Ultima OPIR-5 Detector
22
rLy – Relay
Password required to turn relays off: u19, ^61
AL1
- Alarm Relay #1 (0-5,000 / 0-2,000 ppm•meter)
En
or
dE
- Energized or De-energized.
LA
or
nL
- Latching or Non-Latching.
2000
to
4500
- Alarm level, increments by 500 or
800
to
1800
- Alarm level, increments by 200.
(Value increments each time magnet is applied)
AL2
- Warn Relay #2 (0-5 / 0-1 LEL•meter)
En
or
dE
- Energized or De-energized.
LA
or
nL
- Latching or Non-Latching.
0.5 (0.1)
to
AL3
- Alarm level, increments by 0.5 (0.1).
(Value increments each time magnet is applied)
AL3
- Alarm Relay #3 (0-5 / 0-1 LEL•meter)
En
or
dE
- Energized or De-energized.
LA
or
nL
- Latching or Non-Latching. If this relay is set to “nL” (non-Latching), the
Ultima OPIR-5 Detector must be connected to an auxiliary system which is able to
provide the same function as a latching relay i.e. the alarm can only be reset
manually.
AL2
to
4.5 (1.8)
- Alarm level, increments by 0.5 (0.1).
(Value increments each time magnet is applied)
CH1 – Channel 1 (Modbus)
br – baud rate – 2.4, 4.8, 9.6, 19.2, or 38.4 kbps
For – Format – 8n1, 8E1, 8o1, or 8n2 – bits, parity (none, Even, odd), stop bits
Add – Address
CH2 – Channel 2 HART or Modbus, depending on product configuration)
HART
on or off
Modbus
br – baud rate – 2.4, 4.8, 9.6, 19.2, or 38.4 kbps
For – Format – 8n1, 8E1, 8o1, or 8n2 – bits, parity (none, Even, odd), stop bits
Add – Address
Содержание Ultima OPIR-5
Страница 3: ...Ultima OPIR 5 Detector i This page intentionally left blank...
Страница 27: ...Ultima OPIR 5 Detector 12 Figure 7 Source Wiring Figure 8 Receiver Wiring...
Страница 52: ...Ultima OPIR 5 Detector 37 7 4 Engineering Documentation Figure 13 Outline Drawing...
Страница 55: ...MINE SAFETY APPLIANCES COMPANY CRANBERRY TOWNSHIP PENNSYLVANIA USA 16066 1 800 MSA INST www MSAsafety com...