Ultima OPIR-5 Detector
21
4.2 Menu Options
The Ultima OPIR-5 Detector allows the user to reset, test, and align the system as well as
configure Receiver outputs. To access the menu, place the magnet supplied with the Ultima
OPIR-5 Detector over the MSA logo on the label of the Receiver for approximately five
seconds. The display will cycle between the options. Remove the magnet to select an option.
These options are:
“
rSt
” – Reset – Resets relays
“
---
” - Test
“
SE
” - Setup
“
AJ
” - Alignment/Adjustment
“
Fi
” - Finish, return to normal operation
4.3 Test “---”
Apply the magnet when the flashing bars are showing and the unit enters Test Mode. While
the unit is in this mode the optical faults and relays will be inhibited, the analog output will
drop from 4 mA to 1.5 mA and the display will flash.
This mode allows the user to check the Ultima OPIR-5 Detector response to a Test Gas Film
without activating the relays and analog outputs. After verifying the response, remove the
Test Gas Film. The unit will return to normal operation. If the Test Gas Film is not removed
after 5 minutes, the unit will revert to a fault condition. If left in this mode for 5 minutes without
a Test Gas Film, the unit will return to normal operation automatically.
To abort Test Mode before the gas has been applied, reapply the magnet and the unit will
return to normal operation.
4.4 Setup “SE”
Apply the magnet when “
SE
” is showing and the unit enters Setup.
This mode allows the user to change various unit attributes. Following is the order in which
the options are displayed (to change, apply magnet when the desired option is showing):
Fi
- Exits the current option and goes on to next.
bb
- Beam Block and High IR settings
AOd – 0, 1, 2…10, 15, 20, 25… 60
- Seconds before analog output changes to Beam
Block level.
oFd – 0, 1, 2…10, 15, 20, 25…60
- Minutes before optical fault F3 appears and
analog output changes to Fault level.
FLP
– Flip display – on or off (To read display with a mirror)
Ao1
- Analog #1 (0-5,000 / 0-2,000 ppm•meter)
SPL – Split-Range - on or off
(HART Only) 1.2 or 3.5 - mA signal fault level
Ao2
- Analog #2 (0-5 / 0-1 LEL•meter) (Not available if Split-Range is on)
Содержание Ultima OPIR-5
Страница 3: ...Ultima OPIR 5 Detector i This page intentionally left blank...
Страница 27: ...Ultima OPIR 5 Detector 12 Figure 7 Source Wiring Figure 8 Receiver Wiring...
Страница 52: ...Ultima OPIR 5 Detector 37 7 4 Engineering Documentation Figure 13 Outline Drawing...
Страница 55: ...MINE SAFETY APPLIANCES COMPANY CRANBERRY TOWNSHIP PENNSYLVANIA USA 16066 1 800 MSA INST www MSAsafety com...