background image

38

R E R6 20 

A DVA N C ED  R EC LOSER  P R OT EC T I O N  &  CO N T R O L

Table 56. Supported functions

Function

WebHMI

PCM600

PCM Engineering

PCM Engineering 
Pro

Protection and control relay parameter 
setting

Saving of protection and control relay 
parameter settings in the relay

Signal monitoring

Disturbance recorder handling

Alarm LED viewing

Access control management

Protection and control relay signal 
configuration (signal matrix)

-

Modbus® communication configuration 
(communication management)

-

DNP3 communication configuration 

(communication management)

-

(communication management)

-

Saving of protection and control relay 
parameter settings in the tool

-

Disturbance record analysis 

-

XRIO parameter export/import

-

Graphical display configuration

-

Application configuration

-

IEC 61850 communication configuration, 

GOOSE (communication configuration)

-

-

-

Phasor diagram viewing

-

-

-

Event viewing

-

-

-

Saving of event data on the user’s PC

-

-

-

Содержание RER620

Страница 1: ...PRODUCT GUIDE RER620 Advanced recloser protection control...

Страница 2: ...use failure protection 015 016 15 Uninterruptable Power Supply UPS 016 16 Universal Power Driver UPD 016 17 Access control 016 18 Inputs and outputs 016 017 19 Communications 016 032 20 Technical data...

Страница 3: ...l based communication networks with DNP3 Level 2 Modbus IEC 61850 IEC 60870 5 101 104 and PG E 2179 By using Application Configuration Tool ACT of PCM600 tool different applications such as re closer...

Страница 4: ...odbus or PG E 2179 protocols Included with the optional serial communication ports is IRIG B time synchroniza tion The DNP3 0 PG E 2179 Level 2 implementation in cludes some Level 3 functionality Func...

Страница 5: ...asurement Digital fault waveform recorder Three phase current measurement Sequence current measurement Three phase voltage measurement source 1 Three phase voltage measurement source 2 Sequence voltag...

Страница 6: ...directional ele ments provide a variety of different polarizing quantities such as Positive or Negative sequence voltage self polarizing faulted or cross polarizing healthy voltages To secure a relia...

Страница 7: ...ection functions available for the standard configuration RER620 1 Io selectable by setting Io calculated as default 52 or Va Vb Vc 3 51P 3I 50P 1 3I 50P 2 3I 50P 3 3I 68 46PD 3I2f I2 I1 I2 50BF 3I BF...

Страница 8: ...accepted as a means to significantly im prove circuit reliability and to provide more effec tive system operation embedded Loop Control functionality is provided as a standard feature In such applica...

Страница 9: ...ation FDIR con trol using IEC61850 GOOSE messaging REF 615 LS B HS B 52 52 REF 615 REF 615 T IEC 61850 52 GridShield 52 52 X Fault 52 GridShield 52 GridShield REF 615 LS B HS B 52 52 REF 615 REF 615 T...

Страница 10: ...CONTROL Figure 3 Recloser appli cation with Distributed Energy Resources DER REF 615 LS B HS B 52 REF 615 T M Motorized Disconnect Switch 89 Load break switch 52 G Loads 52 Interconnection Transformer...

Страница 11: ...ield 52 GridShield 52 GridShield Substation Circuit Breaker Source 1 Substation Circuit Breaker Source 2 Sectionalizing Recloser Midpoint Recloser Tie Point Recloser Sectionalizing Recloser Midpoint R...

Страница 12: ...n level COM600 utilizes the data content of the design level protection and control relays to offer enhanced substation level function ality COM600 features a web browser based HMI providing a customi...

Страница 13: ...P3 0 IEC 60870 5 104 Note 1 Peer to peer over IEC61850 GOOSE can be used for sharing information between recloser for possible restoration interlocking isolation etc Note 2 DNP3 0 Serial or TCP IP IEC...

Страница 14: ...w or exceeds the set values The binary signal channels can be set to start a recording on the ris ing or the falling edge of the binary signal or both By default the binary channels are set to record...

Страница 15: ...rithm Upon the detection of a failure the fuse failure supervision function activates an alarm and blocks voltage dependent protection functions from unintended operation 15 Uninterruptable Power Supp...

Страница 16: ...ary input turn on thresholds are programmable from 18 176 V DC by adjusting the relay s parameter settings Besides the dedi cated trip close outputs that are mandatory to drive the magnetic actuators...

Страница 17: ...is sup ported for DNP3 RER620 listens the DNP master on both channels serial and TCP IP simultaneously and responds on both ports One DNP master is supported Status and control including recloser bre...

Страница 18: ...ncy of 2 x fn Hz Maximum interruption time in the auxiliary DC voltage without resetting the protection and control relay 50 ms at 60 V DC Fuse type T4A 250 V Table 7 Uninterruptable Power Supply UPS...

Страница 19: ...on 31 0 to 570 mW Threshold voltage 18 to 176 V DC Reaction time 3 ms Description Value Rated voltage 250 V AC DC Continuous contact carry 5 A Make and carry for 3 0 s 10 A Make and carry 0 5 s 15 A B...

Страница 20: ...IEEE C37 60 2003 15 kV 27 kV 38 kV reclosers No influence Output voltage range for 6 channels half bridge drivers High and low side drives per channel 250 VDC Switching capacity 6 channels half bridg...

Страница 21: ...III Common mode Differential mode 2 5 kV 2 5 kV IEEE C37 90 1 2002 Electrostatic discharge test Contact discharge Air discharge 8 kV 15 kV IEEE C37 90 3 2001 Radio frequency interference tests 20 V m...

