41
Function name
Configuration
IEC61850
IEC60617
ANSI/C37.2
Description
RA01 and RA02
Voltage protection
SPHPTOV1
3U >(1)
59-1
Three-phase overvoltage 1, source 1 low stage
Y
SPHPTOV2
3U >(2)
59-2
Three-phase overvoltage 2, source 1 high stage
Y
SPHPTOV3
3U >(3)
59-3
Three-phase overvoltage 3, source 2 low stage
Y
SPHPTUV1
3U <(1)
27-1
Three-phase undervoltage 1, source 1 low stage
Y
SPHPTUV2
3U <(2)
27-2
Three-phase undervoltage 2, source 1 high stage
Y
SPHPTUV3
3U <(3)
27-3
Three-phase undervoltage 3, source 2 low stage
Y
PSPTOV1
U1>(1)
59PS-1
Positive sequence overvoltage protection, source1
Y
PSPTOV2
U1>(2)
59PS-2
Positive sequence overvoltage protection, source 2
Y
NSPTOV1
U2>(1)
47-1
Negative sequence overvoltage protection, source1
Y
NSPTOV2
U2>(2)
47-2
Negative sequence overvoltage protection, source 2
Y
ROVPTOV1
Uo>(1)
59N-1
Zero sequence overvoltage protection, source1
Y
ROVPTOV2
Uo>(2)
59N-2
Zero sequence overvoltage protection, source 2
Y
Total voltage protection functions included
12
Frequency protection
FRPFRQ1
f</f>,df/dt(1) 81-1
Underfrequency, overfrequency, frequency rate of change, source
1, stage 1
Y
FRPFRQ2
f</f>,df/dt(2) 81-2
Underfrequency, overfrequency, frequency rate of change, source
1, stage 2
Y
LSHDPFRQ1
UFLS/R(1)
81S-1
Load shed & restoration, source 1, stage 1
Y
LSHDPFRQ2
UFLS/R(2)
81S-2
Load shed & restoration, source 1, stage 2
Y
Total frequency protections included
4
Other protection
PHIZ1
PHIZ1
HIZ
High Impedance Fault Detector
Y
SCCBRBRF1
3I>/Io>BF
50BFT
Circuit breaker failure protection
Y
SCCBRBCF1
SCCBRBCF1
50BFC
Circuit breaker close failure protection
Y
DRFLO1
FLO
FLO
Fault Locator (FLOC)
Y
DPSRDIR1
P>->
32P
Directional positive sequence power protection
Y
DNZSRDIR1
Q>->
32N
Directional negative/zero sequence power protection
Y
DLCM1
LCM
LCM
Loop control
Y
Total other protection functions included
7
Control
SDARREC1
O -> I
79
Autoreclosing, 1ph and/or 3-ph
SECRSYN1
SYNC
25
Synchro-check/voltage check
SCBXCBR1
I<->O CB
52
Circuit Breaker 1 (3 state inputs / 3 control outputs)
Total control functions included
3
Condition monitoring
SPSCBR1
CBCM
52CM
CB condition monitoring
Y
SEQRFUF1
FUSEF
60
Fuse failure supervision, source 1
Y
Total cond. monitoring functions
2
Measurements
CMMXU1
3I
IA,IB,IC
Three-phase current
Y
CSMTA1
Demand metering, Max/Min metering
Y
CSMSQI1
I1,I2,I0
I1, I2, I0
Sequence current
Y
RESCMMXU1
Io
IG
Ground current
Y
VMMXU1
3U
VA,VB,VC
Three-phase voltage measurement, source 1
Y
VMMXU2
3U(B)
VA,VB,VC(2) Three-phase voltage measurement, source 2
Y
VSMSQI1
U1,U2,U0
V1,V2,V0
Sequence voltage measurement, source 1
Y
VSMSQI2
U1,U2,U0(B)
V1,V2,V0(2) Sequence voltage measurement, source 2
Y
APEMMXU1
P,E
P,E
Single and three phase power, power factor and three phase
energy, source 1
Y
FMMXU1
f
f
Frequency measurement, source 1
Y
Total meas. functions
10