tDGasPresAlm
: Time delay for gas pressure alarm.
tDGasPresLO
: Time delay for gas pressure lockout.
DirCoef
: Directional coefficient for circuit breaker life calculation.
RatedOperCurr
: Rated operating current of the circuit breaker.
RatedFltCurr
: Rated fault current of the circuit breaker.
OperNoRated
: Number of operations possible at rated current.
OperNoFault
: Number of operations possible at rated fault current.
CBLifeAlmLevel
: Alarm level for circuit breaker remaining life.
AccSelCal
: Selection between the method of calculation of accumulated energy.
OperTimeDelay
: Time delay between change of status of trip output and start of
main contact separation.
13.5
Event function EVENT
IP14590-1 v2
13.5.1
Identification
SEMOD167950-2 v2
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Event function
EVENT
S00946 V1 EN-US
-
13.5.2
Application
M12805-6 v11
When using a Substation Automation system with LON or SPA communication,
time-tagged events can be sent at change or cyclically from the IED to the station
level. These events are created from any available signal in the IED that is
connected to the Event function (EVENT). The EVENT function block is used for
LON and SPA communication.
Analog, integer and double indication values are also transferred through the
EVENT function.
Section 13
1MRK 504 169-UEN A
Monitoring
284
Transformer protection RET650 2.2 IEC
Application manual
Содержание ret650
Страница 1: ...RELION 650 SERIES Transformer protection RET650 Version 2 2 Application manual...
Страница 2: ......
Страница 28: ...22...
Страница 38: ...32...
Страница 42: ...36...
Страница 80: ...74...
Страница 168: ...162...
Страница 174: ...168...
Страница 250: ...244...
Страница 346: ...340...
Страница 366: ...360...
Страница 390: ...384...
Страница 391: ...385...