8
| Manual ZX0 HB 600 en - Revision 05
You have chosen a gas-insulated switchgear of series ZX0 in block
design. This switchgear from the ZX range is notable for the fol-
lowing features:
− SF
6
gas-insulated with hermetically sealed pressure
systems
− Rated voltages up to 24 kV
− Up to 1250 A and 25 kA
− Single busbar design
− Up to six panels grouped together in a block (one common
gas compartment)
− Stainless steel enclosures, fabricated from laser cut sheet
steel
− Modular structure
− Switchgear with a leakage rate of less than 0.1 % per year
− Integrated routine leakage testing of the panel blocks ex-
works
− Indoor installation and free-standing installation
− Wall installation
− Panel widths 400 mm and 600 mm
Please observe further documents in addition to this manual. The
documents relevant to your switchgear are part of the final docu-
mentation.
&
Installation checklist
MC 600 E
&
Order documents
− Single line diagram
− Front view
− Construction data if compiled specifically
for this order
− Circuit diagrams
− Earthing diagram – switchgear earth
to station earth (not part of ABB supply)
&
Instruction manuals
− Use of SF
6
insulating gas
HB 605 E
− Circuit-breaker VD4 X0
BA 440 E
− Snap-action mechanism for
switch-disconnector
BA 445 E
− Stored-energy spring mechanism for
switch-disconnector with fuse
BA 446 E
− Material supplement
BA 509 E
&
Operating instructions and directions for components,
e.g.
− Surge arresters
− Current and voltage transformers
− Current and voltage sensors
− Protection and control devices
− Capacitive indicators.
Do not use cleaning agent containing chlorine for cleaning the switchgear.
If you have technical questions, please contact our service staff
Power technology customer service
Call 49 180 6222-007