Safety
Operating Mechanism Maintenance
4
1HSB515409-100 en rev2
2.2 Safety directives
On all types of work on high-voltage circuit-breakers, the risks listed below must be
taken into consideration and corresponding measures must be taken.
WARNING
Breakers with pressurised insulators.
Mechanical damage to the porcelain can cause it to explode with the
following risk of splintering.
Work on the circuit-breaker that risk mechanical damage to the insulators
should be carried out at a reduced gas pressure, 0.125 MPa (abs).
WARNING
Do not operate the mechanism unloaded!
Operations shall take place only when the mechanism has been connected
and trimmed with the associated circuit-breaker.
The standard operating cycle is O- 0.3 s - CO - 3 min. -CO. The time between
closing operations should not be less than 1 minute when circuit-breakers and relay
systems are tested with more than 3 closing operations.
Содержание SF6 LTB 245E1 BLG 1002A
Страница 1: ...Product Manual 1HSB435416 2 en Rev 1 LTB 245E1 BLG 1002A 3 pole operation ...
Страница 63: ...ABB Switchgear SF6 Circuit Breaker Circuit breakers HPL and LTB 1HSB445410 100 en rev1 Check list assembly ...
Страница 68: ...ABB Switchgear SF6 Circuit Breaker Type LTB E 1HSB435409 100 enrev1 Operating and Maintenance Instructions ...
Страница 92: ...ABB Switchgear SF6 Circuit Breaker Circuit breakers HPL and LTB 1HSB445409 1 en0 Lubricants ...
Страница 94: ...Lubricants 1HSB445409 1 en0 i LIST OF CONTENTS 1 General 1 1 1 Safety instructions 1 2 Oil 3 3 Grease 5 ...
Страница 100: ...ABB Switchgear SF6 Circuit Breaker Operating Mechanism type BLG 1002A 1HSB515409 100 en rev2 Maintenance ...
Страница 184: ...ABB Switchgear SF6 Circuit Breaker Operating mechanism type BLG 1002A 1HSB515409 200 en rev2 Spare Parts ...
Страница 198: ......
Страница 199: ......
Страница 209: ......
Страница 210: ......