Troubleshooting and Diagnostics
Fault
Cause
Remedy
(1)
Motor Overload fault
Excessive motor load for too long
• Verify proper setting of P08
• Verify drive and motor are proper
size for application
Flying Restart fault
Controller was unable to
synchronize with the motor during
restart attempt; (P0 = 5 or )
Check motor / load
Single-Phase fault
A mains phase has been lost
Check mains voltage
Start fault
Start command was present when
power was applied (P0 = 0 or 2).
• Must wait at least 2 seconds
after power-up to apply Start
command
• Consider alternate starting
method (see P0).
() The drive can only be restarted if the error message has been reset