Operating Mechanism Maintenance
1HSB515409-100 en rev2
27
Slow opening operation
May only be done if:
1.
The circuit-breaker is in the closed position.
2.
The switch Local/Remote (1) on
the control panel is in the Off
position.
3.
The motor voltage is switched
off with the direct-on-line
starters (2), (3).
4.
The switch Motor/Hand (4) is in
the Hand position so that the
hand crank shaft can be released.
Figure 4-8. Switch Local/Remote, dirct-on-line starters.
Item
1
Switch Local/Remote
2
Direct-on-line starter
3
Direct-on-line starter
4
Switch Motor/Hand
2
4
1
B20002