background image

ABB | SACE Emax 2

Management operations

4 - Environmental conditions

30 | © 2023 ABB |  1SDH001000R0002 - ECN000297030

>690V version IEC circuit-

breakers

>690V disconnectors and circuit-breakers are available in the following configurations:

Circuit-breaker

Voltage

Version

E2.2/E9/E10

800/900/1000 V

F-W

E4.2/E9/E10/E12

800/900/1000/1150/1200 V

F-W

E6.2/E9

800/900 V

F-W

Insulating protections are mandatory for >690 V fixed versions of E2.2, E4.2 and E6.2.
Details about assembling insulating protections are available at http://www.abb.com/abblibrary/
DownloadCenter/, especially in the kit sheet 

1SDH001000R0746

.

Grounding

The circuit-breakers in fixed version and the fixed part of withdrawable circuit-breakers are equipped with 
a screw for the ground connection.
The connection must be implemented by means of a conductor of suitable cross-section according to the 
IEC 61439-1 Standard.
Clean and degrease the area around the screw before making the connection.
After assembly of the conductor, tighten the screw with a torque of 2 N m - 17.7 lb in.
Alternatively, no connection will be required if circuit-breaker frame continuity with the switchgear 
earthing is provided by the metal contact (support) between the circuit-breaker and the metal structure 
of the switchgear (or a part of the protection circuit) (as long as there are no insulating panels between 
the circuit-breaker and the metal frame of the switchgear).

Figure 74 - Fixed version

Figure 75 - Withdrawable

 

Содержание SACE Emax 2 E2.2

Страница 1: ...01000R0002 ECN000297030 EN EMAX LOW VOLTAGE AIR CIRCUIT BREAKERS E2 2 E4 2 E6 2 Sace Emax 2 Installation operation and maintenance instructions for the instal ler and the user Sace Emax 2 DOC N 1SDH00...

Страница 2: ...ABB SACE Emax 2 ABB SACE Emax 2 2023 ABB 1SDH001000R0002 ECN000297030...

Страница 3: ...andling 10 3 Description 13 4 Environmental conditions 23 5 Installation 23 Ekip Dip 31 1 General characteristics 31 2 Operator interface 32 3 Protections Introduction 34 4 List of alarms and signals...

Страница 4: ...2 2023 ABB SACE Emax 2 1SDH001000R0002 ECN000297030...

Страница 5: ...Trip unit SACE Emax 2 CBs equipped with dip switch type interface Trip coil CB opening actuator controlled directly by Trip unit TRIP Concluding action of protection timing or a test command which ex...

Страница 6: ...ricity can create Trained Persons in the electrical field IEV 195 04 02 person adequately advised or supervised by electrically skilled persons to enable him or her to perceive risks and to avoid dang...

Страница 7: ...nst certain methods installation operation and maintenance that could cause injury to personnel damage equipment or make them unsafe thesewarningsandalarmsdonotincludealltheconceivablemethodsofperform...

Страница 8: ...ng international standards IEC 60947 EN 60947 CEI EN 60947 IEC 61000 UL 1066 They comply with the following EC directives Low Voltage Directives LVD No 2006 95 EC Electromagnetic Compatibility Directi...

Страница 9: ...I IV Fs III IV Fs E2 2 46 Kg 101 lbs 58 Kg 128 lbs 53 Kg 117 lbs 60 Kg 132 lbs 41 Kg 90 lbs 49 Kg 108 lbs E4 2 63 Kg 139 lbs 77 Kg 170 lbs 67 Kg 148 lbs 81 Kg 179 lbs 57 Kg 126 lbs 69 Kg 152 lbs E6 2...

Страница 10: ...aker serial number 6 Features of the circuit breaker Packaging checks Examine the state of the material received and verify that The circuit breaker or the fixed part are consistent with the order The...

Страница 11: ...rage that The circuit breaker is in the open position and the springs are discharged See the chapter Description circuit breaker opening closing operations on page 16 The circuit breaker is protected...

Страница 12: ...breaker safely refer to the instruction sheet in the zipped packaging pouch The following is the procedure for opening the packaging 1 Cut the bands that wrap the packing box See Figure 6 and Figure 7...

Страница 13: ...ws and the mounting brackets See Figure 11 Moving part IEC Figure 12 Moving part UL Figure 13 Fixed part IEC and Figure 14 Fixed part UL Figure 10 Fixed circuit breaker Figure 11 Moving part IEC Figur...

Страница 14: ...lbs NOTE the weights indicated in the table refer to the basic circuit breakers including relays and its sensors without terminals and without accessories the weights of the withdrawable circuit brea...

