Figure 9:
Connection example of the test equipment to the IED when test equipment is
connected to the transformer input module
6.5
Releasing the function to be tested
M11413-2 v6
Release or unblock the function to be tested. This is done to ensure that only the function or
the chain of functions to be tested are in operation and that other functions are prevented
from operating. Release the tested function(s) by setting the corresponding
Blocked
parameter under Function test modes to
No in the local HMI.
When testing a function in this blocking feature, remember that not only the actual function
must be activated, but the whole sequence of interconnected functions (from measuring
inputs to binary output contacts), including logic must be activated. Before starting a new test
mode session, scroll through every function to ensure that only the function to be tested (and
the interconnected ones) have the parameters
Blocked and eventually EvDisable set to No and
Yes respectively. Remember that a function is also blocked if the BLOCK input signal on the
corresponding function block is active, which depends on the configuration. Ensure that the
logical status of the BLOCK input signal is equal to 0 for the function to be tested. Event
function blocks can also be individually blocked to ensure that no events are reported to a
remote station during the test. This is done by setting the parameter
EvDisable to Yes.
Any function is blocked if the corresponding setting in the local HMI under Main
menu/Tests/Function test modes menu remains
On, that is, the parameter
Blocked is set to Yes and the parameter TestMode under Main menu/
Tests/IED test mode remains active. All functions that were blocked or
released in a previous test mode session, that is, the parameter
Test mode is
set to
On, are reset when a new test mode session is started.
Procedure
1.
Click the Function test modes menu.
The Function test modes menu is located in the local HMI under Main menu/Tests/
Function test modes.
2.
Browse to the function instance that needs to be released.
3.
Set parameter
Blocked for the selected function to No.
Section 6
1MRK 505 293-UEN B
Testing IED operation
40
Breaker protection REQ650
Commissioning manual
© Copyright 2013 ABB. All rights reserved