Section 2
Application
2.1
General IED application
GUID-EB939A4F-1C88-4EB1-A217-571FEF72AC7B v4
The RET650 provides fast and selective protection, monitoring and control
functions for two- and three-winding transformers, autotransformers, generator-
transformer units and shunt reactors. The IED is designed to operate correctly over
a wide frequency range in order to accommodate power system frequency
variations during disturbances and generator startup and shutdown. Apparatus
control for 3 circuit breakers is included.
A fast differential protection function with built-in transformer ratio matching and
vector group compensation makes this IED the ideal solution even for the most
demanding applications. Since RET650 has very low requirements on the main
CTs, no interposing CTs are required. The differential protection function is
provided with 2nd harmonic and waveform-blocking restraint features to avoid
tripping for magnetizing inrush current, and 5th harmonic restraint to avoid
tripping for overexcitation.
The differential function offers a high sensitivity for low-level internal faults. The
unique and innovative sensitive differential protection feature of the RET650
provides the best possible coverage for internal turn-to-turn winding faults, based
on the theory of symmetrical components.
A low impedance restricted earth-fault protection function is available as a
complimentary sensitive and fast main protection against winding earth faults. This
function includes a directional zero-sequence current criterion for additional
security.
Tripping from pressure relief/Buchholz and temperature devices can be
implemented through the IED's binary inputs, where trip signal conditioning can be
performed (pulsing, lockout, additional logics, etc.). The binary inputs are
thoroughly stabilized against disturbances in order to prevent incorrect operations
due to DC system capacitive discharges or DC earth faults, for example.
Versatile phase, earth and zero sequence overcurrent functions with directional
capability provide further alternative backup protections. Thermal overload with
two time-constants and breaker failure protection is also available.
A built-in disturbance and event recorder provides valuable data to the user about
status and operation for post-fault disturbance analysis.
Two pre-configured packages have been defined for the following applications:
1MRK 504 169-UEN A
Section 2
Application
Transformer protection RET650 2.2 IEC
23
Application manual
Содержание ret650
Страница 1: ...RELION 650 SERIES Transformer protection RET650 Version 2 2 Application manual...
Страница 2: ......
Страница 28: ...22...
Страница 38: ...32...
Страница 42: ...36...
Страница 80: ...74...
Страница 168: ...162...
Страница 174: ...168...
Страница 250: ...244...
Страница 346: ...340...
Страница 366: ...360...
Страница 390: ...384...
Страница 391: ...385...