by pressing CLEAN HOOD CLEAN HOOD FAN ON OFF SYSTEM FAULT FILL DETERGENT...

Страница 6: ...on process 1 2 3 Profile of Hood Profile of Hood Profile of Hood Profile of Hood Remove side back and top lumber Remove 3 inch lag screws Holding the front lifting skid in place and position the skid...

Страница 7: ...r must be contacted at this time After the fire system has been installed mount the enclosures then the supply plenums If an Horizontal Supply Plenum is provided it should be installed before the encl...

Страница 8: ...u clips and bolts Caulk this joint with NSF Approved silicone caulk GE SCS1000 or its equivalent The caulk is not provided NOTE Before hanging the hoods please verify the hood marks to make sure the...

Страница 9: ...ion instructions now Supply Supply ductwork where applicable should be connected to the hood in a manner approved by the local code authorities For proper installation of duct collars when they are sh...

Страница 10: ...in mm in mm ft m Back Supply 35 0 15 878 6 152 4 Variable Variable 3 to 16 91 to 4 88 145 cfm ft 246 36 m3 hr Air Curtain Supply 14 inch 9 5 4 31 14 355 6 10 254 3 to 16 91 to 4 88 110 cfm ft 186 89 m...

Страница 11: ...STED LOCATION ABOVE CUT 1 4 in X 24 in OPENING AT CENTERED ON WIDTH OF THE SUPPLY IF MODULE 6 ft STEP 1 4 in TO 6 in FASTEN WITH S PLACE THE DU L MODULE LENGTH L 2 L 2 L 2 L MODULE LENGTH L 4 L 4 STEP...

Страница 12: ...UPPLY IF IT WILL NOT INTERFERE 2 BEFORE THE HOOD IS HUNG THE BACKSUPPLY MUST BE SECURED INSTRUCTIONS AND THE FOLLOWING PROPERLY AS DESCRIBED IN STEP 3 in STEP 4 5 Connect the remaining ductwork for th...

Страница 13: ...provided Note Installation instructions may not be applicable for concrete ceilings Installing End Skirts 1 After the hood is hung in position slide the hemmed form on top of the end skirt onto the e...

Страница 14: ...PIECES PANELS UP TO 48 IN 1219 2 MM WIDE SHIP IN ONE PIECE OVER 48 IN 1219 2 MM IN MULTIPLE PIECES Length 1 inch 25 4 mm Heigth Length Height 1 After the hood is hung in position slide the flat flang...

Страница 15: ...nnection Exhaust duct connection is to be a continuous liquid tight weld to hood Supply Duct Connection Supply duct connection to be tack welded with 1 to 2 inch tacks or sheet metal screws at 3 to 6...

Страница 16: ...detergent is non caustic and biodegradable waste water from the hood can be drained in any typical grease trap A One inch unions B Detergent tank C Mounting plate D Isolators qty of four E Detergent...

Страница 17: ...facturer for use in the wash system Use Formula G 510 full strength This product is biodegradable non caustic and safe for kitchen staff to use If G 510 detergent is not used the cleanliness of the ex...

Страница 18: ...ive order of time for example 8 00 pm ON 9 00 pm ON 10 00 pm ON Not 8 00 pm ON 10 00 pm ON 9 00 pm ON b Do not overlap event times for example 8 00 pm ON 12 00 pm OFF and 9 00 pm ON 11 00 pm OFF c Set...

Страница 19: ...se valve until water mist is no longer felt above equipment Once the valve is set it will not need to be moved again Verify the Grease Grabber H2O sequence of operation see the diagram of wash sequenc...

Страница 20: ...pump OFF Spray for 5 minutes Spray for 5 minutes 20 minute dry time Wash rinse dry complete No Temperature Interlock Exhaust Mode in Fire STOP Exhaust Mode in Fire RUN No Yes Shut OFF exhaust fan s T...

Страница 21: ...x 4 846 x Average inlet slot velocity x 2 47 144 Average Velocity Sum of Velocity Readings Number of Readings Hood Length 48 to 72 inches 72 to 120 inches 120 to 192 inches Minimum Number of Test Loca...

Страница 22: ...MICROSWITCH IN NORMAL INSTALLATION THE YELLOW WIRE IS TO BE USED ONLY FOR EXTINGUISHER ALARM LIGHTS CIRCUITS ETC L1 L2 PUSHBUTTON SWITCH 120V 60HZ K1 Ka K1b CURRENT DRAW MAX 8A RESISTIVE 8A INDUCTIVE...

Страница 23: ...WITH ANSUL ANSUL SNAP ACTION SWITCH BLACK RED NEUTRAL HOT 1 L2 L NOTE ANSUL file name Typicalwiringschematicelectricequipmentshutdowndetail ai File received on August 4 2010 TEMPERATURE RATING 110V 6...

Страница 24: ...K RD 12 GA 12 GA 12 GA 18 GA 18 GA 18 GA 18 GA BK BK BK BK N WHT BL BL PR PR PR PR PR BR PR PR PR 18 GA YW YW YW 12 GA 18 GA PR PR R6 120 VAC Wash Timer Relay A1 A2 T1 T2 Timer Contact BK RD BK N WHT...

Страница 25: ...ing the filters Ensure no gaps are between filters after installation If any filter appears damaged consult factory for replacement Floats The floats need to be inspected two weeks after start up and...

Страница 26: ...ks water leaking through the access panels when filling Ensure access panels are securely in place If leak persists partially close inlet water ball valve by others upstream of fill solenoid to reduce...

Страница 27: ...guide on page 26 Grease Grabber H2O Start Up Checklist Check boxes when item has been verified and gone over with customer Hook Up o Electrical Connected 120V 1 30A to terminals L1 and N for wash cont...

Страница 28: ..._______________________________ Date___________________ Time______________ AM PM Notes ___________________________________________ _________________________________________________ ___________________...

Отзывы: