Accurex Grease Grabber H2O XGH2O Скачать руководство пользователя страница 17

17

Model XGH2O

Electrical

Electrical Wiring

All wiring must be done according to NEC (National 
Electrical Code NFPA #70) and local building codes. 
Two sources of power need to be brought into 
the electrical control cabinet. A 120 volt, 30 amp 
service with 12 gauge wire needs to be connected 
to terminals L1 on the disconnect switch and N. A 
120 volt, 15 amp service with 14 gauge wire needs to 
be brought into the electrical cabinet and connected 
to terminal L2 on the disconnect switch and N1.

The main recirculating pump needs to be wired after it 
is installed in the hood. There are three 12 gauge wires 
in flexible conduit wired to the pump. Wiring to the 
pump is complete from the factory. The whip from the 
pump needs to be wired into the control cabinet. 

NOTE

The wash control station will provide a dry contact 
for a fan starter so the fans can be controlled by the 
PLC. The fan starter is not provided with the wash 
control station. 

Detergent Requirements

The detergent brand Formula G-510 (by 2010 
Products, Inc.) is recommended by manufacturer 
for use in the wash system. Use Formula G-510 full 
strength. This product is biodegradable, non-caustic, 
and safe for kitchen staff to use.  If G-510 detergent is 
not used, the cleanliness of the exhaust plenum and 
filters cannot be guaranteed.

Preventative Maintenance

The following practices will prolong the life of the 
detergent pump:
  •  Keep detergent tank filled.
  •   Avoid spilling detergent on the exterior of the 

pump.

  •  Clean the detergent tank at least every six 

months.

  •  Clean the detergent line strainer at least every six 

months.

  • Check tightness of all fittings periodically.
The detergent pump motor has sealed bearings which 
do not require lubrication.

NOTE

G-510 is manufactured by 2010 Products, Inc., Food 
Service Division, Salem, Oregon 97303. For details 
and ordering information, call 800-286-2010.

Detergent Tank Installation

The detergent tank is located as shown in the photo. 
When installing the detergent tank, the low detergent 
indicator float and the detergent pump inlet tubing will 
need to be lifted. Once the tank is in position, the low 
detergent indicator float and detergent inlet tube must 
be lowered into place inside the tank.
 

A.  One-inch unions

 

B.  Detergent tank

 

C.  Mounting plate

 

D.  Isolators (qty of four)

 

E.  Detergent pump

Содержание Grease Grabber H2O XGH2O

Страница 1: ...prevent accidental power up CAUTION When servicing the unit motor may be hot enough to cause pain or injury Allow motor to cool before servicing Installation Operation and Maintenance Manual Please re...

Страница 2: ...each item have been received If any items are missing report shortages to your local representative to arrange for obtaining missing parts Sometimes it is not possible that all items for the unit be s...

Страница 3: ...ically engaged to run at the same time each day through a programmable timer Grease Grabber H2O System Function Table of Contents Grease Grabber H2O System Function 3 Cleaning Cycle Manual and Automat...

Страница 4: ...r and detergent will fill the hood reservoir The soapy water will then be cycled through the hood by the attached recirculation pump cleaning both the filter banks and the exhaust plenum area on a tim...

Страница 5: ...ILL DETERGENT After pressing CLEAN HOOD Fans will automatically stop 472617 In case of emergency the wash cycle can be stopped by pressing CLEAN HOOD CLEAN HOOD FAN ON OFF SYSTEM FAULT FILL DETERGENT...

Страница 6: ...on process 1 2 3 Profile of Hood Profile of Hood Profile of Hood Profile of Hood Remove side back and top lumber Remove 3 inch lag screws Holding the front lifting skid in place and position the skid...

Страница 7: ...r must be contacted at this time After the fire system has been installed mount the enclosures then the supply plenums If an Horizontal Supply Plenum is provided it should be installed before the encl...

Страница 8: ...u clips and bolts Caulk this joint with NSF Approved silicone caulk GE SCS1000 or its equivalent The caulk is not provided NOTE Before hanging the hoods please verify the hood marks to make sure the...

Страница 9: ...ion instructions now Supply Supply ductwork where applicable should be connected to the hood in a manner approved by the local code authorities For proper installation of duct collars when they are sh...

Страница 10: ...in mm in mm ft m Back Supply 35 0 15 878 6 152 4 Variable Variable 3 to 16 91 to 4 88 145 cfm ft 246 36 m3 hr Air Curtain Supply 14 inch 9 5 4 31 14 355 6 10 254 3 to 16 91 to 4 88 110 cfm ft 186 89 m...

