8 SafeRing/SafePlus 36kV
| Installation and operating instruction
3.2 FUSE TABLE - CEF
SafeRing 36
SafePlus 36
F-panel
100% load
Rated voltage:
36 kV
Operating voltage:
30 kV
I
transfer
at 36 kV:
840 A
T
o
:
40 ms
Transformer rating (kVA)
u
k
(%)
Transformer rated current
(A)
ABB Catalogue no
.
Fuse link rated current
(A)
100
4
1,9
1YMB531006M0001
6
125
4
2,4
1YMB531006M0002
10
160
4
3,1
1YMB531006M0002
10
200
4
3,8
1YMB531006M0003
16
250
4
4,8
1YMB531006M0003
16
315
4
6,1
1YMB531006M0003
16
400
4
7,7
1YMB531006M0003
16
500
4
9,6
1YMB531006M0004
25
630
4
12,1
1YMB531006M0004
25
800
5
15,4
1YMB531006M0004
25
1000
6
19,2
1YMB531006M0005
40
1250
6
24,1
1YMB531006M0005
40
SafeRing 36
SafePlus 36
F-panel
120% load
Rated voltage: 36 kV
Operating voltage: 30 kV
I
transfer
at 36 kV: 840 A
T
o
: 40 ms
Transformer rating (kVA)
u
k
(%
)
Transformer rated current
(A)
ABB Catalogue no.
Fuse link rated current
(A)
100
4
1,9
1YMB531006M0001
6
125
4
2,4
1YMB531006M0002
10
160
4
3,1
1YMB531006M0002
10
200
4
3,8
1YMB531006M0003
16
250
4
4,8
1YMB531006M0003
16
315
4
6,1
1YMB531006M0003
16
400
4
7,7
1YMB531006M0003
16
500
4
9,6
1YMB531006M0004
25
630
4
12,1
1YMB531006M0004
25
800
5
15,4
1YMB531006M0005
40
1000
6
19,2
1YMB531006M0005
40
1250
6
24,1
1YMB531006M0005
40
−
Both tables above are based on using ABB CEF high-voltage current-limiting back-up fuse-links
−
Normal operating conditions with no overlaod of transformer (table 1) and with 20% overlaod of transformer (table 2)
−
Ambient air temperature -25
o
C to +40
o
C