ENGLISH
2
Commissioning
Code
Possible Settings
IMPORTANT
No.
Name
Default Selection
Minimum Alarm
0.0
P204
P205
Use with P40, P42 = 8...2
Maximum Alarm
0.0
P204
P205
Preset PID
Setpoint #
0.0
P204
P205
TB-A activated; P2 = and
P200 = or 2
Preset PID
Setpoint #2
0.0
P204
P205
TB-B activated; P22 = and
P200 = or 2
Preset PID
Setpoint #
0.0
P204
P205
TB-C activated; P2 = and
P200 = or 2
Sleep Threshold
0.0
0.0
{Hz}
500.0
• If drive speed < P240 for longer than
P24, output frequency = 0.0 Hz;
drive display =
• P240 = 0.0: Sleep mode is disabled.
• P200 = 0…2: Drive will start again
when speed command is above
P240
• P242 > 0.0: Drive will restart when
the PID feedback differs from the
setpoint by more than the value
of P242
or
when the PID loop
requires a speed above P240.
Sleep Delay
0.0
0.0
{s}
00.0
Sleep Bandwidth
0.0
0.0
B
max
Where: B
max
= |(P205 - P204)|