Primary Switch Mode Inverter
UNV-F
Operation Manual
Page 26 (28)
BHB.UNV-F.D65-1050.HB101
Monitoring
DC-input
voltage
(U
IN
<,U
IN
>) with auto-
matic switch ON/OFF
function,
AC-output voltage(U
OUT
);
overtemperature (T>) and
overload with automatic
switch off function; fan
monitor
Overload
capability
130%
for
30
sec.
LED-Signals
OPERATION,
U
OUT
, U
IN
<,
U
IN
>, I
O
>, T> and ALARM
Relay
contacts
collective
failure
(contact current
110V DC / 0,5A;
60V DC / 1A)
Parallel
operation
max.
7
devices,
load sharing appr. 5%
I
nom
by degressive
output characteristic
Audible noise
40dB(A) at 1m distance
Dimensions
acc.
to
type
list
Mechanical
construction
acc.
VDE
0160
edition
5.88 chapter 7.2.2
Protection
class
IP20
Cooling
(1.2kVA
5.0kVA);
speed controled fan with
monitoring
Ambient
temperature
operation:
0...+40°C;
storage: -30...+65°C
Max.
installation
altitude
1000m
a.s.l.
Humidity
class
F
Surfaces
powder
coating
RAL
7032
(front panel only);
constructive parts:
anodized metal
Connectors (48-1.2F - 108-5.0F) input / output and sig-
nals:
HAN K 4/8 (rearside)
Connectors
(48-5.0F)
input
/
output
and
sig-
nals:
HAN K 6/6 (rearside)
Additional parts included in