Страница 22: ...5 ms Reset time 40 ms Reset ratio Typical 0 96 Retardation time 30 ms Trip time accuracy in definite time mode 1 0 of the set value or 20 ms Trip time accuracy in inverse time mode 5 0 of the theoreti...

Страница 23: ...tact 3 Maximum Pickup range 2 5 x In Pickup range multiples in range of 1 5 to 20 Table 25 51N G 50N G 1 2 50N G 3 technical data Description Value Depending on the frequency of the current measured f...

Страница 24: ...racy Depending on the frequency of the current measured fn 2Hz 1 5 of the set value or 0 002 x In Pickup time 1 2 IFault 2 x set Pickup value IFault 10 x set Pickup value Minimum Typical Maximum 22 ms...

Страница 25: ...a Characteristic Value Operation accuracy Depending on the frequency of the current measured fn 2Hz 1 5 of the set value or 0 002 x Vn Pickup time 1 2 VFault 1 1 x set Pickup value Minimum Typical Max...

Страница 26: ...Value Operation accuracy Depending on the frequency of the current measured fn 2Hz 1 5 of the set value or 0 002 x Vn Pickup time 1 2 Minimum Typical Maximum VFault 1 1 x set Pickup value 29 ms 31 ms...

Страница 27: ...ms Operate time accuracy 1 0 of the set value or 30 ms Characteristic Value Operation accuracy f 10 mHz df dt 100 mHz s in range df dt 5 Hz s 2 0 of the set value in range 5 Hz s df dt 15 Hz s Start...

Страница 28: ...on the frequency of the current measured fn 2Hz At voltages in range 0 01 to 4 00 x In 0 5 or 0 002 x Vn Suppression of harmonics DFT 50dB at f n x fn where n 2 3 4 5 RMS No suppression Characteristi...

Страница 29: ...50dB at f n x fn where n 2 3 4 5 Characteristic Value Operation accuracy 10 mHz in measurement range 35 75 Hz Characteristic Value Operation accuracy At all three currents in range 0 10 to 1 20 x In A...

Страница 30: ...accuracy 1 0 of the set value or 20 ms Table 46 25 technical data Characteristic Value Operation accuracy Depending on the frequency of the voltage measured fn 1 Hz Voltage 3 0 of set value or 0 01 x...

Страница 31: ...fn 60 Hz fault voltage with nominal frequency injected from ran dom phase angle results based on statistical distribution of 1000 measurements 1 Zero sequence voltage before fault 0 0 x Vn fn 60 Hz z...

Страница 32: ...set value or 0 002 x Vn Pickup time 1 2 VFault 1 1 x set Pickup value Minimum Typical Maximum 29 ms 31 ms 32 ms Reset time 40 ms Reset ratio Typical 0 96 Retardation time 35 ms Trip time accuracy in...

Страница 33: ...menu views The large display offers increased front panel us ability with less menu scrolling and improved infor mation overview than with smaller LCD screens The large display is well suited for all...

Страница 34: ...e commands sent from a remote loca tion The relay supports the remote selection of lo cal remote mode via a binary input This feature fa cilitates for example the use of an external switch at the subs...

Страница 35: ...of 9 76 x 6 38 inches 248 x 162 mm Depth behind the panel 6 02 inches 153 mm 24 protection and control relay case and drawout unit For safety reasons the protection and control relay cases are provid...

Страница 36: ...SW Version 1 1 1 18 HW Version HW Version D Notes 1 SNTP is available for time sync with all Ethernet options IRIG B is available for time sync with all RS 485 options Both SNTP and IRIG B are availa...

Страница 37: ...tions such as relay signal configuration using the signal matrix tool and IEC 61850 communication configuration including horizontal relay to relay communication GOOSE The Protection and Con trol Rela...

Страница 38: ...nt Protection and control relay signal configuration signal matrix Modbus communication configuration communication management DNP3 communication configuration communication management communication m...

Страница 39: ...24 23 SO4 X115 9 6 10 12 11 13 2 14 3 4 7 8 15 16 17 250Vdc Boost From UPS Battery Return Common RS 485 RS 485 RS 485 COM X115 19 20 23 24 Phase A Position 22 21 BI 6 BI 4 BI 5 V 18 15 X130 1 2 3 9 U...

Страница 40: ...d fault protection high stage 1 Y XEFHPTOC3 Io 3 50N 2 Non directional time overcurrent ground fault protection high stage 2 Y XEFIPTOC2 Io 2 50N 3 Non directional instantaneous time overcurrent groun...

Страница 41: ...2 Load shed restoration source 1 stage 2 Y Total frequency protections included 4 Other protection PHIZ1 PHIZ1 HIZ High Impedance Fault Detector Y SCCBRBRF1 3I Io BF 50BFT Circuit breaker failure prot...

Страница 42: ...utputs Y PTGAPC1 PTGAPC1 PTGAPC1 Pulse timer 8 timers Y SPCGGIO1 SPCGGIO1 SPCGGIO1 Generic control points 16 outputs Y SRGAPC1 SRGAPC1 SRGAPC1 Set reset flip flops 8 outputs Y TOFGAPC1 TOFGAPC1 TOFGAP...

Страница 43: ...n date Version Update A December 2010 V1 1 Initial product version release B November 2011 V1 1 PG E Protocol counters added C August 2014 V1 2 Ability to read low currents added D July 2017 V1 2 Upda...

Страница 44: ...ervice group us abb com ABB Inc 4300 Coral Ridge Drive Coral Springs FL 33065 Phone 1 954 752 6700 Toll free 1 800 523 2620 Product support 1 954 825 0606 Toll free 1 800 222 1946 abb com mediumvoltag...