26
R E R6 20
A DVA N C ED R EC LOSER P R OT EC T I O N & CO N T R O L
—
Table 31. 27 technical data
—
Table 32. 59G technical data
—
Table 33. 47 technical data
Characterstic
Value
Operation accuracy
Depending on the frequency of the current measured: f
n
±2Hz
±1.5% of the set value or ±0.002 x V
n
Pickup time
1) 2)
V
Fault
= 0.9 x set Pickup value
Minimum
Typical
Maximum
62 ms
64 ms
66 ms
Reset time
< 40 ms
Reset ratio
Depends on the set Relative hysteresis
Retardation time
< 35 ms
Trip time accuracy in definite time mode
±1.0% of the set value or ±20 ms
Trip time accuracy in inverse time mode
±5.0% of the theoretical value or ±20 ms
3)
Suppression of harmonics
DFT: -50dB at f = n x f
n
, where n = 2, 3, 4, 5,…-
Characteristic
Value
Operation accuracy
Depending on the frequency of the current measured: f
n
±2Hz
±1.5% of the set value or ±0.002 x V
n
Pickup time
1) 2)
V
Fault
= 1.1 x set Pickup value
Minimum
Typical
Maximum
29 ms
31 ms
32 ms
Reset time
< 40 ms
Reset ratio
Typical 0.96
Retardation time
< 35 ms
Trip time accuracy in definite time mode
±1.0% of the set value or ±20 ms
Suppression of harmonics
DFT: -50dB at f = n x f
n
, where n = 2, 3, 4, 5,…-
Characteristic
Value
Operation accuracy
Depending on the frequency of the current measured: f
n
±2Hz
±1.5% of the set value or ±0.002 x V
n
Pickup time
1) 2)
Minimum
Typical
Maximum
V
Fault
= 1.1 x set Pickup value 29 ms
31 ms
32 ms
V
Fault
= 2.0 x set Pickup value 24 ms
26 ms
28 ms
Reset time
< 40 ms
Reset ratio
Typical 0.96
Retardation time
< 35 ms
Trip time accuracy in definite time mode
±1.0% of the set value or ±20 ms
Suppression of harmonics
DFT: -50dB at f = n x f
n
, where n = 2, 3, 4, 5,…-
1)
Pickup value = 1.0 x V
n
, Voltage before fault 1.1 x V
n
, f
n
= 50 Hz, undervoltage in one phase-to-phase with nominal frequency injected from random phase angle, results based on
statistical distribution of 1000 measurements
2)
Includes the delay of the signal output contact
3)
Minimum Pickup range = 0.50, Pickup range multiples in range of 0.90 to 0.20
1)
Ground voltage before fault 0.0 x V
n
, f
n
= 50 Hz, residual voltage with nominal frequency injected from radom phase angle, results based on statistical distribution of 1000 mea
-
surements
2)
Includes the delay of the signal output contact
1)
Negative sequence voltage before fault 0.0 x U
n
, f
n
= 50 Hz, negative sequence overvoltage with nominal frequency injected from random phase angle, results based on statistical
distribution of 1000 measurements
2)
Includes the delay of the signal output contact