Ultima OPIR-5 Detector
35
7.2.4 Environmental
Specification
7.2.5 Approvals
Meets the performance requirements of FM 6325, EN 60079-29-4 and IEC 60079-29-4,
CSA, FM, ATEX, IECEx, INMETRO approved; HART Registered; IEC 61508 approved to
SIL 3, 2 or 1.
CSA & FM Approval:
Explosion-proof for Class I, Division 1, Groups B, C, and D, Dust-ignition proof for Class
II/III, Division 1 Groups E, F and G, Non-Incendive for Class I/II/III, Division 2, Groups B, C,
D, E, F, G.
ATEX & IECEx Approval:
Flameproof ‘d’ with Equipment Protection Level ‘Gb’ for Gas Group IIB + H
2
, Category 2G.
Dust Ignition Protection by Enclosure with level of protection ‘tb’ and Equipment Protection
Level ‘Db’ for Equipment Group IIIC, Category 2D.
7.2.6 Cable
Requirements
It is the responsibility of the facilities engineer to comply with all regulatory, legal, and safety
issues concerning appropriate wiring for the facility.
The sample calculations are for reference only. Customers must derive the distance from
supply to device based on cable specifications, expected maximum ambient temperature
and cable temperature rise, estimated connection losses, allowances for error in distance
measurement, and other variables particular to the customer installation.
Sample Calculations for Power Cable
V_supply = 24 VDC, V_device= 20 VDC, I_Receiver_max = 0.50 A, cable resistance per
meter = 9.00 ohms per meter at maximum ambient temperature for 2.5 mm
2
cable.
Maximum distance from supply to Receiver = (1/2) x (V_supply – V_device) / (I_device_max
x cable resistance per meter)
Maximum distance = (1/2) x (24 – 20) / (0.50 x 9.00 / 1000) = 444 meters
Sample maximum distances from supply to device
Terminal Type
Push
Screw
Push
Screw
Max Wire Size
16 AWG
14 AWG
1.5 mm2
2.5 mm2
Typical
Resistance
5.00 ohms /
1000 ft
3.00 ohms /
1000 ft
16.0 ohms /
1000 m
9.00 ohms /
1000 m
Source
625 feet
1040 feet
195 meters
347 meters
Receiver
800 feet
1330 feet
250 meters
444 meters
Table 5
:
Distances from Power Supply to Source and Receiver
Operating Range:
-55°C to +65°C @ 10% to 95% RH non-condensing,
86-108 kPa non-compensated
Storage Range:
-65°C to +75°C @ 10% to 95% RH non-condensing,
86-108 kPa non-compensated
Enclosure Protection Rating:
Type 4X, IP66/67
Содержание Ultima OPIR-5
Страница 3: ...Ultima OPIR 5 Detector i This page intentionally left blank...
Страница 27: ...Ultima OPIR 5 Detector 12 Figure 7 Source Wiring Figure 8 Receiver Wiring...
Страница 52: ...Ultima OPIR 5 Detector 37 7 4 Engineering Documentation Figure 13 Outline Drawing...
Страница 55: ...MINE SAFETY APPLIANCES COMPANY CRANBERRY TOWNSHIP PENNSYLVANIA USA 16066 1 800 MSA INST www MSAsafety com...