Overhaul Instructions
Dismantling the circuit-breaker
1HSB435409-201 enrev1
11
4.3 Cleaning and waste disposal
CAUTION
Some decomposition products formed in the breaking unit can, when
coming in contact with moisture, become corrosive and can irritate the
skin, eyes and mucous membrane.
Protective gloves of plastic or rubber, long-sleeved overalls and a full face mask
with a fine particle and acidic gas filter must be worn when cleaning the inside of
the circuit-breaker.
The dust (decomposition products) that forms in the circuit-breaker can be removed
using a vacuum cleaner fitted with a micro-filter and wiped off using a soft cloth
dampened with alcohol.
N. B.
All dust, old absorption agent, used cloths, etc., should be collected in
a sealed vessel and treated as chemical waste according to applicable
local directives.
Protective gloves must be worn during all waste handling.
N. B.
Protective gloves should be rinsed thoroughly in water after waste
handling.
Содержание SF6 LTB 245E1 BLG 1002A
Страница 1: ...Product Manual 1HSB435416 2 en Rev 1 LTB 245E1 BLG 1002A 3 pole operation ...
Страница 63: ...ABB Switchgear SF6 Circuit Breaker Circuit breakers HPL and LTB 1HSB445410 100 en rev1 Check list assembly ...
Страница 68: ...ABB Switchgear SF6 Circuit Breaker Type LTB E 1HSB435409 100 enrev1 Operating and Maintenance Instructions ...
Страница 92: ...ABB Switchgear SF6 Circuit Breaker Circuit breakers HPL and LTB 1HSB445409 1 en0 Lubricants ...
Страница 94: ...Lubricants 1HSB445409 1 en0 i LIST OF CONTENTS 1 General 1 1 1 Safety instructions 1 2 Oil 3 3 Grease 5 ...
Страница 100: ...ABB Switchgear SF6 Circuit Breaker Operating Mechanism type BLG 1002A 1HSB515409 100 en rev2 Maintenance ...
Страница 184: ...ABB Switchgear SF6 Circuit Breaker Operating mechanism type BLG 1002A 1HSB515409 200 en rev2 Spare Parts ...
Страница 198: ......
Страница 199: ......
Страница 209: ......
Страница 210: ......