35
9 - REGOLAZIONE ELETTRONICA
9 - ELECTRONIC CONTROL
231
Tempo integrale PID 1 / Ti Pid 1
R/W
Integral Time Pid 1
232
Tempo integrale PID 2 / Ti Pid 2
R/W
Integral Time Pid 2
233
Tempo integrale PID 3 / Ti Pid 3
R/W
Integral Time Pid 3
234
Tempo integrale PID 4 / Ti Pid 4
R/W
Integral Time Pid 4
235
Modo lavoro serrande modulanti I/O / Modulating I/O
Damper Action
0
R/W
0=fixed position, 1=CO2 PID, 2= CO2
treshold
236
Apertura fissa serrande I/O / Fixed open I/O
% 70
R/W
fixed open of I/O damper if action is 0
237
Apertura fissa serranda ricircolo / Fixed open
Recirculating Damper
% 30
R/W
fixed open of Irec. damper if action is 0
238
Minima apertura serrande I/O / Min Open I/O Dampe % 30
R/W
min open I/O Dampers if action is 2
239
Media apertura serrande I/O / Med Open I/O
Dampers
% 60
R/W
med open I/O Dampers if action is 2
240
Massima apertura serrande I/O / Max Open I/O
Dampers
% 100
R/W
max open I/O Dampers if action is 2
Variabili digitali / Digital variables
Indirizzo
Nome / Name
Default Accesso /
Access
Descrizione / Description
1
Stato uscita digitale 1 / DO1 status
R
Actual value of digital output 1
2
Stato uscita digitale 2 / DO2 status
R
Actual value of digital output 2
3
Stato uscita digitale 3 / DO3 status
R
Actual value of digital output 3
4
Stato uscita digitale 4 / DO4 status
R
Actual value of digital output 4
5
Stato uscita digitale 5 / DO5 status
R
Actual value of digital output 5
6
Stato uscita digitale 6 / DO6 status
R
Actual value of digital output 6
7
Stato unità / Unit status
R
0= off, 1=on
8
Allarme / Alarm
R
Alarm summary
9
On/Off da supervisore /Supervisor on/off
R/W
Unit on from supervisor
10
On/off remoto / Remote On/
R
Status of Remote on/off digital input
12
Pressostato filtri / Filter Pressure switch
R
Status of filter pressure switch digital input
13
Micro porte / Door sensor
R
Status of doors sensor digital input
14
Termico / Thermal protection
R
Status of thermal protection digital input
15
Ingresso Allarme / Alarm input
R
Status of Alarm digital input
16
Riservato / Reserved
R
17
Riservato / Reserved
R
18
Riservato / Reserved
R
19
Riservato / Reserved
R
20
Allarme sonda su AI1 / Probe alarm AI1
R
Probe broken or disconnected AI1
21
Allarme sonda su AI2 / Probe alarm AI2
R
Probe broken or disconnected AI2
22
Allarme sonda su AI3 / Probe alarm AI3
R
Probe broken or disconnected AI3
23
Allarme sonda su AI4 / Probe alarm AI4
R
Probe broken or disconnected AI4
24
Allarme sonda su AI5 / Probe alarm AI5
R
Probe broken or disconnected AI5
25
Allarme sonda su AI6 / Probe alarm AI6
R
Probe broken or disconnected AI6
26
Allarme sonda su AI7 / Probe alarm AI7
R
Probe broken or disconnected AI7
27
Allarme sbrinamento / Defrost Alarm
R
Defrost Alarm
28
Riservato / Reserved
R
29
Attivazione antigelo / Antifreeze activation
R/W
Activated antifreeze action when post
treatment is water coil
30
Antigelo su sonda immissione / Antifreeze probe is
supply probe
R/W
False= probe on B7, True= Inlet Probe
31
Comportamento ventilatori durante antigelo / Fan
action during antifreeze
R/W
False= fan off, True=Fan On
40
Stato DO7 / DO7 Status
R
Actual value of digital output 7
41
Stato DO8 / DO8 Status
R
Actual value of digital output 8
42
Stato DO9 / DO9 Status
R
Actual value of digital output 9
43
Stato DO10 / DO10 Status
R
Actual value of digital output 10
44
Stato DO11 / DO11 Status
R
Actual value of digital output 11
45
Stato DO12 / DO12 Status
R
Actual value of digital output 12
46
Stato DI1 / DI1 Status
R
Actual Value of digital input 1
46
Stato DI2 / DI2 Status
R
Actual Value of digital input 2
48
Stato DI3 / DI3 Status
R
Actual Value of digital input 3
49
Stato DI4 / DI4 Status
R
Actual Value of digital input 4
50
Stato DI5 / DI5 Status
R
Actual Value of digital input 5
51
Stato DI6 / DI6 Status
R
Actual Value of digital input 6
52
Stato DI7 / DI7 Status
R
Actual Value of digital input 7
53
Stato DI8 / DI8 Status
R
Actual Value of digital input 8