Страница 15: ...nt transformer of its own phase The circuit breaker is available in two types fixed version withdrawable The circuit breaker in fixed version see Figure 18 has its own terminals for connection to the...

Страница 16: ...ipped TU 7 Closing pushbutton 8 Springs charged discharged signalling device 9 Electrical data plate Description of electrical data plate IEC 1 9 10 4 5 11 8 7 2 3 12 6 13 Uimp 12 kV Figure 23 Pos Des...

Страница 17: ...a ge V 254 635 Ra t e d S hor t Cir c ui t kA 100 85 S hor t Time kA Accessories AUX 4 AUX 6 RT C YR YC2 U 3 A 400 V AC 220 V 250 V AC DC 220 V 250 V AC DC 220 V 250 V AC DC 508 100 Low Vol tage AC P...

Страница 18: ...s charged signalling device B is yellow CHARGED SPRING as indicated in Figure 26 Figure 25 A B Figure 26 3 Check that the circuit breaker is open open closed signalling device O OPEN and check that th...

Страница 19: ...to close see Figure 35 This state occurs when after closing see step 4 Manual operations for opening and closing the circuit breaker the springs are recharged manually or automatically by the gearmot...

Страница 20: ...remove all equipment used during the work and remove processing waste and materials used 1 Turn plate through 90 before inserting the moving part CLICK 1 2 3 Figure 37 2 Position the lifting plates on...

Страница 21: ...latch the tongue and remove the lifting plates from the moving part See Figure 41 1 2 3 Figure 41 6 Make sure that the signalling device indicates the DISCONNECT position See Figure 42 Figure 42 7 Gri...

Страница 22: ...his phase the moving part will still be in the DISCONNECT position See Figure 45 Figure 44 2 1 Figure 45 10 Turn the crank clockwise until the pushbutton comes out and the indicator shows that the cir...

Страница 23: ...rder to be able to reach the test position On the UL version the fail safe prevents the removal of the circuit breaker from the fixed part with springs charged Discharge the springs before removing th...

Страница 24: ...part make sure that both guides on the fixed part travel to the same extent thereby keeping the moving part parallel to the fixed part See Figure 51 Mechanical position indicators The following are th...

Страница 25: ...arge of handling and lifting must use appropriate safety equipment Mounting of the fixed circuit breaker Fix the circuit breaker to a horizontal surface using 4 x M10 screws Lock the screws with tight...

Страница 26: ...E6 2 circuit breakers can only be installed in vertical position Lateral fixing only for circuit breakers to IEC 60068 2 6 Test Fc standards Further details about lateral fixing of fixed parts are ava...

Страница 27: ...bility The table of terminals available for each circuit breaker is given below F HR VR SHR SVR FL E2 2 IEC 690 V F W X X X X X 800 900 V X X X 1000 1150 V X UL 600 V X X E4 2 IEC 690 V X X X 800 900V...

Страница 28: ...E4 2 E6 2 Phase separators Phase barriers are mandatory for 2ps configuration For the 4ps configuration it is possible to place isolation barriers for the segregation of live parts In addition the pha...

Страница 29: ...0 6 100x10 1 values for spread terminals circuit breaker UL 1066 Iu A Horizontal terminals Vertical terminals Q ty Dimension of busbars in Q ty Dimension of busbars in E2 2 A 1600 3 1 4 x 2 5 2 1 4 x...

Страница 30: ...SDH001060R0100 E6 2 III IV Fixed HR IEC 1SDH001060R0101 E6 2 III IV Fixed VR IEC 1SDH001060R0102 E6 2 IV FS Fixed HR VR IEC 1SDH001060R0104 E6 2 III IV Fixed F IEC 1SDH001060R0105 E6 2 III IV Withdraw...

Страница 31: ...type and the peak current 100 3 94 150 5 91 200 7 87 250 9 84 300 11 81 350 13 78 400 15 75 450 17 72 500 19 69 40 60 80 100 120 140 160 180 200 220 240 260 280 300 E2 2 E4 2 E6 2 L mm 1 Ipk kA 2 Fig...

Страница 32: ...kers in fixed version and the fixed part of withdrawable circuit breakers are equipped with a screw for the ground connection The connection must be implemented by means of a conductor of suitable cro...

Страница 33: ...s Parameter Rated operating range Primary current 0 004 16 In 1 Rated frequency 45 55 Hz with fn 50 Hz 54 66 Hz with fn 60 Hz Peak factor Complying with standard IEC 60947 2 1 range with reference to...

Страница 34: ...n LED alarm and trip B L Protection LED pre alarm C S Protection LED alarm and trip D I Protection LED trip E G Protection LED alarm and trip F Power on LED trip unit powered and on G Protections thre...

Страница 35: ...able Neutral allows activation and adjustment of the protections on the neutral pole Frequency allows the selection of the installation frequency iTest pushbutton The iTest pushbutton is useful for th...

Страница 36: ...versions of the trip unit When the activation threshold is exceeded the protection trips in a time that decreases as the current read increases Parameters All the parameters that can be modified by th...

Страница 37: ...Threshold I2 It defines the current value that activates the protection when exceeded with reference to the curve it is the part parallel to the y axis IMPORTANT The I2 threshold set must be higher t...

Страница 38: ...adjustable time Parameters The user can set the intervention threshold Parameter Description Enable By setting the threshold dip switches to the Off position the protection is disabled Threshold I3 I...

Страница 39: ...ding to the selection NOTE calculation of the tripping time of the inverse time curve is based on a mathematical expression The details are provided in the table on page39 Threshold I4 It defines the...

Страница 40: ...on the Neutral is disabled Threshold InN It establishes the multiplication factor applied to the trip thresholds of the protections 50 trip threshold of the neutral current lower than other phases 10...

Страница 41: ...Iinst Defined by ABB Instantaneous 1 See the serigraph for the available combinations 2 t t calculation is valid for If values that have exceeded the trip threshold of the protection Use fault curren...

Страница 42: ...R single G All R G G G Internal configuration error 5 x x x A Trip coil disconnected or trip command failed x B Current sensors disconnected x B Rating Plug error X B E Protection delay x C Temperatur...

Страница 43: ...n for all other sizes in the absence of auxiliary power supply t2 0 4s in the case of UL circuit breaker t4 0 4s in the case of UL circuit breaker I4 1200 A in case of UL circuit breaker E Install by...

Страница 44: ...l YO 4 YC R R YO2 4 R R YU 2 4 R R M R R YR R Security mechanical KLC PLC R R KLP PLP 1 R R SL 1 S S DLC R R Anti insertion lock S S MOC R R FAIL SAFE 3 R R Protection mechanical PBC R R IP54 R R HTC...

Страница 45: ...r HAZARD RISKOFELECTRICSHOCK Testthecircuit breakerwithallswitchgearapparatus de energized IMPORTANT The verifications involve procedures which must only be performed by persons skilled in the electri...

Страница 46: ...the presence of an undervoltage coil the circuit breaker can be closed only after the trip unit is energized Trip unit alarm Connect the protection device Ekip TT to the trip unit and verify that ther...

Страница 47: ...The circuit breaker closes correctly the signals are normal 2 Turn off the voltage supply to the trip unit The circuit breaker opens 3 Power the undervoltage coil at the relevant rated voltage and per...

Страница 48: ...acked 1 Perform operating tests Result the interlocks function correctly Racking in out device 1 Perform a few racking in and racking out operations Result in the rack in operation the circuit breaker...

Страница 49: ...dures and checked the accessories Print this sheet and use it to make an inspection report in the Checks column Operation Description Check 1 Circuit breaker OFF Open the circuit breaker 2 Circuit bre...

Страница 50: ...EV 195 04 01 person with sufficient training and experience to enable him or her to perceive risks and to avoid the dangers potentially created by electricity This is because it may be necessary to pe...

Страница 51: ...set Press the TU Reset button The power supply voltage of the auxiliary circuits is too low Measure the voltage it should not be lower than 70 of the rated voltage of the coil The power supply voltage...

Страница 52: ...y in the terminals Make sure there is continuity between cable and terminal and if necessary reconnect the cables of the gearmotor to the terminals The connections of the power supply circuit are wron...

Страница 53: ...le it if it is not necessary Incorrect neutral selection Modify the neutral selection Rapid trip with I3 Off linst trip Correct operating condition with short circuit at high current High ground fault...

Страница 54: ...forming procedures that can be performed by Trained Persons in the electrical field IEV 195 04 02 person adequately advised or supervised by electrically skilled persons to enable him or her to percei...

Страница 55: ...ABB SACE Emax 2 Putting into service and maintenance 4 Decommissioning and treatment at end of life 53 2023 ABB 1SDH001000R0002 ECN000297030...

Страница 56: ...ity whatsoever for potential errors or possible lack of information in this document We reserve all rights in this document and in the subject matter and illustrations contained therein Any reproducti...

Отзывы: