Accepted originator categories for PSTO
If the requested command is accepted by the authority control, the value will
change. Otherwise the attribute
blocked-by-switching-hierarchy
is set in the
cause
signal. If the PSTO value is changed during a command, then the command is
aborted.
The accepted originator categories for each PSTO value are shown in
.
Table 20:
Accepted originator categories for each PSTO
Permitted Source To Operate
Originator (orCat)
0 = Off
4,5,6
1 = Local
1,4,5,6
2 = Remote
2,3,4,5,6
3 = Faulty
4,5,6
4 = Not in use
4,5,6
5 = All
1,2,3,4,5,6
6 = Station
2,4,5,6
7 = Remote
3,4,5,6
PSTO = All, then it is no priority between operator places. All operator places are
allowed to operate.
According to IEC 61850 standard the
orCat
attribute in originator category are
defined in
Table 21:
orCat attribute according to IE C61850
Value
Description
0
not-supported
1
bay-control
2
station-control
3
remote-control
4
automatic-bay
5
automatic-station
6
automatic-remote
7
maintenance
8
process
11.1.1.1
Bay control QCBAY
M16595-3 v9
The Bay control (QCBAY) is used to handle the selection of the operator place per
bay. The function gives permission to operate from two main types of locations
either from Remote (for example, control centre or station HMI) or from Local
1MRK 504 169-UEN A
Section 11
Control
Transformer protection RET650 2.2 IEC
179
Application manual
Содержание ret650
Страница 1: ...RELION 650 SERIES Transformer protection RET650 Version 2 2 Application manual...
Страница 2: ......
Страница 28: ...22...
Страница 38: ...32...
Страница 42: ...36...
Страница 80: ...74...
Страница 168: ...162...
Страница 174: ...168...
Страница 250: ...244...
Страница 346: ...340...
Страница 366: ...360...
Страница 390: ...384...
Страница 391: ...385...