18.10
Signal matrix for analog inputs SMAI
SEMOD55751-1 v2
18.10.1
Application
SEMOD55744-4 v10
Signal matrix for analog inputs (SMAI), also known as the preprocessor function
block, analyses the connected four analog signals (three phases and neutral) and
calculates all relevant information from them like the phasor magnitude, phase
angle, frequency, true RMS value, harmonics, sequence components and so on.
This information is then used by the respective functions connected to this SMAI
block in ACT (for example protection, measurement or monitoring functions).
18.10.2
Frequency values
GUID-B494B93C-B5AA-4FD6-8080-8611C34C2AD8 v5
The SMAI function includes a functionality based on the level of positive sequence
voltage,
MinValFreqMeas
, to validate if the frequency measurement is valid or not.
If the positive sequence voltage is lower than
MinValFreqMeas
, the function
freezes the frequency output value for 500 ms and after that the frequency output is
set to the nominal value. A signal is available for the SMAI function to prevent
operation due to non-valid frequency values.
MinValFreqMeas
is set as % of
UBase
/√3
If SMAI setting
ConnectionType
is
Ph-Ph
, at least two of the inputs GRPxL1,
GRPxL2 and GRPxL3, where 1≤x≤12, must be connected in order to calculate the
positive sequence voltage. Note that phase to phase inputs shall always be
connected as follows: L1-L2 to GRPxL1, L2-L3 to GRPxL2, L3-L1 to GRPxL3. If
SMAI setting
ConnectionType
is
Ph-N
, all three inputs GRPxL1, GRPxL2 and
GRPxL3 must be connected in order to calculate the positive sequence voltage.
If only one phase-phase voltage is available and SMAI setting
ConnectionType
is
Ph-Ph
, the user is advised to connect two (not three) of the inputs GRPxL1,
GRPxL2 and GRPxL3 to the same voltage input as shown in figure
to make
SMAI calculate a positive sequence voltage.
SMAI1
BLOCK
DFTSPFC
REVROT
^GRP1L1
^GRP1L2
^GRP1L3
^GRP1N
SPFCOUT
G1AI3P
G1AI1
G1AI2
G1AI4
G1N
NEUTRAL
PHASEL3
PHASEL2
PHASEL1
UL1L2
SAPTOF
U3P*
BLOCK
BLKTRIP
TRIP
START
BLKDMAGN
FREQ
TRM_40.CH7(U)
SAPTOF(1)_TRIP
EC10000060-3-en.vsdx
IEC10000060 V3 EN-US
Figure 124:
Connection example
1MRK 504 169-UEN A
Section 18
Basic IED functions
Transformer protection RET650 2.2 IEC
347
Application manual
Содержание ret650
Страница 1: ...RELION 650 SERIES Transformer protection RET650 Version 2 2 Application manual...
Страница 2: ......
Страница 28: ...22...
Страница 38: ...32...
Страница 42: ...36...
Страница 80: ...74...
Страница 168: ...162...
Страница 174: ...168...
Страница 250: ...244...
Страница 346: ...340...
Страница 366: ...360...
Страница 390: ...384...
Страница 391: ...385...