Страница 11: ...STED LOCATION ABOVE CUT 1 4 in X 24 in OPENING AT CENTERED ON WIDTH OF THE SUPPLY IF MODULE 6 ft STEP 1 4 in TO 6 in FASTEN WITH S PLACE THE DU L MODULE LENGTH L 2 L 2 L 2 L MODULE LENGTH L 4 L 4 STEP...

Страница 12: ...UPPLY IF IT WILL NOT INTERFERE 2 BEFORE THE HOOD IS HUNG THE BACKSUPPLY MUST BE SECURED INSTRUCTIONS AND THE FOLLOWING PROPERLY AS DESCRIBED IN STEP 3 in STEP 4 5 Connect the remaining ductwork for th...

Страница 13: ...provided Note Installation instructions may not be applicable for concrete ceilings Installing End Skirts 1 After the hood is hung in position slide the hemmed form on top of the end skirt onto the e...

Страница 14: ...PIECES PANELS UP TO 48 IN 1219 2 MM WIDE SHIP IN ONE PIECE OVER 48 IN 1219 2 MM IN MULTIPLE PIECES Length 1 inch 25 4 mm Heigth Length Height 1 After the hood is hung in position slide the flat flang...

Страница 15: ...nnection Exhaust duct connection is to be a continuous liquid tight weld to hood Supply Duct Connection Supply duct connection to be tack welded with 1 to 2 inch tacks or sheet metal screws at 3 to 6...

Страница 16: ...detergent is non caustic and biodegradable waste water from the hood can be drained in any typical grease trap A One inch unions B Detergent tank C Mounting plate D Isolators qty of four E Detergent...

Страница 17: ...facturer for use in the wash system Use Formula G 510 full strength This product is biodegradable non caustic and safe for kitchen staff to use If G 510 detergent is not used the cleanliness of the ex...

Страница 18: ...ive order of time for example 8 00 pm ON 9 00 pm ON 10 00 pm ON Not 8 00 pm ON 10 00 pm ON 9 00 pm ON b Do not overlap event times for example 8 00 pm ON 12 00 pm OFF and 9 00 pm ON 11 00 pm OFF c Set...

Страница 19: ...se valve until water mist is no longer felt above equipment Once the valve is set it will not need to be moved again Verify the Grease Grabber H2O sequence of operation see the diagram of wash sequenc...

Страница 20: ...pump OFF Spray for 5 minutes Spray for 5 minutes 20 minute dry time Wash rinse dry complete No Temperature Interlock Exhaust Mode in Fire STOP Exhaust Mode in Fire RUN No Yes Shut OFF exhaust fan s T...

Страница 21: ...x 4 846 x Average inlet slot velocity x 2 47 144 Average Velocity Sum of Velocity Readings Number of Readings Hood Length 48 to 72 inches 72 to 120 inches 120 to 192 inches Minimum Number of Test Loca...

Страница 22: ...MICROSWITCH IN NORMAL INSTALLATION THE YELLOW WIRE IS TO BE USED ONLY FOR EXTINGUISHER ALARM LIGHTS CIRCUITS ETC L1 L2 PUSHBUTTON SWITCH 120V 60HZ K1 Ka K1b CURRENT DRAW MAX 8A RESISTIVE 8A INDUCTIVE...

Страница 23: ...WITH ANSUL ANSUL SNAP ACTION SWITCH BLACK RED NEUTRAL HOT 1 L2 L NOTE ANSUL file name Typicalwiringschematicelectricequipmentshutdowndetail ai File received on August 4 2010 TEMPERATURE RATING 110V 6...

Страница 24: ...K RD 12 GA 12 GA 12 GA 18 GA 18 GA 18 GA 18 GA BK BK BK BK N WHT BL BL PR PR PR PR PR BR PR PR PR 18 GA YW YW YW 12 GA 18 GA PR PR R6 120 VAC Wash Timer Relay A1 A2 T1 T2 Timer Contact BK RD BK N WHT...

Страница 25: ...ing the filters Ensure no gaps are between filters after installation If any filter appears damaged consult factory for replacement Floats The floats need to be inspected two weeks after start up and...

Страница 26: ...ks water leaking through the access panels when filling Ensure access panels are securely in place If leak persists partially close inlet water ball valve by others upstream of fill solenoid to reduce...

Страница 27: ...guide on page 26 Grease Grabber H2O Start Up Checklist Check boxes when item has been verified and gone over with customer Hook Up o Electrical Connected 120V 1 30A to terminals L1 and N for wash cont...

Страница 28: ..._______________________________ Date___________________ Time______________ AM PM Notes ___________________________________________ _________________________________________________ ___________________...

Отзывы: