ENGLISH
5
Commissioning
4.5
Parameter menu
4.5.1
Basic Setup Parameters
Code
Possible Settings
IMPORTANT
No.
Name
Default Selection
Start Control
Source
0
0 Local Keypad
Use RUN button on front of drive to start
Terminal Strip
Use start/stop circuit wired into the
terminal strip. See Section .2.
2 Remote Keypad Only
Use RUN button on optional Remote
Keypad to start
Network Only
• Start command must come from
network (Modbus, CANopen, etc)
• Requires optional communication
module (refer to the network module
documentation).
• Must also set one of the TB-
inputs to 9 (Network Enable); see
P2...P2
4 Terminal Strip or Local
Keypad
Allows start control to be switched
between terminal strip and local
keypad using one of the TB- inputs.
See note below.
5 Terminal Strip or Remote
Keypad
Allows start control to be switched
between terminal strip and optional
remote keypad using one of the TB-
inputs. See note below.
WARNING!
P00 = 0 disables TB- as a STOP input! STOP circuitry may be disabled
if parameters are reset back to defaults (see P99)
Note
• P00 = 4, 5: To switch between control sources, one of the TB-
inputs (P2...P2) must be set to 08 (Control Select);
TB-x OPEN (or not configured): Terminal strip control
TB-x CLOSED: Local (P00 = 4) or Remote (P00 = 5) keypad
• P00 = 0, , 4: Network can take control if P2...P2 = 9 and the
corresponding TB-x input is CLOSED.
• The STOP button on the front of the drive is always active except in
JOG mode.
•
An
fault will occur if the Assertion Level switch (ALsw)
position does not match the P20 setting and P00 is set to a
value other than 0.
Standard
Reference
Source
0
0 Keypad (Local or Remote)
Selects the default speed or torque
reference when no Auto Reference is
selected using the TB- inputs
0-0 VDC
2 4-20 mA
Preset #
4 Preset #2
5 Preset #
Network