Ultima OPIR-5 Detector
xi
Startup
Before applying power to the system for the first time, all wiring connections should be
checked and the housing cover securely fastened.
Display Sequence on Power Up
Display
Duration (s)
0 0 0
1
8.8.8. (Test all segments)
2
blank 3
Software revision letter
2
SU (Start Up)
120
0 (Gas Concentration)
Continuous
The Ultima OPIR-5 Detector contains a heater circuit to remove condensation from the
windows. The unit should be allowed to stabilize for approximately two hours before
continuing with the setup mode.
The resolution of the display is the either 0.1 LEL
●
m or 100 ppm
●
m. Since HART, Modbus,
and 4-20 mA outputs have more resolution, the least significant digit of the displayed value
might not agree with that of other outputs due to rounding error.